Page 49
English
VLH/VLC HSE STD
704
804
904
1004
1104
1204
Rated voltage
V/ph/Hz
400 (±10%) /3/50
Max. absorbed power
kW
82,6
98,2
107,6
114,4
132,4
150,4
Rated current
A
112,3
120,3
142,4
160,4
172,4
184,4
Max. current FLA
A
186,3
172,3
193,4
210,4
239,4
268,4
Max. start-up current LRA
A
350,0
357
378
434
486
515
External fuses
A
250
250
250
250
315
315
Max. cable section (*)
mm
2
3x120
3x120
3x120
3x120
3x185
3x185
Exchanger resistance
Rated voltage
V/ph/Hz
230/ (± 10%)/1/50
Max. absorbed power
W
130
VLH/VLC HSE L
704
804
904
1004
1104
1204
Rated voltage
V/ph/Hz
400 (±10%) /3/50
Max. absorbed power
kW
82,6
98,2
107,6
114,4
132,4
150,4
Rated current
A
112,3
120,3
142,4
160,4
172,4
184,4
Max. current FLA
A
186,3
172,3
193,4
210,4
239,4
268,4
Max. start-up current LRA
A
350
357
378
434
486
515
External fuses
A
250
250
250
250
315
315
Max. cable section (*)
mm
2
3x120
3x120
3x120
3x120
3x185
3x185
Exchanger resistance
Rated voltage
V/ph/Hz
230/ (± 10%)/1/50
Max. absorbed power
W
130
VLH/VLC HSE S
704
804
904
1004
1104
1204
Rated voltage
V/ph/Hz
400 (±10%) /3/50
Max. absorbed power
kW
82,6
98,2
107,6
114,4
132,4
150,4
Rated current
A
112,3
120,3
142,4
160,4
172,4
184,4
Max. current FLA
A
186,3
172,3
193,4
210,4
239,4
268,4
Max. start-up current LRA
A
350
357
378
434
486
515
External fuses
A
250
250
250
250
315
315
Max. cable section (*)
mm
2
3x120
3x120
3x120
3x120
3x185
3x185
Exchanger resistance
Rated voltage
V/ph/Hz
230/ (± 10%)/1/50
Max. absorbed power
W
130
Technical data
(*) The dimensioning of the unit’s power cables is the responsibility of the installer, who shall consider: the rating, the maximum working
temperature in the room, the type of insulation and the cable laying, the maximum length of the power supply line.