background image

iWorx® HPU Series

2

 

502-025, Effective: April 17, 2013 

© 2013 Taco Electronic Solutions, Inc.

SRAM:

 8

 Kilobytes 

Termination:

 0.197” (5.0 mm) Pluggable Terminal Blocks, 14-22

 AWG

Temperature:

 32

 

°F to 140

 °F 

(0

 

°C to 60

 °C)

Humidity:

 0 to 90%, non-condensing

UL Listed

 for US and Canada, Energy Management Equipment PAZX and PAZX7 

FCC

 Part 15 Class A compliant

Equipment Location

Abide by all warnings regarding equipment location provided in this document. This equipment is suitable for 
indoor use only. Preferably, or as required by National Electrical Code, the unit is intended to be installed within 
an electrical control enclosure. Operate where ambient temperatures do not exceed 140

 

°F (60

 

°C) or fall 

below 32

 °F 

(0

 

°C) and relative humidity does not exceed 90%, non-condensing.

If the equipment is to be installed outdoors, it must be contained within a protective enclosure that maintains internal tem-
perature and humidity within the ranges specified for this equipment.

The equipment must be installed within 500 feet of all input peripherals (smoke detectors, sensors, etc.) that are connected 
to the equipment.

Avoid locations where corrosive fumes, excessive moisture, vibration or explosive vapors are present.

Avoid electrical noise interference. Do not install near large contactors, electrical machinery, or welding equipment.

Selecting a Power Source

This equipment requires a UL recognized Class 2 external power source (not supplied) to operate. The controller power 
input requires a voltage of 24

 Volts

 AC.

To calculate power source current requirements, add the power consumption of all peripheral devices to that of the control-
ler.

The controller and sensor power supplies can use the same power source. If both are using the same power source, the 
loads must have EMF protection. This protection can be integral to the load, or installed in the 24

 VAC 

wiring 

across 

the 

load’s coil.

To provide necessary RFI and transient protection, the controller’s ground (GND) pin (T40) must be connected to earth 
ground or the earth ground of the packaged unit’s enclosure ground. Failure to properly ground the controller may cause it 
to exceed FCC limits. Excessive noise could also produce inaccurate sensor data. The power source must be capable of 
operating with this connection to ground.

INSTALLATION PRECAUTIONS

General

CAUTION:

 This symbol is intended to alert the user to the presence of important installation and maintenance 

(servicing) instructions in the literature accompanying the equipment.

CAUTION:

 Risk of explosion if battery is replaced by an incorrect type. Contains lithium type battery; dispose 

of properly.

WARNING: 

Electrical shock hazard. Disconnect 

ALL

 power sources when installing or servicing this equip-

ment to prevent electrical shock or equipment damage.

Make all wiring connections in accordance with these instructions and in accordance with pertinent national and local elec-
trical codes. Use only copper conductors that are suitable for 167 °F (75 °C).

Summary of Contents for iWorx HPU2

Page 1: ...internally limited to 0 04 A TS300 Series Electrical Outputs Modulated Fan HPU3 only Analog 0 10 Vdc 2K Ohm minimum load 8 bit resolution Stage 1 Stage 2 Reversing Valve Fan Dehumidification HPU3 only...

Page 2: ...lass 2 external power source not supplied to operate The controller power input requires a voltage of 24 Volts AC To calculate power source current requirements add the power consumption of all periph...

Page 3: ...onnect the equipment to a power source different from that to which the receiver is connected Consult the equipment supplier or an experienced radio TV technician for help You are cautioned that any c...

Page 4: ...iWorx HPU Series 4 502 025 Effective April 17 2013 2013 Taco Electronic Solutions Inc...

Page 5: ...iWorx HPU Series 502 025 Effective April 17 2013 5 2013 Taco Electronic Solutions Inc...

Page 6: ...be shorted Setup Instructions 1 Press Controllers from main screen 2 Select required HPU from controller list and press appropriate controller 3 Press All Settings 4 Press Thermostat 5 The Thermostat...

Page 7: ...p Stages 9 The Comp Stages menu opens a Select number of Stages of equipment 1 or 2 b Select the stage Control Band in degrees Cannot be set to 0 c Select the Stage Time in minutes Cannot be set to 0...

Page 8: ...iWorx HPU Series 8 502 025 Effective April 17 2013 2013 Taco Electronic Solutions Inc...

Page 9: ...iWorx HPU Series 502 025 Effective April 17 2013 9 2013 Taco Electronic Solutions Inc...

Page 10: ...shorted Setup Instructions 1 Press Controllers from main screen 2 Select required HPU3 from controller list and press appropriate controller 3 Press All Settings 4 Press Dehumidification 5 The Dehumid...

Page 11: ...s 1 Press Controllers from main screen 2 Select required HPU3 from controller list and press appropriate controller 3 Press All Settings 4 Press Next 3 5 Press Mod Fan Settings 6 The Mod Fan Settings...

Page 12: ...lot relay have been pow ered with 24 VAC and the output has been correctly wired to the coil of the pilot relay Also ensure that the pilot relay has a 24 VAC coil The 10K thermistor reading is at its...

Page 13: ...ormation please refer to the last page of this Document for the company s Limited Warranty Statement which is also issued with the product or available at www taco hvac com Notes Description Audience...

Page 14: ...iWorx HPU Series 14 502 025 Effective April 17 2013 2013 Taco Electronic Solutions Inc...

Page 15: ...iWorx HPU Series 502 025 Effective April 17 2013 15 2013 Taco Electronic Solutions Inc...

Page 16: ...be covered by this warranty TES products are not intended for use to support fire suppression systems life support systems critical care applications commercial aviation nuclear facilities or any othe...

Reviews: