background image

SYSTEM START-UP:

1. Prior to pump start-up, closed heating and cooling

systems should be thoroughly cleaned, flushed and
drained.

2. Open isolation valves and re-fill system with clean water.

Check for any leaks.

3. Vent all air from system at an air vent located at the

high point in the system.

4. Start circulator to check for proper operation.

PERIODIC INSPECTION, MAINTENANCE:

Taco 1400 Series Hi-Capacity circulators are designed to
provide years of trouble-free service. However, periodic
inspection and routine maintenance is recommended for
all hydronic systems and mechanical equipment. If any evi-
dence of leakage or damage is present, take preventive
steps to repair or replace the circulator immediately. 

REPLACING THE MECHANICAL SEAL: 

Refer to Fig. 2

on back page.

1. Follow steps 1 thru 5 in section “Removal of existing

pump from system piping”.

2. Loosen the four body bolts that attach the motor hous-

ing to the casing. While supporting the motor, remove
the four bolts and carefully remove the motor and
impeller assembly from the casing.

3. To remove the impeller, first insert a screwdriver into

the motor ventilation slots to make contact with one of
the rotor cooling fins. While holding the rotor in place
with the screwdriver, turn the impeller clockwise to
loosen and remove from shaft.

4. Remove the seal assembly from the shaft.

5. Remove the face plate from the motor housing. To

remove face plate, gently pry it away from the housing.

6. Remove the old seal seat and cup. Lubricate the new

cup with soapy water and install new parts in the face
plate recess. Replace the face plate to its original posi-
tion. Carefully tap the face plate evenly into the recess
in the motor housing.

7. Clean the impeller shaft before installing the new seal.

8. Lubricate the impeller shaft with soapy water. Do not

install new seal on a dry impeller shaft or damage to
seal may result.

9. Slide the new carbon seal and spring assembly onto

the shaft until it contacts the ceramic seal seat.

10. While holding the rotor in place as in Step 3, thread the

impeller onto the shaft in a counter-clockwise direction
until it stops. Check to make sure the pump will rotate.
If the impeller will not spin freely, contact Taco
Technical Support at 1-401-942-8000.

11. Remove old body gasket, clean the recess in the pump

casing and install the new body gasket provided.

12. Attach the pump casing to the motor housing and

secure with the four body bolts. Be sure flow arrow is
pointing in proper direction. Tighten the four bolts
evenly in a criss-cross pattern to 70 in-lb of torque.
There should be a small, even gap between the casing
and the motor mounting bracket.

13. Re-install circulator into system using new flange

gaskets. Refer to section “Installation of 1400 Series
circulator” for complete mounting and wiring instruc-
tions.

CAUTION: Do not start the pump until the sys-
tem has been completely filled and vented.
Running the pump dry may damage the
mechanical seal and void warranty.

CAUTION: Do not allow screwdriver to make
contact with motor windings or insulation.
Permanent damage to motor may result.

CAUTION: Do not allow screwdriver to make
contact with motor windings or insulation.
Permanent damage to motor may result.

CIRCULATOR

MODEL

SEAL KIT NO.*

1400-10, 1400-20, 1400-30,
1400-40, 1400-60, 1400-70

1400-001 RP

1400-50

1400-002 RP

* Includes new body gasket

Summary of Contents for 1400 Series

Page 1: ...e installed on the pump suction and discharge to simplify future ser vice or replacement without draining the system 1 Using teflon tape or high quality thread sealant install Taco companion flanges on threaded pipe ends to ensure proper fit up and leak protection Instruction Sheet 1400 Series Hi Capacity Circulator 102 147 SUPERSEDES June 1 2003 EFFECTIVE August 15 2005 Plant ID 001 1183 INSTALLE...

Page 2: ...ccordance with local and national codes and regulations Electrical supply and grounding wires must be suitable for at least 90ºC 194ºF 1400 Series circulators are thermally protected and do not require external overload protection 1 Be sure all electrical power to pump is disconnected and locked out before proceeding with wiring 2 Loosen capacitor conduit box screw and remove cover 3 Attach approp...

Page 3: ...ce the face plate to its original posi tion Carefully tap the face plate evenly into the recess in the motor housing 7 Clean the impeller shaft before installing the new seal 8 Lubricate the impeller shaft with soapy water Do not install new seal on a dry impeller shaft or damage to seal may result 9 Slide the new carbon seal and spring assembly onto the shaft until it contacts the ceramic seal se...

Page 4: ... been subject to misuse misapplication the addition of petroleum based fluids or certain chemical additives to the systems or other abuse will not be covered by this warranty If in doubt as to whether a particular substance is suitable for use with a Taco product or part or for any application restrictions consult the applicable Taco instruction sheets or contact Taco at 401 942 8000 Taco reserves...

Reviews: