INITiate:CONTinuous{OFF|ON|0|1}(?)
Description
This command will set the output in continuous operation and interrupted operation. The run mode
commands will affect the 5251 only after it will be set to interrupted operation.
Parameters
Name
Type
Default
Description
ON
Discrete
ON
Disables all interrupted modes and forces the
continuous run mode
OFF
Discrete
Select the interrupted run mode. While in this switch
option, you can program the 5251 to operate in
triggered, gated, or counted burst run modes.
Response
The 5251 will return OFF, or ON depending on the selected option.
TRIGger:BURSt{OFF|ON|0|1}(?)
Description
This command will toggle the counted burst run mode on and off. This command will affect the 5251 only
after it will be set to INIT:CONT OFF.
Parameters
Name
Type
Default
Description
OFF
Discrete
OFF
Turns the burst run mode off.
ON
Discrete
Enables the counted burst run mode. Burst count is
programmable using the TRIG:BURS:COUN
command.
Response
The 5251 will return OFF, or ON depending on the selected option.
TRIGger:BURSt:COUNt<burst>(?)
Description
This function sets the number of cycles when the Burst Mode is on. Use the init:cont off;:trig:burs on
commands to select the Burst Mode.
Parameters
Name
Range
Type
Default
Description
<burst>
1 to 1M
Numeric
(integer)
1
Programs the burst count.
Response
The 5251 will return the present burst count value.
Summary of Contents for 5251
Page 17: ...List of Figures continued xiv...
Page 35: ...TE5251 User Manual 1 18 This page was intentionally left blank...
Page 37: ...TE5251 User Manual 2 2...
Page 134: ...TE5251 User Manual 3 82 Figure 3 62 Log File Example...
Page 222: ...TE5251 User Manual 4 88 This page was left intentionally blank...
Page 258: ...TE5251 User Manual 5 36 This page was intentionally left blank...
Page 288: ...TE5251 User Manual 6 30 This page was intentionally left blank...
Page 289: ...1 Appendices Appendix Title Page A Specifications A 1...
Page 290: ...TE5251 User Manual 2...