flow direction.

C. Electrical Wiring:

• All electrical wiring must be installed by a licensed elec-

trician in accordance with local and national codes and

regulations.

• Electrical supply and grounding wires must be suitable

for at least 90ºC (194ºF).

• 2400 Series circulators are thermally protected and do

not require external overload protection.

1. Be  sure  all  electrical  power  to  pump  is  disconnected

and locked-out before proceeding with wiring. 

2. Loosen capacitor/conduit box screw and remove cover.
3. Attach  appropriate  size  connector  to  one  of  the  two

knock-out holes in the capacitor/conduit box.

4. Using minimum 18 AWG wire, connect the hot and neu-

tral  leads  from  the  electrical  supply  to  the  respective

black and white leads in the capacitor box.

5. Connect the ground wire to the green ground screw in

the capacitor box.

6. Replace capacitor/conduit box cover.
7. Insert plastic plug provided in unused knock-out hole.

SYSTEM START-UP:

1. Prior to pump start-up, the system should be thoroughly

cleaned,  flushed  and  drained  to  prevent  damage  to

seal surfaces.

2. Open isolation valves and re-fill system with clean water.

Check for any leaks.

3. Vent all air from system at an air vent located at the

high point in the system.

4. Start circulator to check for proper operation.

PERIODIC INSPECTION, MAINTENANCE:

Taco 2400 Series Hi-Capacity circulators are designed to

provide  years  of  trouble-free  service.  However,  periodic

inspection and routine maintenance are recommended for

all hydronic systems and mechanical equipment. If any evi-

dence  of  leakage  or  damage  is  present,  take  preventive

steps to repair or replace the circulator immediately. 

REPLACING  THE  MECHANICAL  SEAL: 

Refer  to  Fig.  2

on back page.

1. Follow steps 1 thru 5 in section “Removal of existing

pump from system piping”.

2. Loosen the four body bolts that attach the motor hous-

ing to the casing. While supporting the motor, remove

the  four  bolts  and  carefully  remove  the  motor  and

impeller assembly from the casing.

3. To  remove  the  impeller,  first  insert  a  screwdriver  into

the motor ventilation slots to make contact with one of

the rotor cooling fins. While locking the rotor in place

with  the  screwdriver,  turn  the  impeller  clockwise  to

loosen and remove from shaft.

4. Remove the seal assembly from the shaft.

Note:

2400 models with “3P” suffix  are provided with a

3-piece rotating seal.

5. Remove  the  face  plate  from  the  motor  housing.  To

remove face plate, gently pry it away from the housing.

6. Remove the old seal seat and cup. Lubricate the new

cup with soapy water and install new parts in the face

plate recess. Replace the face plate to its original posi-

tion. Carefully tap the face plate evenly into the recess

in the motor housing.

7. Clean the impeller shaft before installing the new seal.
8. Lubricate the impeller shaft with soapy water. Do not

install new seal on a dry impeller shaft or damage to

seal may result.

9. Slide  the  new  carbon  seal  and  spring  assembly  onto

the shaft until it contacts the silicon-carbide seal seat.

10. While holding the rotor in place as in Step 3, thread the

impeller onto the shaft in a counter-clockwise direction

until it stops. Check to make sure the pump will rotate.

If the impeller will not spin freely, contact Taco Technical

Support at 1-401-942-8000.

11. Remove old body gasket and replace with new gasket

provided in seal kit. Press gasket into seal face plate,

then attach motor to casing. Use caution not to pinch

body gasket or leaks may result.

12. Attach  the  pump  casing  to  the  motor  housing  and

secure with the four body bolts. Be sure flow arrow is

pointing in proper direction. Tighten the four bolts even-

ly in a criss-cross pattern to 65 (+/-15) in-lb of torque.

13. Re-install  circulator  into  system  using  new  flange

gaskets.  Refer  to  section  “Installation  of  2400  Series

Circulator”  for  complete  mounting  and  wiring  instruc-

tions.

CAUTION: Do not start the pump until the sys-

tem  has  been  completely  filled  and  vented.

Running  the  pump  dry  may  damage  the

mechanical seal and void warranty.

CAUTION: Do not allow screwdriver to make

contact  with  motor  windings  or  insulation.

Permanent damage to motor may result.

CAUTION: Do not allow screwdriver to make

contact  with  motor  windings  or  insulation.

Permanent damage to motor may result.

CAUTION:  The  majority  of  mechanical  seal

failures are due to poor media (fluid) quality

in  the  system.  To  maximize  seal  life,  media

quality  must  be  maintained  in  the  system,

and TDS (Total Dissolved Solids)/TSS (Total

Suspended  Solids)  should  not  exceed

500ppm  with  standard  Carbon/Silicon-

Carbide  seals.  The  use  of  inhibitor  based

glycols  is  acceptable,  but  additional

inhibitors  should  not  be  added. Always  fol-

low  the  glycol  manufacturer’s  specification

for  system  preparation  and  water  quality.

Treatment with silicates should not be used.

Failure to maintain media quality will void the

standard Taco warranty.

Summary of Contents for 2400 Series

Page 1: ...anion flanges on threaded pipe ends to ensure proper fit up and leak protection See Table 1 for companion flange set specifications 2 Minimize pipe strain on pump by using pipe hangers on Instruction Sheet 2400 Series Hi Capacity Circulator 102 361 SUPERSEDES December 19 2014 EFFECTIVE March 2 2015 Plant ID 001 3932 INSTALLER Please leave these instructions for owner s use CAUTION Taco 2400 Series...

Page 2: ...port suspend or brace pump motor or early failure may result Support provided by casing is sufficient for structural integrity of pump Fig 1 Installation Positions Models Connection 3 4 1 11 4 11 2 2 21 2 3 2400 10 3P 2400 20 3P 2400 45 3P 2400 50 3P Iron NPT 110 251F 110 252F 110 253F 110 254F Stainless Steel NPT 110 251SF 110 252SF 110 253SF 110 254SF Bronze Sweat 110 523BSF 110 524BSF 110 525BS...

Page 3: ...a 3 piece rotating seal 5 Remove the face plate from the motor housing To remove face plate gently pry it away from the housing 6 Remove the old seal seat and cup Lubricate the new cup with soapy water and install new parts in the face plate recess Replace the face plate to its original posi tion Carefully tap the face plate evenly into the recess in the motor housing 7 Clean the impeller shaft be...

Page 4: ... any application restrictions consult the applicable Taco instruction sheets or contact Taco at 401 942 8000 Taco reserves the right to provide replacement products and parts which are substantially similar in design and functionally equivalent to the defective product or part Taco reserves the right to make changes in details of design construc tion or arrangement of materials of its products wit...

Reviews: