background image

iWorx® HPU3

505-035, Effective: June 30, 2015

23 

© 2015 Taco Electronic Solutions, Inc.

Hydronic Zone Interaction 

To configure the controller to be part of a hydronic zone, associate the controller with a BZU3 from the BZU3 control-
ler's configuration screens. Refer to the BZU3 Application Guide for details on this procedure.

The HPU3 controller initiates network communication with the associated BZU3 Zone controller, which replies with the 
following zone parameters to the HPU3. These zone parameters take precedence over the HPU3 calculated parame-
ters:

• Space Temperature
• Occupied Setpoint
• Unoccupied Setpoint
• HVAC mode
• Fan mode
• Occupied state

When the HPU3 is configured to be part of a hydronic zone, the Space humidity may be obtained from either a separate 
RH sensor or an SLink thermostat; either of these are connected to the STAT input and configured from the Thermostat 
configuration screen.

Automatic Configuration

The HPU3 and iWorx® Local Control Interface (LCI) use a self-configuring network management scheme requiring no 
external tools, binding, or L

ON

W

ORKS

 knowledge.  The LCI recognizes and configures the HPU3 when the controller’s 

service pin is pressed. The controller’s status light flashes green until the controller is configured, and is solid green 
after the controller is configured.  Once the service pin has been pressed, no further action is required by the user; the 
controller is fully accessible to the LCI. Users may bind to SNVTs on the HPU3 with LNS or other L

ON

W

ORKS

 tools if 

they wish.

The LCI also provides network supervision of the HPU3.  The LCI periodically sends a "ping" message to the HPU3, 
which elicits a response. If the response fails, an alarm is displayed on the LCI. The LCI also uses the "ping" message 
to refresh the occupancy mode and other system wide data.

Communication with Associated Controllers

In addition to Hydronic Zone interaction with the BZU3, the HPU3 is capapable of communicating with any LHP, GHP 
and CCU controllers on the network to share demand and power usage data. These associations are configured from 
the main controller screens of the other controllers.

Please refer to the iWorx® 

LCI Application Guide

, iWorx® 

GHP1 Application Guide

 or iWorx® 

LHP2 Application Guide

for a detailed description of how to associate the HPU3 and these other controllers.

CONTROLLER IDENTIFICATION

To register the controller with the LCI, press the service pin on the controller once it is properly installed and the LCI is 
active on the network.

Once the HPU3 is properly installed and recognized by the LCI, the LCI can be used to configure the settings of the 
controller. This section describes the commands available on the LCI for configuration of the HPU3, and the meanings 
and default values for controller parameters. For more information on using the LCI, see the 

iWorx® LCI Application 

Guide.

Network Inputs 

The HPU3 allows a network manager to modify the Network Input Variables for the purpose of overriding configuration, 
operation, inputs and outputs of the controller. Values written to the Network Input Variables have priority over normal 
controller operation.

Summary of Contents for iWorx HPU3

Page 1: ...evice 6 Routing Cabling to the Device 7 Grounding the Device 7 Wiring Information 8 Connecting Input Devices 9 Connecting Output Devices 10 Other Connections 11 Specifications 11 Electrical 11 Mechani...

Page 2: ...iWorx HPU3 2 505 035 Effective June 30 2015 2015 Taco Electronic Solutions Inc THIS PAGE LEFT BLANK INTENTIONALLY...

Page 3: ...tem for monitoring and control applications Features Two stage compressor heating cooling control Reversing valve control Auxiliary Emergency Heat enable Dehumidification with Reheat both internal and...

Page 4: ...hvac com APPLICABLE DOCUMENTATION See the table below for additional documentation that may be applicable to this controller Description Audience Purpose iWorx LCI Application Guide Docu ment No 505 0...

Page 5: ...ital device pursuant to Part 15 of the FCC rules These limits are designed to provide reasonable protection against harmful interference This equip ment can radiate radio frequency energy and if not i...

Page 6: ...Volts AC To calculate power source current requirements add the power consumption of all peripheral devices to that of the controller The controller and sensor power supplies can use the same power s...

Page 7: ...control enclosure and wiring conduit Grounding the Device The ground terminal T40 must be securely connected to earth ground Failure to properly ground this equipment will result in improper operation...

Page 8: ...ons Inc WIRING INFORMATION WARNING Terminals 6 9 and 12 are connected internally on all HPU3 controllers Disconnect ALL power sources when installing or servicing this equipment to prevent electrical...

Page 9: ...connect the heat pump thermostat or an RH humidity sensor to the unit attach one wire from the thermostat or sensor to STAT T3 and the other wire to the adjacent common T4 Equipment Status EQS To con...

Page 10: ...e SAT optional To connect a thermistor Precon III to the analog input attach one wire of the sensor to ST T13 and the other wire to the adjacent common T12 Connecting Output Devices Stage 1 Stage 2 S1...

Page 11: ...wire from a 24 VAC power supply to PWR T39 and the other output wire from the power supply to the adjacent common terminal T38 T38 must be connected to earth ground Ground GND Terminal GND T40 must b...

Page 12: ...ters For detailed specifications refer to the FTT 10A Free Topology Transceiver User s Guide published by Echelon Corpo ration www echelon com support documentation manuals transceivers Mechanical Hou...

Page 13: ...control algorithm to minimize excessive cycling As the temperature decreases below the cooling setpoint the compressor stages are sequenced off When the unoccupied mode is entered the cooling setpoint...

Page 14: ...l alarm is reported to the LCI When the zone humidity rises above the humidity setpoint dehumidification is enabled by activating the dehumidifica tion output external dehumidification and optionally...

Page 15: ...point offset also affects the calculated heating and calculated cooling setpoints by an equal amount The set point offset only applies in the occupied mode of operation it has no affect in the unoccup...

Page 16: ...erature drops below the calculated heating setpoint the reversing valve is cycled to the heating position When the space temperature drops below the calculated heating setpoint minus the heating con t...

Page 17: ...e temperature is less than the space setpoint If the temperature rises above the space setpoint then the minimum on and off times are ignored When the space temperature rises above the space setpoint...

Page 18: ...ling setpoint for a predefined time period the last energized stage is turned off Note that the last stage that was turned on will be the first one to be turned off If the space tem perature remains b...

Page 19: ...1 On T1 T2 T1 T2 Reversing Valve COOL Cooling Sequence Unoccupied Mode Commissioning The controller has a Commissioning screen that allows any of the controller s outputs to be manually configured to...

Page 20: ...after dehumidification occurs Dehumidification begins when the Space Humidity rises above the configured dehumidification setpoint and stops when the Space Humidity falls three percent below the dehu...

Page 21: ...o zero percent humidification is not enabled Thermostat Space temperature current humidity setpoint adjustment fan auto on status depending on the thermostat model and occupancy override request are m...

Page 22: ...ly closed active when open When a pressure alarm input becomes active a high or low pressure alarm message is sent to the LCI and the heat pump outputs are disabled When the pressure alarm clears norm...

Page 23: ...n the HPU3 with LNS or other LONWORKS tools if they wish The LCI also provides network supervision of the HPU3 The LCI periodically sends a ping message to the HPU3 which elicits a response If the res...

Page 24: ...go beyond the Supply RH Limit nviSetpoint overrides the setpoint as obtained from the thremostat SLink or BZU LCI or a pre configured backup schedule nviOccCmd overrides the occupancy as obtained fro...

Page 25: ...iResetRuntime SNVT_lev_disc 0 no reset 1 reset runtimes Resets fan heating and cooling runtimes nviSysTime SNVT_time_stamp Date Time System time nviUnitEnable unsigned byte 0 Off 4 On 1 no effect Unit...

Page 26: ...ature Space Humidity 0 to 100 Space Humidity Supply Air Temp 22 F to 122 F 30 C to 50 C Supply Air Temperature Supply Air Humidity 22 F to 122 F 30 C to 50 C Supply Air Humidity Inst Power 0 to 3 4E38...

Page 27: ...Off On Status of Dehumidification output DHUM Humidify Off On Status of Humidification output HUM Reheat Off On Status of reheat output RH Auxiliary Heat Off On State of auxiliary heat output AUX Sett...

Page 28: ...min Allowable occupancy extension time Alarm Temp Offset 0 to 10 0 F 0 to 5 56 C 5 F 2 8 C Degrees below the heating setpoint or above the cooling setpoint to trigger a low limit or high limit alarm...

Page 29: ...55 minutes 5 minutes Compressor control cycle timer Setting Range Default Description Setpoint 459 to 621 F 273 to 327 C 20 0 F 6 7 C The outside air temperature OAT that trig gers auxiliary heating T...

Page 30: ...ormally Open Normally Closed Disabled Enable equipment status High Press Alm Polarity Disabled Normally Open Normally Closed Disabled Enable high pressure status input Low Press Alm Polarity Disabled...

Page 31: ...e for the alarm limit or reset the accumulated runtimes to zero High Pressure Normal Soft Alarm Hard Alarm Occurs when the High Pressure Alarm input is faulted Alarm is Hard if more than one alarm hap...

Page 32: ...he controller was previously in an equipment status fault condition the controller must be reset before proper operation can be restored The fan and staged pilot relays will not come on even though th...

Page 33: ...r A complete description of difficulties encountered Notes Thermistor readings fluctuate rapidly sometimes by several degrees The controller is not properly grounded The controller s ground GND pin T4...

Page 34: ...overed by this warranty TES products are not intended for use to sup port fire suppression systems life support sys tems critical care applications commercial aviation nuclear facilities or any other...

Reviews: