To change operating mode and settings:

a. Press and hold the 

SET

button for 3 seconds until the operating mode on the

LCD begins  to flash.

b. Use the 

UP

or 

DOWN

buttons to scroll through the 5 operating mode options.

When the desired mode flashes on the LCD, press the 

SET

button. The LCD will

begin to flash either temperature or speed setting options, whichever applies.

c. Use the 

UP

button to increase temperature or speed settings. Use the 

DOWN

button  to  decrease  temperature  or  speed  settings.  When  the  desired  setting

flashes, press the 

SET

button.

d. Your programming is complete and the operating mode and setting will appear

on the LCD screen.

US or Metric Units

The VT2218 can be programmed to display in either US or Metric units. The default is US units. To change units to Metric, use

the programming steps above to scroll to 

SETUP  MODE

. Press 

SET

and the default US units will begin to flash. Press the

DOWN

button to change to Metric. The 

UP

button will change back to US units. When the desired units are flashing, press the

SET

button.

7.    Reading the LCD screen:

The LCD screen will display important diagnostic information:

Operating Mode

- Delta-T, Constant Speed, Set Point Heat, Set Point Cool, or Boiler Protection.

Setting

- Delta-T target, Fixed speed, Set Point target temperature, or Boiler Protection target minimum temperature.

Watts

- Power usage of the circulator.

GPM

- Flowrate through system.

S

Supply

sensor temperature.

R (or BP)

Return

sensor temperature (or 

Boiler Return

temperature in Set Point mode).

8.    Sequence of Operation - How the VT2218 Works:

Delta-T Mode (5°F - 50°F, default = 20°F)

In Delta-T mode, the VT2218 will start at the lowest speed. If it reads a temperature differential (∆T)  LESS than its target, it will    

gradually increase speed through a 3 minute “Start Cycle” to its highest speed, until target ∆T is reached. “Start Cycle” will dis-

play on the LCD screen in place of “Watts”. If ∆T is GREATER than target, the pump will immediately go into Variable Speed

operation and vary speed to maintain the target ∆T.

Constant Speed Mode (Speeds 1, 2, 3, 4, default = Speed 4)

In Constant Speed mode, the VT2218 will always start and run at the pre-set Speed Level (1 through 4). Only watts will be dis-

played. Temperature sensors are not active in this mode.

Set Point Heat Mode (with Boiler Protection (BP) option) (50°F - 220°F, default = 105°F, BP default = 140°F)

In Set Point Heat mode, the VT2218 will start at the lowest speed. It then immediately switches to Variable Speed operation,

increasing speed to raise temperature or decreasing speed to lower temperature and maintain the Set Point Heat target.
If Boiler Protection (BP) option is used with Set Point Heat, the return sensor (R) will over-ride the supply sensor (S) and slow

the pump down if boiler return water temperature falls below BP target (for example 140°F). Once the return sensor reads BP

target, the pump will then speed up to reach the supply temperature Set Point target. In this mode the return sensor will read

“BP” on the LCD.

Set Point Cool Mode (32°F - 100°F, default = 70°F)

In Set Point Cool mode, the VT2218 operates in the reverse of Set Point Heat. It will start at the lowest speed. It then immediately

switches to Variable Speed operation, increasing speed to lower temperature or decreasing speed to raise temperature and

maintain the Set Point Cool target.

Boiler Protection (BP)  Mode (100°F - 160°F, default = 140°F)
Note:

Boiler Protection Mode is designed to maintain a minimum boiler temperature to prevent flue gas condensation.

CAUTION: Do not attempt to remove LCD panel from circulator. Serious damage to circulator electronics may
result.
ATTENTION: N'essayez pas de retirer le panneau de LCD du circulateur. Des dommages s

é

rieux à l'électron-

ique du circulateur peuvent en r

é

sulter.

6

Summary of Contents for 00e VT2218 Series

Page 1: ...one Valve Control or SR Switching Relay for ON OFF operation Integral Flow Check IFC is included in carton Simply press into discharge flange if required Nut capture feature on flanges for easier fit up Whisper quiet operation BIO Barrier protects the pump from system contaminants SureStart automatic unblocking mode Optional 2 way flange model available to reduce SKU s and provide universal fit up...

Page 2: ...E RECOMMENDED PURGING STEPS 1 CLOSE V1 PV4 V2 2 OPEN V3 3 OPEN FF VALVE 4 OPEN V2 PV4 TO PURGE LAST ZONE FIRST ZONE 3 5 CLOSE FF VALVE 6 CLOSE V2 PV4 7 REPEAT STEPS 1 TO 6 FOR EACH ADDITIONAL ZONE PURGE ZONE 1 LAST 8 OPEN V1 WHEN ALL ZONES ARE PURGED 9 ADJUST SYSTEM TO DESIRED OPERATING FILL PRESSURE IF REQUIRED ...

Page 3: ... PURGING STEPS 1 CLOSE V1 PV4 V2 2 OPEN V3 AND ZV3 3 OPEN FF VALVE 4 OPEN V2 PV4 TO PURGE LAST ZONE FIRST ZONE 3 5 CLOSE FF VALVE 6 CLOSE V2 PV4 7 REPEAT STEPS 1 TO 6 FOR EACH ADDITIONAL ZONE PURGE ZONE 1 LAST 8 OPEN V1 WHEN ALL ZONES ARE PURGED 9 ADJUST SYSTEM TO DESIRED OPERATING FILL PRES SURE IF REQUIRED 10 MOVE ALL ZV TO CLOSED AUTOMATIC POSITION ...

Page 4: ...rential T Set Point Heat Varies speed to maintain a fixed temperature Boiler Protection Option Decreases speed to protect boiler from low return water temperature and flue gas condensation Boiler Protection Increases speed to protect boiler from low return water temperature and flue gas condensation Heating or Chilled Water Cooling Set Point Heat Decreases speed on temperature rise Set Point Cool ...

Page 5: ...ta T operating mode with a 20 F temperature differential setting If this is your desired operating mode and Delta T setting no programming changes are required CAUTION Never run the circulator dry or permanent damage may result ATTENTION Ne laissez jamais le circulateur tourner à sec des dommages permanents peuvent en résulter The VT2218 has 5 Operating Modes Delta T Varies speed to maintain a fix...

Page 6: ...Start Cycle to its highest speed until target T is reached Start Cycle will dis play on the LCD screen in place of Watts If T is GREATER than target the pump will immediately go into Variable Speed operation and vary speed to maintain the target T Constant Speed Mode Speeds 1 2 3 4 default Speed 4 In Constant Speed mode the VT2218 will always start and run at the pre set Speed Level 1 through 4 On...

Page 7: ...n ERROR CODE DESCRIPTION CORRECTIVE ACTION SENSOR 1 MISSING Supply sensor disconnected Reconnect sensor SENSOR 2 MISSING Return sensor disconnected Reconnect sensor SENSOR 1 SHORTED Bad sensor Replace sensor SENSOR 2 SHORTED Bad sensor Replace sensor AC INPUT UNDER VOLTAGE Low voltage problem Check power supply AC INPUT OVER VOLTAGE High voltage problem Check power supply LOCKED ROTOR Probable loc...

Page 8: ...t or for any application restrictions consult the applicable Taco instruction sheets or contact Taco at 401 942 8000 Taco reserves the right to provide replacement products and parts which are substantially similar in design and functionally equivalent to the defective product or part Taco reserves the right to make changes in details of design construc tion or arrangement of materials of its prod...

Reviews: