F_19: Multifunctional input terminal 1 function = 1~ 5(1~6:CPU version
v1.9 and above)
F_20: Multifunctional input terminal 2 function = 1~ 5(1~6:CPU version
v1.9 and above)
1. F_19=1 or F_20 =1: JOG control (refer to F_09)
2. F_19, F_20 =2 or 6 Multi-speed control:
F_19=2 & F_20=6:
TM2 SP1 Terminal
TM2 RESET Terminal
Output frequency
ON OFF
F_08
OFF ON
F_26
ON ON
F_27
F_19=6
﹠
F_20=2:
TM2 SP1 Terminal
TM2 RESET Te
r
minal Output
frequency
ON OFF
F_26
OFF ON
F_08
ON ON
F_27
NOTE: F_19,F_20=2 or 6 are new function for CPU version v1.9 and above.
3. F_19, F_20 =3: External emergency stop
When the external emergency stop signal is activated, the inverter proceeds to decelerate and
stop, (ignoring the setting of F_14). The inverters E.S. light will flash after stopping. After the
emergency stop signal is deactivated, turn the RUN switch OFF and then ON again to cycle it.
(F_10 =1) Or, push the RUN key (F_10=0). The inverter will then resume operation and restart. If
the emergency stop signal is removed before the inverter stops, the inverter will still execute the
emergency stop.
4. F_19, F_20 =4: External Base Block (Immediate Shut Down)
When the external base block signal is activated, the inverter output will be immediately shut off
(ignoring the setting of F_14) and flash b.b. Light. After the base block signal is deactivated, turn
the RUN switch OFF and then ON again (F_10 = 1) or push the RUN key (F_10=0), the inverter will
restart from the original starting frequency.
Time
Run/Stop on off on
F_19=3 off on
F_02