background image

Analog or Digital Input

In “0-10V” mode, the circulator accepts either a 0-10VDC voltage signal or a PWM signal. 

The selection of the type of signal is made automatically by the circulator.

0-10VDC Input

The circulator operates at variable speed depending on the DC input voltage.

At voltages between 2 V and 10 V, the circulator operates at a variable speed depending on the voltage:

- Max. Speed voltage not exceeding or equal to 1V

- Max. Speed voltages greater than or equal to 10V

PWM (Pulse Width Modulation)

2V

4V

6V

8V

10V

0

140

100

120

80

40

20

60

2

0

4

6

8

10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50

H

ead [f

t.]

0

2

4

6

8

10

12

14

16

18

20

22

24

26

28

0-10V

0-10V

Po

w

er (

W

)

2

4

6

8

10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50

0

Flow Rate Q [GPM]

Flow Rate Q [GPM]

0026e High-Efficiency Circulator

0-10V DC Performance Curves

Power Consumption

0026e High-Efficiency Circulator

0-10V DC Curves

YELLOW LED

YELLOW LED

10V

8V

6V

4V

2V

100%

75%

50%

25%

0%

-10-

10V

2V

1V

0.5V

MIN

MAX

SPEED

Input Voltage

0-10V DC Input Mode:

The circulator will vary its speed and

performance based on a 0-10V DC

analog signal external input.

PWM (Pulse Width Modulation)

2V

4V

6V

8V

10V

0

140

100

120

80

40

20

60

2

0

4

6

8

10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50

H

ead [f

t.]

0

2

4

6

8

10

12

14

16

18

20

22

24

26

28

0-10V

0-10V

Po

w

er (

W

)

2

4

6

8

10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50

0

Flow Rate Q [GPM]

Flow Rate Q [GPM]

0026e High-Efficiency Circulator

0-10V DC Performance Curves

Power Consumption

0026e High-Efficiency Circulator

0-10V DC Curves

YELLOW LED

YELLOW LED

10V

8V

6V

4V

2V

100%

75%

50%

25%

0%

IMPORTANT: If the input remains disconnected, the circulator runs at max. speed

PWM Input

Circulator operates at variable speed according to digital 

input duty cycle. PWM digital input is shared with 0-10V DC 

analog input, the pump will automatically switch between 

different input protocols when it detects a constant  

frequency input signal. 0% and 100% PWM inputs are  

not valid and will be treated as an analog input.
PWM amplitude must be from 5 to 12V, frequency 

between 200Hz to 5kHz
Operations based on PWM input:

- Standby for PWM below 5%

- Min speed for PWM between 9-16%

- Half speed for 50% PWM

- Max speed for PWM in over 90%

Between 5% to 9% PWM the circulator remains in standby 

or run mode according to minimum threshold

90%

in

valid

in

valid

5% 9% 16%

0%

100%

SPEED

PWM input

Standby

-11-

Summary of Contents for 0026e

Page 1: ...for easier fit up Dual electrical knockouts and removable quick connect terminal strip for easy wiring Whisper quiet operation BIO Barrier protects the pump from system contaminants SureStart automat...

Page 2: ...E 1 ZONE 2 ZONE 3 ZONE 1 ZONE 2 ZONE 3 FC FC Optional Location FC FC ZONE 1 ZONE 2 ZONE 3 FC FC Optional Location FC FC V3 V3 V3 V2 V2 V2 P P P EXPANSION TANK V1 V1 PV4 P EXPANSION TANK BOILER EXPANSI...

Page 3: ...E 3 ZONE 1 ZONE 2 ZONE 3 ZONE 1 ZONE 2 ZONE 3 KEY V1 V2 V3 SHUT OFF ISOLATION VALVE P TACO 0026e CIRCULATOR FF FAST FILL BOILER FEED VALVE PV4 PURGE VALVE ZV ZONE VALVE MOD CON BOILER EXPANSION TANK E...

Page 4: ...the system will result in immediate lubrication of the bearings It is always good practice to flush a new system of foreign matter before starting the circulator WARNING Risk of electric shock To red...

Page 5: ...hecirculatorfor0 10VDCOperation See Page 9 5 Start the circulator When purging the system it is recommended to run the circulator at full speed long enough to remove all remaining air from the bearing...

Page 6: ...on back page The 0026e has 5 Operating Settings activeADAPT Automatic self adjusting proportional pressure variable speed Violet LED LOW 8 feet of head constant pressure variable speed Orange LED MED...

Page 7: ...16 18 20 22 24 26 28 30 32 34 36 38 50 40 42 44 46 48 Flow Rate Q GPM 0 4 6 2 8 10 12 14 16 18 20 22 24 26 28 Head ft 6 0026e High Efficiency Circulator activeADAPT Range Purple LED activeADAPT active...

Page 8: ...h Efficiency Circulator Maximum Curve Fixed Speed Blue LED 2 0 Flow Rate Q GPM 0 2 4 6 8 10 12 Head ft 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 14 16 18 20 22 24 26 28 HIGH...

Page 9: ...r external signal wiring 3 Disconnect the connector 4 from control board 5 4 Insert the cable 6 into the cable gland M12x1 5 7 and screw it to the cover 5 Strip the wires 5 mmMIN and insert them into...

Page 10: ...10V DC analog signal external input PWM Pulse Width Modulation 2V 4V 6V 8V 10V 0 140 100 120 80 40 20 60 2 0 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 Head ft 0 2 4 6 8 10 1...

Page 11: ...replaced FAULTS CONTROL PANEL CAUSE S E I D E M E R S The circulator is noisy LED on Suction pressure is insufficient cavitation Increase the system suction pressure within the permissible range LED...

Page 12: ...UPS 32 80 Magna 32 60 Alpha2 26 99 Stratos 1 25 x 3 25 1 25 x 3 20 Top S 1 25 x 15 1 25 x 25 1 50 x 20 Top Z 1 5 x 15 1 5 x 20 12 LIMITED WARRANTY STATEMENT Taco Inc will repair or replace without ch...

Reviews: