Troubleshooting the error codes:

 

Listed below are potential diagnostic error codes which will appear on the LED display in case of a malfunction.

Unlocking Procedure:

 A red LED indicates the circulator is locked or sticking. Disconnect and connect power supply to start the 

automatic release process. The circulator makes 100 attempts to restart (process lasts approximately 15 minutes). Every restart is 

signaled by a short white flash of the LED. If the locking is not removed through the automatic release process after 100 attempts 

to restart the circulator, it goes into standby and the LED remains red. In this case follow the manual procedure described in 

the next steps: during any attempt, the red LED keeps blinking; after that the circulator tries again to start. If the locking is not 

removed through the automatic release process (the warning light returns to red), perform the manual steps described below.

1.

  Disconnect power supply - the warning light switches off.

2. 

Close both isolating valves and allow cooling. If there are no shut-off devices, 

drain the system so that the fluid level is beneath that of the circulator.

3.

  Loosen 4 motor bolts. Remove motor from casing. Carefully pull the rotor/impeller from the motor.

4.

  Remove impurities and deposits from the impeller and casing.

5.

  Reinsert the rotor/impeller into the motor.

6. 

Connect power supply. Check for impeller rotation.

7. 

If the circulator still doesn’t run it will need to be replaced.

FAULTS

CONTROL 
PANEL

CAUSE

S

E

I

D

E

M

E

R

S

The circulator is noisy 

LED on 

Suction pressure is 
insufficient - cavitation 

Increase the system suction pressure 

within the permissible range.

LED on

Presence of foreign bodies 
in the impeller

Disassemble the motor and clean the impeller.

Loud noises of water circulation 

Flashing white 
LED

Air in the system. Circulator
may be air-bound. 

Vent the system.
Repeat fill and purge steps.

Circulator is not running although
the electrical power supply is
switched on

LED off 

Lack of power supply

Verify voltage value of the electric plant.

Verify the connection of the motor.

Circuit breaker might be
tripped

Check circuit breaker at panel

and reset if necessary.

The circulator is defective

Replace the circulator.

Overheating

Let the circulator cool down for some minutes.
Then try to restart it. Verify that the water
and ambient temperature are within the
indicated temperature ranges.

LED red

The rotor is blocked

Disassemble the motor and clean the impeller.
See unlocking procedure below.

Insufficient supply voltage

Verify that the power supply matches
the data on the name plate.

Building does not get warm 

LED on

System may be air-bound

Vent system.
Repeat fill and purge steps.

Analog Output 0-10V DC

The circulator has an analog output signal feature to indicate 

the operating status and the presence of any errors.

0V

Circulator off, not powered

2V

Circulator powered in standby

4V

Circulator on and running

6V

Warning presence (overheating, air)

10V

Alarm presence (Circulator blocked, 

under voltage, over temperature)

Note: When input is unconnected 0026e circulator runs at full speed.

-11-

Summary of Contents for 0026e

Page 1: ...for easier fit up Dual electrical knockouts and removable quick connect terminal strip for easy wiring Whisper quiet operation BIO Barrier protects the pump from system contaminants SureStart automat...

Page 2: ...E 1 ZONE 2 ZONE 3 ZONE 1 ZONE 2 ZONE 3 FC FC Optional Location FC FC ZONE 1 ZONE 2 ZONE 3 FC FC Optional Location FC FC V3 V3 V3 V2 V2 V2 P P P EXPANSION TANK V1 V1 PV4 P EXPANSION TANK BOILER EXPANSI...

Page 3: ...E 3 ZONE 1 ZONE 2 ZONE 3 ZONE 1 ZONE 2 ZONE 3 KEY V1 V2 V3 SHUT OFF ISOLATION VALVE P TACO 0026e CIRCULATOR FF FAST FILL BOILER FEED VALVE PV4 PURGE VALVE ZV ZONE VALVE MOD CON BOILER EXPANSION TANK E...

Page 4: ...the system will result in immediate lubrication of the bearings It is always good practice to flush a new system of foreign matter before starting the circulator WARNING Risk of electric shock To red...

Page 5: ...hecirculatorfor0 10VDCOperation See Page 9 5 Start the circulator When purging the system it is recommended to run the circulator at full speed long enough to remove all remaining air from the bearing...

Page 6: ...on back page The 0026e has 5 Operating Settings activeADAPT Automatic self adjusting proportional pressure variable speed Violet LED LOW 8 feet of head constant pressure variable speed Orange LED MED...

Page 7: ...16 18 20 22 24 26 28 30 32 34 36 38 50 40 42 44 46 48 Flow Rate Q GPM 0 4 6 2 8 10 12 14 16 18 20 22 24 26 28 Head ft 6 0026e High Efficiency Circulator activeADAPT Range Purple LED activeADAPT active...

Page 8: ...h Efficiency Circulator Maximum Curve Fixed Speed Blue LED 2 0 Flow Rate Q GPM 0 2 4 6 8 10 12 Head ft 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 14 16 18 20 22 24 26 28 HIGH...

Page 9: ...r external signal wiring 3 Disconnect the connector 4 from control board 5 4 Insert the cable 6 into the cable gland M12x1 5 7 and screw it to the cover 5 Strip the wires 5 mmMIN and insert them into...

Page 10: ...10V DC analog signal external input PWM Pulse Width Modulation 2V 4V 6V 8V 10V 0 140 100 120 80 40 20 60 2 0 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 Head ft 0 2 4 6 8 10 1...

Page 11: ...replaced FAULTS CONTROL PANEL CAUSE S E I D E M E R S The circulator is noisy LED on Suction pressure is insufficient cavitation Increase the system suction pressure within the permissible range LED...

Page 12: ...UPS 32 80 Magna 32 60 Alpha2 26 99 Stratos 1 25 x 3 25 1 25 x 3 20 Top S 1 25 x 15 1 25 x 25 1 50 x 20 Top Z 1 5 x 15 1 5 x 20 12 LIMITED WARRANTY STATEMENT Taco Inc will repair or replace without ch...

Reviews: