TIC-4M MANUAL
13
Parameter Setting
Category
Display
Set.value
Start value
Contents
Equip.
Number
1~99
1
Set the address by setting the equipment number when using Remote
Supervisory Control.
Power
Recovery
OFF /
1~250sec
5 sec
Set the delay time for the blackout and the driver to operate the concurrent
controller.
Apply differential time to multiple equipment simultaneously to prevent loss of power
after returning to power.
OFF : No outage returns.
Stop
Delay
OFF /
1~250sec
60 sec
During shutdown of the equipment, all outputs are stopped sequentially
and the fan completes after the shutdown delay.
OFF : Output Off without stop delay.
Cooling
Delay
1~250sec
5 sec
Set the delay time for the compressor output to ON after the fan output has
been put on the cooling condition.
Heating
Delay
1~250sec
3 sec
Set the delay period for the auxiliary heater output after the fan output is
turned on in the heating conditions.
Comp.
Restart
OFF /
1~250sec
20 sec
Set standby delay setting for the Compton output to ON after the Comp
output is turned ON and OFF.
Fan Mode
ON / Au
ON
Set the air flow mode.
ON : The fan output is ON whenever the controller is in operation.
Auto:flower is driven in conjunction with the Compton output output output.
Manual Menu
Defrost Setting
Category
Display
Set.value
Start value
Contents
Defrost
Mode
OFF / FAN
/ H.t
H.t
Set defrosting mode when defrosting.
OFF: Defrosting prohibited. / FAN: Only blower operates during defrost time after
driving cycle stop.
H.t: In defrosting condition, blower stops after pump down and defrost heater output
is ON during defrost time.
Defrost
Cycle
1~24H
6H
The cycle at which defrosting begins during operation
Defrosting
Time
1~60min
20 min
Set defrosting time.
Fan Delay
after
Defrosting
OFF /
1~250sec
60 sec
Setting delay time of blowing operation after defrost termination.
OFF: Fan output operation without delay after defrosting.
Cooling
Delay After
Defrosting
OFF /
1~250sec
OFF
Cooling operation delay time after defrost termination.
OFF: Cooling operation without delay after defrosting.
High Temp.
Alarm
Delay After
Defrosting
OFF /
1~250sec
30 sec
Set the high alarm detection time after defrosting operation.
OFF: High temperature alarm is detected without delay after defrosting.