background image

iWorx® HPU3

505-035, Effective: June 30, 2015

21 

© 2015 Taco Electronic Solutions, Inc.

Global Unit Enable

The controller can be synchronized to the main plant water supply through its global unit enable feature (located on the 
ASM2 controller). The status of the supply water flow is measured by an external device, and provided to the HPU3 
over the network. The controller waits in shutdown mode until water flow is detected.

Humidification

A digital output for humidification (HUM) is provided for adding humidity to the space. When the Space Humidity falls 
below the configured 

Space RH Setpoint

, the humidification output is energized. Humidification output remains ener-

gized until the Space Humidity rises three percent above the configured setpoint. Humidification may be configured to 
operate when Occupied or Always.

If the humidity in the supply duct rises above the configurable 

Supply RH Limit

, humidification output is deenergized 

regardless of the space humidification requirements.

The fan is used to purge the supply duct before and after the humidification output is energized for a configurable 
amount of time.

To enable humidification, sensors for Supply Air Humidity (SAH) and Space Humidity must be present. Space Humidity 
may be obtained from an SLink thermostat, or alternatively, from a separate humidity sensor connected to the STAT 
input (such as when temperature is provided from a BZU3 thermostat that does not provide humidity - see "Hydronic 
Zone Interaction"). The STAT input is configured in the 

Thermostat

 configuration screen.

To disable humidification, configure either 

Space RH Setpoint

 or 

Supply RH Limit

 to zero percent. If either (or both) of 

these are configured to zero percent, humidification is not enabled.

Thermostat

Space temperature, current humidity, setpoint adjustment, fan auto/on status (depending on the thermostat model), 
and occupancy override request are monitored by the thermostat and sent to the controller.

The controller automatically detects a failure of the thermostat. When the thermostat fails, the compressor stages turn 
off, the fan turns off, and control is disabled.

Note: 

The thermostat must be connected. The status LED on the controller turns solid red if the thermostat is not con-

nected. Once the thermostat is connected, the status LED turns green indicating normal operation. Alternatively, the 
thermostat input (STAT) may be used for an RH sensor for Space Humidity, if the controller is also configured as part of 
a hydronic zone - see "Hydronic Zone Interaction".

Local Backup Schedule

The LCI normally determines the operating mode. A local backup schedule can be defined for situations when the LCI 
is not available. When the controller detects that the LCI is not available (after 10 minutes without communication), it 
resorts to the configured local backup schedule. If the local backup schedule is disabled, the controller defaults to occu-
pied mode.

The configured occupied and unoccupied times are used in determining the current operating mode of the controller 
when it is running the backup schedule. By default, both the unoccupied and occupied time are set to zero, which dis-
ables the local backup schedule. This causes the controller to default to the occupied mode of operation if it cannot 
communicate with the LCI.

Runtime Accumulation

The total runtime is accumulated for the compressor and fan outputs. The runtimes can be used to indicate that main-
tenance is required on the equipment controlled by these outputs. The runtime can be reset by an operator or mainte-
nance person once servicing has been performed. 

Summary of Contents for iWorx HPU3

Page 1: ...evice 6 Routing Cabling to the Device 7 Grounding the Device 7 Wiring Information 8 Connecting Input Devices 9 Connecting Output Devices 10 Other Connections 11 Specifications 11 Electrical 11 Mechani...

Page 2: ...iWorx HPU3 2 505 035 Effective June 30 2015 2015 Taco Electronic Solutions Inc THIS PAGE LEFT BLANK INTENTIONALLY...

Page 3: ...tem for monitoring and control applications Features Two stage compressor heating cooling control Reversing valve control Auxiliary Emergency Heat enable Dehumidification with Reheat both internal and...

Page 4: ...hvac com APPLICABLE DOCUMENTATION See the table below for additional documentation that may be applicable to this controller Description Audience Purpose iWorx LCI Application Guide Docu ment No 505 0...

Page 5: ...ital device pursuant to Part 15 of the FCC rules These limits are designed to provide reasonable protection against harmful interference This equip ment can radiate radio frequency energy and if not i...

Page 6: ...Volts AC To calculate power source current requirements add the power consumption of all peripheral devices to that of the controller The controller and sensor power supplies can use the same power s...

Page 7: ...control enclosure and wiring conduit Grounding the Device The ground terminal T40 must be securely connected to earth ground Failure to properly ground this equipment will result in improper operation...

Page 8: ...ons Inc WIRING INFORMATION WARNING Terminals 6 9 and 12 are connected internally on all HPU3 controllers Disconnect ALL power sources when installing or servicing this equipment to prevent electrical...

Page 9: ...connect the heat pump thermostat or an RH humidity sensor to the unit attach one wire from the thermostat or sensor to STAT T3 and the other wire to the adjacent common T4 Equipment Status EQS To con...

Page 10: ...e SAT optional To connect a thermistor Precon III to the analog input attach one wire of the sensor to ST T13 and the other wire to the adjacent common T12 Connecting Output Devices Stage 1 Stage 2 S1...

Page 11: ...wire from a 24 VAC power supply to PWR T39 and the other output wire from the power supply to the adjacent common terminal T38 T38 must be connected to earth ground Ground GND Terminal GND T40 must b...

Page 12: ...ters For detailed specifications refer to the FTT 10A Free Topology Transceiver User s Guide published by Echelon Corpo ration www echelon com support documentation manuals transceivers Mechanical Hou...

Page 13: ...control algorithm to minimize excessive cycling As the temperature decreases below the cooling setpoint the compressor stages are sequenced off When the unoccupied mode is entered the cooling setpoint...

Page 14: ...l alarm is reported to the LCI When the zone humidity rises above the humidity setpoint dehumidification is enabled by activating the dehumidifica tion output external dehumidification and optionally...

Page 15: ...point offset also affects the calculated heating and calculated cooling setpoints by an equal amount The set point offset only applies in the occupied mode of operation it has no affect in the unoccup...

Page 16: ...erature drops below the calculated heating setpoint the reversing valve is cycled to the heating position When the space temperature drops below the calculated heating setpoint minus the heating con t...

Page 17: ...e temperature is less than the space setpoint If the temperature rises above the space setpoint then the minimum on and off times are ignored When the space temperature rises above the space setpoint...

Page 18: ...ling setpoint for a predefined time period the last energized stage is turned off Note that the last stage that was turned on will be the first one to be turned off If the space tem perature remains b...

Page 19: ...1 On T1 T2 T1 T2 Reversing Valve COOL Cooling Sequence Unoccupied Mode Commissioning The controller has a Commissioning screen that allows any of the controller s outputs to be manually configured to...

Page 20: ...after dehumidification occurs Dehumidification begins when the Space Humidity rises above the configured dehumidification setpoint and stops when the Space Humidity falls three percent below the dehu...

Page 21: ...o zero percent humidification is not enabled Thermostat Space temperature current humidity setpoint adjustment fan auto on status depending on the thermostat model and occupancy override request are m...

Page 22: ...ly closed active when open When a pressure alarm input becomes active a high or low pressure alarm message is sent to the LCI and the heat pump outputs are disabled When the pressure alarm clears norm...

Page 23: ...n the HPU3 with LNS or other LONWORKS tools if they wish The LCI also provides network supervision of the HPU3 The LCI periodically sends a ping message to the HPU3 which elicits a response If the res...

Page 24: ...go beyond the Supply RH Limit nviSetpoint overrides the setpoint as obtained from the thremostat SLink or BZU LCI or a pre configured backup schedule nviOccCmd overrides the occupancy as obtained fro...

Page 25: ...iResetRuntime SNVT_lev_disc 0 no reset 1 reset runtimes Resets fan heating and cooling runtimes nviSysTime SNVT_time_stamp Date Time System time nviUnitEnable unsigned byte 0 Off 4 On 1 no effect Unit...

Page 26: ...ature Space Humidity 0 to 100 Space Humidity Supply Air Temp 22 F to 122 F 30 C to 50 C Supply Air Temperature Supply Air Humidity 22 F to 122 F 30 C to 50 C Supply Air Humidity Inst Power 0 to 3 4E38...

Page 27: ...Off On Status of Dehumidification output DHUM Humidify Off On Status of Humidification output HUM Reheat Off On Status of reheat output RH Auxiliary Heat Off On State of auxiliary heat output AUX Sett...

Page 28: ...min Allowable occupancy extension time Alarm Temp Offset 0 to 10 0 F 0 to 5 56 C 5 F 2 8 C Degrees below the heating setpoint or above the cooling setpoint to trigger a low limit or high limit alarm...

Page 29: ...55 minutes 5 minutes Compressor control cycle timer Setting Range Default Description Setpoint 459 to 621 F 273 to 327 C 20 0 F 6 7 C The outside air temperature OAT that trig gers auxiliary heating T...

Page 30: ...ormally Open Normally Closed Disabled Enable equipment status High Press Alm Polarity Disabled Normally Open Normally Closed Disabled Enable high pressure status input Low Press Alm Polarity Disabled...

Page 31: ...e for the alarm limit or reset the accumulated runtimes to zero High Pressure Normal Soft Alarm Hard Alarm Occurs when the High Pressure Alarm input is faulted Alarm is Hard if more than one alarm hap...

Page 32: ...he controller was previously in an equipment status fault condition the controller must be reset before proper operation can be restored The fan and staged pilot relays will not come on even though th...

Page 33: ...r A complete description of difficulties encountered Notes Thermistor readings fluctuate rapidly sometimes by several degrees The controller is not properly grounded The controller s ground GND pin T4...

Page 34: ...overed by this warranty TES products are not intended for use to sup port fire suppression systems life support sys tems critical care applications commercial aviation nuclear facilities or any other...

Reviews: