9.    Troubleshooting the error codes:

SureStart

Feature:

The VT2218 is programmed with an automatic unblocking feature. In the case of a locked rotor condition, it will

attempt to unblock the rotor with a series of rapid oscillating actions. It will repeat this process up to 100 times. If still locked after

100 attempts, “LOCKED ROTOR” will apppear on the LCD. See error code listing below.
Listed below are potential diagnostic error codes which will appear on the LCD display in case of a malfunction.

Testing the Sensors

A good quality test meter capable of measuring up to 5,000 k

Ω

(1 k

Ω

= 1000

Ω

) is required to measure the sensor resistance. In

addition to this, the actual temperature must be measured with a good quality digital thermometer.
First measure the temperature using the thermometer and then measure the resistance of the sensor at the VT2218. The wires from

the sensor must not be connected to the circulator while this test is performed. The wiring terminals are easily removed by pulling

them from the circulator. Using the chart below, estimate the temperature measured by the sensor. The sensor and thermometer

readings should be close. If the test meter reads a very high resistance, there may be a broken wire, a poor wiring connection or a

defective sensor. If the resistance is very low, the wiring may be shorted, there may be moisture in the sensor or the sensor may be

defective. To test for a defective sensor, measure the resistance directly at the sensor location.

ERROR CODE*

DESCRIPTION

CORRECTIVE ACTION

SENSOR 1 MISSING

Supply sensor disconnected.

Reconnect sensor.

SENSOR 2 MISSING

Return sensor disconnected.

Reconnect sensor.

SENSOR 1 SHORTED

Bad sensor.

Replace sensor.

SENSOR 2 SHORTED

Bad sensor.

Replace sensor.

AC INPUT UNDER VOLTAGE Low voltage problem.

Check power supply.

AC INPUT OVER VOLTAGE

High voltage problem.

Check power supply.

LOCKED ROTOR

Probable locked rotor or motor failure.

Replace pump.

MOTOR OVER CURRENT

Possible locked rotor or motor over current.

Replace pump.

OVER TEMPERATURE

PC Board overheating.

Pump will reduce current and speed until PCB

temperature is acceptable. If speed falls below

1650 RPM, pump will stop on safety. Cycle AC

power OFF/ON to restart.

SPEED

TACO

GRUNDFOS

WILO

B & G/XYLEM

ARMSTRONG

1

003

Alpha-15-55 (1)

-

-

-

2

006

Alpha-15-55 (2)

-

-

Compass (1)

3

007

008

0015-1

0015-2

UP-15-42

UPS-15-58 (1)

UPS-15-58 (2)

Star S-2 (1)

Star S-21 (2)

NRF-25 (1)

NRF-25 (2)

Astro 230 (1)

Astro 230 (2)

Compass (2)

4

0015-3

UPS-15-58 (3)

Alpha-15-55 (3)

Star S-21 (3)

NRF-25 (3)

Eco-Vario

Astro 230 (3)

Compass (3)

Pump Cross Reference (Constant Speed Mode):

Temperature

Resistance

Temperature

Resistance

Temperature

Resistance

Temperature

Resistance

°F

°C

Ω

°F

°C

Ω

°F

°C

Ω

°F

°C

Ω

-30

-34

234,196

30

-1

34,558

90

32

7,334

150

66

2,045

-20

-29

165,180

40

4

26,099

100

38

5,828

160

71

1,689

-10

-23

118,018

50

10

19,900

110

43

4,665

170

77

1,403

0

-18

85,362

60

16

15,311

120

49

3,760

180

82

1,172

10

-12

62,465

70

21

11,883

130

54

3,050

190

88

983

20

-7

46,218

80

27

9,299

140

60

2,490

200

93

829

MODE

TACO

GRUNDFOS

WILO

B & G/XYLEM

ARMSTRONG

Delta-T

008-VDT

Alpha 15-55

Stratos Eco 16FX

Eco-Auto 19-14

Compass 2020

Pump Cross Reference (Delta-T Mode):

Flashing Displayed on LCD

Summary of Contents for 00e VT2218 Series

Page 1: ...one Valve Control or SR Switching Relay for ON OFF operation Integral Flow Check IFC is included in carton Simply press into discharge flange if required Nut capture feature on flanges for easier fit up Whisper quiet operation BIO Barrier protects the pump from system contaminants SureStart automatic unblocking mode Optional 2 way flange model available to reduce SKU s and provide universal fit up...

Page 2: ...E RECOMMENDED PURGING STEPS 1 CLOSE V1 PV4 V2 2 OPEN V3 3 OPEN FF VALVE 4 OPEN V2 PV4 TO PURGE LAST ZONE FIRST ZONE 3 5 CLOSE FF VALVE 6 CLOSE V2 PV4 7 REPEAT STEPS 1 TO 6 FOR EACH ADDITIONAL ZONE PURGE ZONE 1 LAST 8 OPEN V1 WHEN ALL ZONES ARE PURGED 9 ADJUST SYSTEM TO DESIRED OPERATING FILL PRESSURE IF REQUIRED ...

Page 3: ... PURGING STEPS 1 CLOSE V1 PV4 V2 2 OPEN V3 AND ZV3 3 OPEN FF VALVE 4 OPEN V2 PV4 TO PURGE LAST ZONE FIRST ZONE 3 5 CLOSE FF VALVE 6 CLOSE V2 PV4 7 REPEAT STEPS 1 TO 6 FOR EACH ADDITIONAL ZONE PURGE ZONE 1 LAST 8 OPEN V1 WHEN ALL ZONES ARE PURGED 9 ADJUST SYSTEM TO DESIRED OPERATING FILL PRES SURE IF REQUIRED 10 MOVE ALL ZV TO CLOSED AUTOMATIC POSITION ...

Page 4: ...rential T Set Point Heat Varies speed to maintain a fixed temperature Boiler Protection Option Decreases speed to protect boiler from low return water temperature and flue gas condensation Boiler Protection Increases speed to protect boiler from low return water temperature and flue gas condensation Heating or Chilled Water Cooling Set Point Heat Decreases speed on temperature rise Set Point Cool ...

Page 5: ...ta T operating mode with a 20 F temperature differential setting If this is your desired operating mode and Delta T setting no programming changes are required CAUTION Never run the circulator dry or permanent damage may result ATTENTION Ne laissez jamais le circulateur tourner à sec des dommages permanents peuvent en résulter The VT2218 has 5 Operating Modes Delta T Varies speed to maintain a fix...

Page 6: ...Start Cycle to its highest speed until target T is reached Start Cycle will dis play on the LCD screen in place of Watts If T is GREATER than target the pump will immediately go into Variable Speed operation and vary speed to maintain the target T Constant Speed Mode Speeds 1 2 3 4 default Speed 4 In Constant Speed mode the VT2218 will always start and run at the pre set Speed Level 1 through 4 On...

Page 7: ...n ERROR CODE DESCRIPTION CORRECTIVE ACTION SENSOR 1 MISSING Supply sensor disconnected Reconnect sensor SENSOR 2 MISSING Return sensor disconnected Reconnect sensor SENSOR 1 SHORTED Bad sensor Replace sensor SENSOR 2 SHORTED Bad sensor Replace sensor AC INPUT UNDER VOLTAGE Low voltage problem Check power supply AC INPUT OVER VOLTAGE High voltage problem Check power supply LOCKED ROTOR Probable loc...

Page 8: ...t or for any application restrictions consult the applicable Taco instruction sheets or contact Taco at 401 942 8000 Taco reserves the right to provide replacement products and parts which are substantially similar in design and functionally equivalent to the defective product or part Taco reserves the right to make changes in details of design construc tion or arrangement of materials of its prod...