8.3 Unit electrical data
(*) The dimensioning of the unit’s power cables is the responsibility of the installer, who shall consider: the rating, the maximum working
temperature in the room, the type of insulation and the cable laying, the maximum length of the power supply line.
VLH/VLC STD
704
804
904
1004
1104
1204
Rated voltage
V/ph/Hz
400 (±10%) /3/50
Max. absorbed power
kW
80,8
96,4
105,2
112,0
130,0
148,0
Rated current
A
112,0
120,0
142,0
160,0
172,0
184,0
Max. current FLA
A
186,0
172,0
193,0
210,0
239,0
268,0
Max. start-up current LRA
A
350,0
357,0
378,0
433,5
486,0
515,0
External fuses
A
250,0
250,0
250,0
250,0
315,0
315,0
Max. cable section (*)
mm
2
3x120
3x120
3x120
3x120
3x185
3x185
Exchanger resistance
Rated voltage
V/ph/Hz
230/ (± 10%)/1/50
Max. absorbed power
W
130
Technical data
VLH/VLC L
704
804
904
1004
1104
1204
Rated voltage
V/ph/Hz
400 (±10%) /3/50
Max. absorbed power
kW
78,6
94,2
102,2
109,0
127,0
145,0
Rated current
A
106,9
114,9
135,2
153,2
165,2
177,2
Max. current FLA
A
180,9
166,9
186,2
203,2
232,2
261,2
Max. start-up current LRA
A
344,9
351,9
371,2
426,7
479,2
508,2
External fuses
A
250,0
250,0
250,0
250,0
315,0
315,0
Max. cable section (*)
mm
2
3x120
3x120
3x120
3x120
3x185
3x185
Exchanger resistance
Rated voltage
V/ph/Hz
230/ (± 10%)/1/50
Max. absorbed power
W
130
VLH/VLC S
704
804
904
1004
1104
1204
Rated voltage
V/ph/Hz
400 (±10%) /3/50
Max. absorbed power
kW
78,6
94,2
102,2
109,0
127,0
145,0
Rated current
A
106,9
114,9
135,2
153,2
165,2
177,2
Max. current FLA
A
180,9
166,9
186,2
203,2
232,2
261,2
Max. start-up current LRA
A
344,9
351,9
371,2
426,7
479,2
508,2
External fuses
A
250,0
250,0
250,0
250,0
315,0
315,0
Max. cable section (*)
mm
2
3x120
3x120
3x120
3x120
3x185
3x185
Exchanger resistance
Rated voltage
V/ph/Hz
230/ (± 10%)/1/50
Max. absorbed power
W
130