Page 42
VLC L
704
804
904
Power supply
V/ph/Hz
400 (±10%) / 3 / 50
Number of circuits
2
2
2
Capacity steps
%
20-50-70-100
25-50-75-100
28-50-78-100
Refrigerant
Type / GWP
R410A / 2.088
Charge 1/2
(1)
kg
21,5/21,5
24,5/24,5
27/27
tCO
2
eq
44,9/44,9
51,2/51,2
56,4/56,4
Compressor
Type
Scroll
Number
4
4
4
Start-up type
Direct
N°of loading stages
0/100
0/100
0/100
Condenser
Type
Coil
Refrigerant connections
Inlet diameter
inch
7/8”
7/8”
1 1/8”
Outlet diameter
inch
15/8”
15/8”
2 1/8”
Weights
Shipping weight
kg
1367
1494
1578
Additional Weights
HSE* versions
kg
30
30
40
Dimensions
Length
mm
4300
4300
4300
Width
mm
1100
1100
1100
Height
mm
2300
2300
2300
(1) The value is representing the contribution to the global refrigerant charge given by the standard unit only. Contribution of connection piping and remote evaporator
is not included here.
(*) High Efficiency Units (HSE) with inverter fans.
Technical data