1. Location: 

The circulator can be installed on the supply or return side of the boiler but for best system

performance, it should always pump away from the expansion tank. See piping diagrams in Figure 2 & Figure 3.

NOTE: Two shorter 1-1/4” x 7/16” flange bolts are provided with the circulator to

use on the discharge flange to prevent interference with the circulator casing.

CAUTION: Do not use flat rubber gaskets. Only use O-ring gaskets provided or leaks may result. Warranty will be void.

2. Mounting position: 

Circulator must be mounted with the motor in the horizontal position. See Figure 4 & Figure 5

below for acceptable and unacceptable motor mounting orientations. See Figure 6 for Rotating Control Cover.

CAUTION: To reduce the possibility of noise transmission, be sure to add vibration dampeners to piping when mounting

circulator to wall or floor joists. 

ATTENTION : Pour réduire la possibilité de transmission de bruit, veillez à ajouter des amortisseurs de vibration à

la tuyauterie lors du montage du circulateur sur des chevêtres de mur ou de plancher.

3. Filling the system: 

Fill the system with tap water or a maximum of 50% propylene-glycol and water solution.

The system must be filled before operating the circulator. The bearings are water lubricated and should not

be allowed to operate dry. Filling the system will result in immediate lubrication of the bearings. It is always

good practice to flush a new system of foreign matter before starting the circulator.

WARNING: Risk of electric shock. To reduce the risk of electric shock, be certain that it is connected only to a properly

grounded, grounding-type receptacle. Follow all local electrical and plumbing codes.

AVERTISSEMENT : Risque de choc électrique. Pour réduire le risque de choc électrique, veillez à ce qu’elle soit raccordée uniquement  

à un réceptacle de type mise à la terre proprement mis à la terre. Respectez tous les codes de plomberie et électriques locaux.

WARNING: Use supply wires suitable for 90°C.

AVERTISSEMENT : Employer des fils d’alimentation adeqauts pour 90°C. 

WARNING: Disconnect power when servicing.

AVERTISSEMENT : Couper l’alimentation lors de l’entretien.

CAUTION: Use flexible conduit only. Not for use with rigid conduit.

ATTENTION : N’utiliser que du conduit flexible ; n’est pas fait pour du conduit rigide.

-4-

Figure 4 — Acceptable Mounting Positions

Flow

Flow

Flow

Flow

Figure 6 — Rotating Control Cover

Figure 5 — Unacceptable Mounting Positions

The 0026e is equipped 

with a symmetrical control 

cover connected to the 

pump with a ribbon cable. 

The cover can be removed, 

rotated and repositioned 

for best viewing and user 

operation. It allows the 

installer to mount the 

circulator casing in any flow 

direction, then rotate the 

cover to the upright position. 

Remove the 4 cover screws, 

rotate cover to upright 

position, reattach cover 

with 4 screws.

Summary of Contents for 0026e

Page 1: ...for easier fit up Dual electrical knockouts and removable quick connect terminal strip for easy wiring Whisper quiet operation BIO Barrier protects the pump from system contaminants SureStart automat...

Page 2: ...E 1 ZONE 2 ZONE 3 ZONE 1 ZONE 2 ZONE 3 FC FC Optional Location FC FC ZONE 1 ZONE 2 ZONE 3 FC FC Optional Location FC FC V3 V3 V3 V2 V2 V2 P P P EXPANSION TANK V1 V1 PV4 P EXPANSION TANK BOILER EXPANSI...

Page 3: ...E 3 ZONE 1 ZONE 2 ZONE 3 ZONE 1 ZONE 2 ZONE 3 KEY V1 V2 V3 SHUT OFF ISOLATION VALVE P TACO 0026e CIRCULATOR FF FAST FILL BOILER FEED VALVE PV4 PURGE VALVE ZV ZONE VALVE MOD CON BOILER EXPANSION TANK E...

Page 4: ...the system will result in immediate lubrication of the bearings It is always good practice to flush a new system of foreign matter before starting the circulator WARNING Risk of electric shock To red...

Page 5: ...hecirculatorfor0 10VDCOperation See Page 9 5 Start the circulator When purging the system it is recommended to run the circulator at full speed long enough to remove all remaining air from the bearing...

Page 6: ...on back page The 0026e has 5 Operating Settings activeADAPT Automatic self adjusting proportional pressure variable speed Violet LED LOW 8 feet of head constant pressure variable speed Orange LED MED...

Page 7: ...16 18 20 22 24 26 28 30 32 34 36 38 50 40 42 44 46 48 Flow Rate Q GPM 0 4 6 2 8 10 12 14 16 18 20 22 24 26 28 Head ft 6 0026e High Efficiency Circulator activeADAPT Range Purple LED activeADAPT active...

Page 8: ...h Efficiency Circulator Maximum Curve Fixed Speed Blue LED 2 0 Flow Rate Q GPM 0 2 4 6 8 10 12 Head ft 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 14 16 18 20 22 24 26 28 HIGH...

Page 9: ...r external signal wiring 3 Disconnect the connector 4 from control board 5 4 Insert the cable 6 into the cable gland M12x1 5 7 and screw it to the cover 5 Strip the wires 5 mmMIN and insert them into...

Page 10: ...10V DC analog signal external input PWM Pulse Width Modulation 2V 4V 6V 8V 10V 0 140 100 120 80 40 20 60 2 0 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 Head ft 0 2 4 6 8 10 1...

Page 11: ...replaced FAULTS CONTROL PANEL CAUSE S E I D E M E R S The circulator is noisy LED on Suction pressure is insufficient cavitation Increase the system suction pressure within the permissible range LED...

Page 12: ...UPS 32 80 Magna 32 60 Alpha2 26 99 Stratos 1 25 x 3 25 1 25 x 3 20 Top S 1 25 x 15 1 25 x 25 1 50 x 20 Top Z 1 5 x 15 1 5 x 20 12 LIMITED WARRANTY STATEMENT Taco Inc will repair or replace without ch...