4
When power is applied
WARNING
z
Do not attempt to install or remove input or out put connectors of inverter when the
power supply is turned on. Otherwise, the inverter may be damaged due to the
surge peak caused by the insertion or removal of power.
z
When momentary power loss is longer than 2 seconds (the large of horse power,
the longer of time), the inverter does not have enough storage power to control the
circuit; Therefore, when power is regenerated, the operation of the inverter is
based on the setup of F_10 and the condition of external switch, this is considered
to be
「
restart
」
in the following paragraphs.
z
When the momentary power loss is short, the inverter still has enough storage
power to control the circuit; therefore, when power is regenerated, the inverter will
automatically start operation again depends on the setup of F_23.
When restart the inverter, the operation of the inverter is based on the setup of
F_10 and the condition of external switch (FWD/REV button). Attention: the
restart operation is irrelevant with F_23/F_24.
(1) When F_10=0, the inverter will not start after restart.
(2) When F_10=1 and the external switch (FWD/REV button) is OFF, the inverter
will not start after restart.
(3) When F_10=1 and the external switch (FWD/REV button) is ON, the inverter
will start automatically after restart. Attention: Base on safety reason, please
turn off the external switch (FWD/REV button) after power loss to avoid
possible damage to the machine and the human body after sudden
regeneration of power.