9.  Troubleshooting the error codes:

Listed below are potential diagnostic error codes which will appear on the LCD display in case of a malfunction.

Testing the Sensors

A good quality test meter capable of measuring up to 5,000 k

(1 k

= 1000

) is required to measure the sensor resistance. In

addition to this, the actual temperature must be measured with a good quality digital thermometer.

First measure the temperature using the thermometer and then measure the resistance of the sensor at the Bumble Bee. The wires
from the sensor must not be connected to the circulator while this test is performed. The wiring terminals are easily removed by
pulling them from the circulator. Using the chart below, estimate the temperature measured by the sensor. The sensor and ther-
mometer readings should be close. If the test meter reads a very high resistance, there may be a broken wire, a poor wiring con-
nection or a defective sensor. If the resistance is very low, the wiring may be shorted, there may be moisture in the sensor or the
sensor may be defective. To test for a defective sensor, measure the resistance directly at the sensor location.

ERROR CODE*

DESCRIPTION

CORRECTIVE ACTION

SENSOR 1 MISSING

Supply sensor disconnected.

Reconnect sensor.

SENSOR 2 MISSING

Return sensor disconnected.

Reconnect sensor.

SENSOR 1 SHORTED

Bad sensor.

Replace sensor.

SENSOR 2 SHORTED

Bad sensor.

Replace sensor.

AC INPUT UNDER VOLTAGE

Low voltage problem.

Check power supply.

AC INPUT OVER VOLTAGE

High voltage problem.

Check power supply.

LOCKED ROTOR

Probable locked rotor or motor failure.

Replace pump.

MOTOR OVER CURRENT

Possible locked rotor.

Replace pump.

OVER TEMPERATURE

PC Board overheating.

Pump will reduce current and speed until PCB tem-
perature is acceptable. If speed falls below 1650
RPM, pump will stop on safety. Cycle AC power
OFF/ON to restart.

Flashing Displayed on LCD

SPEED

TACO

GRUNDFOS

WILO

B & G/XYLEM

ARMSTRONG

1

003

-

-

-

-

2

006

-

-

-

Compass-1

3

007
008
0015-1
0015-2

UP-15-42
UPS-15-58-1
UPS-15-58-2

Star S-21-1
Star S-21-2

NRF-25-1
NRF-25-2

Astro 230-1
Astro 230-2
Compass-2

4

0015-3

UPS-15-58-3

Star S-21-3

NRF-25-3
Eco-Vario

Astro 230-3
Compass-3

Pump Cross Reference (Constant Speed Mode):

Temperature

Resistance

Temperature

Resistance

Temperature

Resistance

Temperature

Resistance

°F

°C

°F

°C

°F

°C

°F

°C

-30

-34

234,196

30

-1

34,558

90

32

7,334

150

66

2,045

-20

-29

165,180

40

4

26,099

100

38

5,828

160

71

1,689

-10

-23

118,018

50

10

19,900

110

43

4,665

170

77

1,403

0

-18

85,362

60

16

15,311

120

49

3,760

180

82

1,172

10

-12

62,465

70

21

11,883

130

54

3,050

190

88

983

20

-7

46,218

80

27

9,299

140

60

2,490

200

93

829

MODE

TACO

GRUNDFOS

WILO

B & G/XYLEM

ARMSTRONG

Delta-T

008-VDT

Alpha 15-55

Stratos Eco

Eco-Auto

Compass

Pump Cross Reference (Delta-T Mode):

Summary of Contents for Viridian Delta-T

Page 1: ...y temperature return temperature and error code diagnostics Use with a Taco ZVC Zone Valve Control or SR Switching Relay for ON OFF operation Integral Flow Check IFC is included in carton Simply press into discharge flange if required Swivel flanged casing provides 360 rotation mounting flexibility BIO BarrierTM protects rotor and bearings from black iron oxide Whisper quiet operation 40dB INSTALL...

Page 2: ...NE 2 V2 V2 V3 V3 P P ZONE 3 ZONE 3 V2 V3 P AIR PURGING SEQUENCE BY ZONE LAST FIRST KEY VI V2 V3 SHUT OFF ISOLATION VALVE P TACO CIRCULATOR WITH IFC FF FAST FILL BOILER FEED VALVE PV4 PURGE VALVE RECOMMENDED PURGING STEPS 1 CLOSE V1 PV4 V2 2 OPEN V3 3 OPEN FF VALVE 4 OPEN V2 PV4 TO PURGE LAST ZONE FIRST ZONE 3 5 CLOSE FF VALVE 6 CLOSE V2 PV4 7 REPEAT STEPS 1 TO 6 FOR EACH ADDITIONAL ZONE PURGE ZONE...

Page 3: ... M ZV1 ZV2 ZV3 M M M M M SUPPLY T SENSOR WIRING RETURN SUPPLY T SENSOR WIRING RETURN 3 KEY VI V2 V3 SHUT OFF ISOLATION VALVE P TACO CIRCULATOR WITHOUT IFC INSTALLED FF FAST FILL BOILER FEED VALVE PV4 PURGE VALVE ZV ZONE VALVE RECOMMENDED PURGING STEPS 1 CLOSE V1 PV4 V2 2 OPEN V3 AND ZV3 3 OPEN FF VALVE 4 OPEN V2 PV4 TO PURGE LAST ZONE FIRST ZONE 3 5 CLOSE FF VALVE 6 CLOSE V2 PV4 7 REPEAT STEPS 1 T...

Page 4: ...sion be sure to add vibration dampeners to piping when mounting circulator to wall or floor joists ATTENTION Pour réduire la possibilité de transmission de bruit veillez à ajouter des amortisseurs de vibration à la tuyauterie lors du montage du circulateur sur des chevêtres de mur ou de plancher WARNING Risk of electric shock To reduce the risk of electric shock be certain that it is connected onl...

Page 5: ...sulter The VT2218 has 5 Operating Modes Delta T Varies speed to maintain a fixed temperature differential factory pre set mode Constant Speed 4 fixed speeds see pump curves on previous page to select desired performance Set Point Heat Increases speed to increase temperature includes Boiler Protection option Set Point Cool Increases speed to lower temperature Boiler Protection Varies speed to maint...

Page 6: ...In Constant Speed mode the VT2218 will always start and run at the pre set Speed Level 1 through 4 Only watts will be dis played Temperature sensors are not active in this mode Set Point Heat Mode with Boiler Protection option 50 F 220 F default 105 F BP default 140 F In Set Point Heat mode the VT2218 will start at the lowest speed It then immediately switches to Variable Speed operation increasin...

Page 7: ...sor disconnected Reconnect sensor SENSOR 1 SHORTED Bad sensor Replace sensor SENSOR 2 SHORTED Bad sensor Replace sensor AC INPUT UNDER VOLTAGE Low voltage problem Check power supply AC INPUT OVER VOLTAGE High voltage problem Check power supply LOCKED ROTOR Probable locked rotor or motor failure Replace pump MOTOR OVER CURRENT Possible locked rotor Replace pump OVER TEMPERATURE PC Board overheating...

Page 8: ...to make changes in details of design construc tion or arrangement of materials of its products without notification TACO OFFERS THIS WARRANTY IN LIEU OF ALL OTHER EXPRESS WARRANTIES ANY WARRANTY IMPLIED BY LAW INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS IS IN EFFECT ONLY FOR THE DURA TION OF THE EXPRESS WARRANTY SET FORTH IN THE FIRST PARAGRAPH ABOVE THE ABOVE WARRANTIES ARE IN LIEU OF ALL ...