TIC-4M MANUAL

13

Parameter Setting

Category

Display

Set.value

Start value

Contents

Equip.

Number

1~99

1

Set the address by setting the equipment number when using Remote 
Supervisory Control.

Power

Recovery

OFF / 

1~250sec

5 sec

Set the delay time for the blackout and the driver to operate the concurrent 
controller.

Apply differential time to multiple equipment simultaneously to prevent loss of power    

after returning to power.
OFF : No outage returns.

Stop

Delay

OFF / 

1~250sec

60 sec

During shutdown of the equipment, all outputs are stopped sequentially 
and the fan completes after the shutdown delay.

OFF : Output Off without stop delay.

Cooling 

Delay

1~250sec

5 sec

Set the delay time for the compressor output to ON after the fan output has 
been put on the cooling condition.

Heating 

Delay

1~250sec

3 sec

Set the delay period for the auxiliary heater output after the fan output is 
turned on in the heating conditions.

Comp.

Restart

OFF / 

1~250sec

20 sec

Set standby delay setting for the Compton output to ON after the Comp 
output is turned ON and OFF.

Fan Mode

ON / Au

ON

Set the air flow mode.

ON : The fan output is ON whenever the controller is in operation.
Auto:flower is driven in conjunction with the Compton output output output.

Manual Menu

Defrost Setting

Category

Display

Set.value

Start value

Contents

Defrost

Mode

OFF / FAN 

/ H.t

H.t

Set defrosting mode when defrosting. 

OFF: Defrosting prohibited. / FAN: Only blower operates during defrost time after 
driving cycle stop. 
H.t: In defrosting condition, blower stops after pump down and defrost heater output 
is ON during defrost time.

Defrost

Cycle

1~24H

6H

The cycle at which defrosting begins during operation

Defrosting

Time

1~60min

20 min

Set defrosting time.

Fan Delay 

after 

Defrosting

OFF /

1~250sec

60 sec

Setting delay time of blowing operation after defrost termination. 

OFF: Fan output operation without delay after defrosting.

Cooling

Delay After

Defrosting

OFF /

1~250sec

OFF

Cooling operation delay time after defrost termination. 

OFF: Cooling operation without delay after defrosting.

High Temp. 

Alarm 

Delay After 

Defrosting

OFF /

1~250sec

30 sec

Set the high alarm detection time after defrosting operation. 

OFF: High temperature alarm is detected without delay after defrosting.

Summary of Contents for TIC-4M

Page 1: ...301 Bucheon Techno park 345 Seokcheon ro Bucheon si Gyeonggi do Republic of Korea Phone 10 32 324 2777 Fax 10 32 324 2717 Homepage www ss22 com TIC 4M USER MANUAL Compact Temperature Controller VER 1...

Page 2: ...nlight 4 Places affected by electromagnetic waves 5 Places where high temperature or humidity is high sites with over 85 of ambient humidity 6 Places where dust and salt are plentiful Precautions on i...

Page 3: ...o input 2 ports by setting the temperature monitoring port according to the setting conditions and customize it to suit the site conditions This is a product that is equipped with a built in communica...

Page 4: ...ent Controller 1EA TIC 4M Bracket 2EA Normal type NTC sensor 1EA SCTS 01 Sensor Component Advanced NTC sensor 1EA SCTS 02 High temperature type NTC sensor 1EA SCTS 03 Well type NTC sensor 1EA SCTS 04...

Page 5: ...A Relay output Output Port 4 Port Input power output Input Port 2 Port Non power source Changeable to temperature sensor input Sensor Port 1 Port NTC 10K at 25 1 Communication Port 1 Port RS 485 Opera...

Page 6: ...Advanced type cable sensor SCTS 02 Temperature Range 45 105 NTC 10K at 25 0 5 Sensor Weight 37 5g Cable 3M standard High temperature type cable sensor SCTS 03 Temperature Range 45 150 NTC 10K at 25 1...

Page 7: ...TIC 4M MANUAL 7 Front view Product Dimension Top view Side view Front view Side view Bracket Dimension Controller Dimension Display 42 5 x 20 3...

Page 8: ...mm x 30 mm in accordance with the specification insert the controller into the perforated holes 2 Push the controller onto the wall and secure it firmly by pushing the bracket When disconnecting remov...

Page 9: ...duct Wiring Diagram L L Sensor INPUT COM DI1 DI2 DO1 DO2 DO3 DO4 220VAC Relay 220VAC 5A COMP FAN DEF AL circuit breaker R N 220VAC Set output function DO3 DO4 Input function input contact setting poss...

Page 10: ...up screen Alarm generated for 2 seconds by pressing for 2 seconds DEF UP key Defrost ON OFF Detailed menu movement and increased menu data value PWR DOWN key Controller power ON OFF Detailed menu move...

Page 11: ...t the current temperature of 20 or below Heating Deviation OFF 0 1 9 9 OFF The function of setting up the heater while operating the controller while operating the controller OFF Without auxiliary hea...

Page 12: ...eter Set Main Display Cooling Delay After Defrosting Fan Delay after Defrosting Defrosting Time Defrost Cycle Defrost Mode Defrost Set High Temp Alarm Heater Alarm Comp Alarm Alarm Set Comp Integratio...

Page 13: ...e Comp output is turned ON and OFF Fan Mode ON Au ON Set the air flow mode ON The fan output is ON whenever the controller is in operation Auto flower is driven in conjunction with the Compton output...

Page 14: ...rature an alarm is generated If the temperature is 1 degree below the set point of the high temperature alarm the alarm is cleared Heater operation stops when high temperature alarm occurs OFF Alarm i...

Page 15: ...een Input Contact 1 Input 2 Set Input 1 Set Output 4 Set Output 3 Set System Set Comp Alarm Return Alarm Set Temp Filtering Temp Display Interval Display Set Input Contact 2 Temp Sensor Calibration Lo...

Page 16: ...ct method of the port n o Operates normally when the corresponding input is detected n C Normal operation should be performed if no corresponding input is detected during operation Alarm Setting Categ...

Page 17: ...of the operation alarm Normal operation High Temp Alarm Alarm occurs when control temperature is higher than high temperature alarm during controller operation Heating operation stops when an alarm oc...

Page 18: ...Reset Push for more the 2sec Notice All settings on the controller will return to their initial state Push for more the 10sec Main Screen Factory Reset Menu Factory Reset Complete Factory Reset Cance...

Page 19: ...he precautions and instructions specified in the manual For more information on the service refer to the product warranty statement in the user manual 1 Please note that any problem failure caused by...

Page 20: ...o generate noise 4 Noise source may occur due to contact switching Among the causes of the above noise sources the noise that the system manufacturer can reduce is only the contact switching noise Con...

Page 21: ...to install close to the line where the noise is generated and the line where the noise is generated by placing a plated steel barrier 2 If you need a lot of noisy power in area A it is recommended to...

Page 22: ...il s positive or negative terminal or an equivalent snubber capacitor Generally 100 and 0 1Uf are connected in series but it needs to be adjusted according to the load power How to Identify the Source...

Page 23: ...TIC 4M MANUAL 23...

Reviews: