TIC-4M MANUAL
16
Engineer Menu
System Setting
Category
Display
Set.value
Start value
Contents
Output 3
Set.
H.T / dEF
Def
Output The function to set the output of 3 port.
H.t (heater) / dEF (defrost)
Output 4
Set.
AL / dEF
AL
Output The function to set the output of 4 ports.
dEF (defrost) / AL (comprehensive alarm)
Input 1 Set.
Fan / C.P
/ H.t / Def
/ rE
Def
Input 1 A function that sets the alarm and status functions of the port.
FAn (fan) / C.P (compressor) / H.t (heater) / dEF (defrost) / rE (remote)
Input 2 Set.
Fan / C.P
/ H.t / Def
/ rE
rE
Input 2 Function to set alarm and status function of port.
FAn (fan) / C.P (compressor) / H.t (heater) / dEF (defrost) / rE (remote)
Input
Contact 1
n.o / n.C
n.C
Input 1 The function to set the input contact method of the port.
n.o: Operates normally when the corresponding input is detected.
n.C: Normal operation should be performed if no corresponding input is detected
during operation.
Input
Contact 2
n.o / n.C
n.C
Input 2 Set the input contact method of the port.
n.o: Operates normally when the corresponding input is detected.
n.C: Normal operation should be performed if no corresponding input is detected
during operation.
Alarm Setting
Category
Display
Set.value
Start value
Contents
Comp.
Alarm
Return
Su / Au
Su
Function to set Comp alarm release method.
Su (manual return) / Au (automatic return)
Display Setting
Category
Display
Set.value
Start value
Contents
Temp.
Display
Interval
0.1~
5.0 sec
0.5 sec
The function to set the change time interval of the current control
temperature.
Temp.
Filtering
32 / 64 /
128 times
128 times
Function to set temperature sensor sensitivity.
Temp.
Sensor
Calibration
-9.9~
9.9℃
0.0℃
Function to correct the temperature value when the current temperature
differs from the actual temperature value in the room.
When the actual temperature is 20.0℃ and the display temperature is 18.0℃, if the
correction value is changed to 2.0℃, Converted to 20.0℃.
Upper
Temp.
Setting
-40.0~
150.0℃
50.0℃
Function to set upper limit temperature range of set temperature.
Lower
Temp.
Setting
-40.0~
150.0℃
-40.0℃
Function to set lower limit temperature range of set temperature.