DESCRIPTION:

The 0026e™ is a high-performance, variable speed, high-efficiency, wet-rotor circulator 

with an ECM permanent magnet motor. With 5 easy settings, its variable speed 

performance curves are equivalent to the Taco 0010, 0011, 0012, 0012 3-Speed,

0013, 0013 3-Speed & 0014. Ideal for large residential and light commercial hydronic 

heating, chilled water cooling and domestic hot water systems. The 0026e reduces 

power consumption by up to 85% compared to equivalent AC permanent split 

capacitor circulators. With a maximum of 26 feet of head and 44 gpm. It is available

in either Cast Iron or NSF certified Stainless Steel.

APPLICATION:

• Maximum operating pressure: 150 psi (10.3 bar)

• Maximum fluid temperature: 230°F (110˚C)

• Minimum fluid temperature: 14°F (-10˚C)

• Electrical specifications:

Voltage: 115/208/230V, 50/60 Hz, single phase

Maximum operating power: 120W

Maximum amp rating: 1.05 A

• Equipped with a Cast Iron or Stainless Steel casing

• SS Model suitable for open loop potable water systems

• Taco circulators are for indoor use only – employer uniquement a l’interieur

• Acceptable for use with water or maximum of 50% water/glycol solution

FEATURES:

• 5 easy dial settings to match system requirements - activeADAPT, LOW, MEDIUM, HIGH or 0-10V DC input

• Replaces all single speed and 3-speed circulators in its class

• ECM performance equivalent to Taco’s 0010, 0011, 0012 & 0014 circulators

• Multi-color LED: power on, mode setting and error code diagnostics

• Use with a Taco ZVC Zone Valve Control or SR Switching Relay for ON/OFF operation

• Nut-capture feature on flanges for easier fit up

• Dual electrical knockouts and removable quick-connect terminal strip for easy wiring

• Whisper quiet operation

BIO Barrier®

 protects the pump from system contaminants

SureStart®

 automatic unblocking and air purging mode

• Rotatable control cover to allow any pump body orientation

INSTALLATION:

WARNING: Do not use in swimming pool or spa areas. Pump has not been investigated for these applications.

AVERTISSEMENT : Ne pas utiliser dans une piscine ou un spa. La pompe n’a pas été étudiée pour ces applications.

CAUTION: The addition of petroleum based fluids or certain chemical additives to systems using TACO equipment

voids the warranty. Consult factory for fluid compatibility.

ATTENTION : L’ajout de liquides à base de pétrole ou de certains additifs chimiques à des systèmes utilisant un

équipement TACO annule la garantie. Consultez le fabricant pour connaître la compatibilité de liquides.

CAUTION: Installations at elevations over 5000 feet must have higher fill pressure of 20 psi minimum to prevent

pump cavitation and flashing. Premature failure may result. Adjust expansion tank pressure to equal fill pressure. 

A larger size expansion tank may be required.
ATTENTION : Des installations à des altitudes de plus de 1600 mètres doivent présenter une pression de remplissage plus élevée de 20 psi 

au minimum afin d’éviter toute cavitation ou flashing de la pompe. Une défaillance prématurée peut en résulter. Réglez la pression 

du réservoir d’expansion de façon qu’elle soit égale à la pression de remplissage. Un réservoir d’expansion d’une taille supérieure 

peut être nécessaire.

Instruction Sheet

102-566

SUPERSEDES: 

February 1, 2021

EFFECTIVE: 

August

 1

6

, 2021

Plant ID No. 001-5032

-1-

Figure 1

Standard flange model: 0026e-F2

Certified to

NSF/ANSI 61 & 372

Summary of Contents for 0026e

Page 1: ...for easier fit up Dual electrical knockouts and removable quick connect terminal strip for easy wiring Whisper quiet operation BIO Barrier protects the pump from system contaminants SureStart automat...

Page 2: ...E 1 ZONE 2 ZONE 3 ZONE 1 ZONE 2 ZONE 3 FC FC Optional Location FC FC ZONE 1 ZONE 2 ZONE 3 FC FC Optional Location FC FC V3 V3 V3 V2 V2 V2 P P P EXPANSION TANK V1 V1 PV4 P EXPANSION TANK BOILER EXPANSI...

Page 3: ...E 3 ZONE 1 ZONE 2 ZONE 3 ZONE 1 ZONE 2 ZONE 3 KEY V1 V2 V3 SHUT OFF ISOLATION VALVE P TACO 0026e CIRCULATOR FF FAST FILL BOILER FEED VALVE PV4 PURGE VALVE ZV ZONE VALVE MOD CON BOILER EXPANSION TANK E...

Page 4: ...the system will result in immediate lubrication of the bearings It is always good practice to flush a new system of foreign matter before starting the circulator WARNING Risk of electric shock To red...

Page 5: ...hecirculatorfor0 10VDCOperation See Page 9 5 Start the circulator When purging the system it is recommended to run the circulator at full speed long enough to remove all remaining air from the bearing...

Page 6: ...on back page The 0026e has 5 Operating Settings activeADAPT Automatic self adjusting proportional pressure variable speed Violet LED LOW 8 feet of head constant pressure variable speed Orange LED MED...

Page 7: ...16 18 20 22 24 26 28 30 32 34 36 38 50 40 42 44 46 48 Flow Rate Q GPM 0 4 6 2 8 10 12 14 16 18 20 22 24 26 28 Head ft 6 0026e High Efficiency Circulator activeADAPT Range Purple LED activeADAPT active...

Page 8: ...h Efficiency Circulator Maximum Curve Fixed Speed Blue LED 2 0 Flow Rate Q GPM 0 2 4 6 8 10 12 Head ft 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 14 16 18 20 22 24 26 28 HIGH...

Page 9: ...r external signal wiring 3 Disconnect the connector 4 from control board 5 4 Insert the cable 6 into the cable gland M12x1 5 7 and screw it to the cover 5 Strip the wires 5 mmMIN and insert them into...

Page 10: ...10V DC analog signal external input PWM Pulse Width Modulation 2V 4V 6V 8V 10V 0 140 100 120 80 40 20 60 2 0 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 Head ft 0 2 4 6 8 10 1...

Page 11: ...replaced FAULTS CONTROL PANEL CAUSE S E I D E M E R S The circulator is noisy LED on Suction pressure is insufficient cavitation Increase the system suction pressure within the permissible range LED...

Page 12: ...UPS 32 80 Magna 32 60 Alpha2 26 99 Stratos 1 25 x 3 25 1 25 x 3 20 Top S 1 25 x 15 1 25 x 25 1 50 x 20 Top Z 1 5 x 15 1 5 x 20 12 LIMITED WARRANTY STATEMENT Taco Inc will repair or replace without ch...