background image

5. To reverse the direction of rotation, first switch OFF the

power supply.

6. On three-phase motors, switch 2 of the 3 power leads

on the load side of the starter. On single-phase motors,
see the connection diagram on the motor nameplate.
Change the wiring as indicated.

Hazardous voltage.

Voltage can shock, burn

or cause death. Ground the pump motor correctly before
connecting to power supply per article 250-80 of National
Electrical Code (NEC) in the U.S., or the Canadian
Electrical Code (CEC), as applicable.

7. Switch on the power supply and recheck the direction of

motor rotation. 

Starting

1. If a suction line isolation valve has been installed, check

to be sure that it is completely opened.

2. For initial starting, the isolation valve in the discharge

pipe should be almost closed.

3. Start the pump.
4. When the piping system has been filled with liquid,

slowly open the discharge isolation valve until it is
completely open. Opening the valve too fast may result
in water hammer in the discharge pipe. If the pump or
system start to rattle, the pump is cavitating; to avoid
damage to the pump, reduce the flow through the
discharge isolation valve until the rattling stops. If this
does not give adequate flow for your installation, call
your installer or system designer.

5. Record the voltage and amperage of the motor. Adjust

the motor overloads if required.

6. If pressure gauges have been installed, check and record

operating pressures.

7. Check all controls for proper operation.

Motor Bearings

For the greasing schedule and greasing procedure of the
motor bearings follow the motor manufacturers
recommendations.

Calculating Minimum Inlet Pressure:

Minimum inlet pressure is required to avoid cavitation in
the pump and is calculated as follows:

H = Pb  - NPSHR - Hf - Hv - Hs
H = Minimum Inlet Pressure in Feet of Head
Pb = Barometric Pressure in Feet
1 Bar = 29.92 inches of Mercury (Hg)
1 PSI = 2.31 Ft of Head
1 Bar = 33.5 Ft. of Head
NPSHR = Net Positive suction head required.  To be read
from the NPSHR curve, Figure 8, at the highest flow the
pump will be delivering.
Hf = Friction Loss in suction pipe in ft of head
Hv = Vapor pressure in feet of head (See Table VI).
Hs = A safety margin of 1.64 ft of head

Example for VM04:

If:

Flow = 60 GPM
Pb = 1 Bar = 29.92 Inches of Mercury*
(Convert from Bar to Feet of Head)
Inches of mercury = 1.33’ inches of mercury
T = 100° F
NPSHR = 10’ (See Figure 7)
Hf = 10’ of 2” Steel Pipe @ 11.9’ of loss per 100’ 
of Pipe (Hf = 11.9’/10’ = 1.19’)
Hv = 2.195’ (from Table VI)
Hs = 1.64’ (safety factor from above)

Then:

H = 33.5’* - NPSHR** - Hf - Hv - Hs
H = 33.5’ - 10’ - 1.19’ - 2.195’ - 1.64 = 18.475’
H = 18.475’ = Minimum Inlet Pressure

* 1 Bar = 14.5 PSI x 2.31 Ft of Head = 33.5’

7

5

10

15

20

30

25

0

10

20

30

40

50

60

70

80

90 100 110 120

NPSHR in Feet

Flow in GPM

VM06

VM04

VM02

VM01

FIGURE 8 - VM01 through VM06
Net Positive Suction Head Requirement (NPSHR)

Temperature

Vapor Pressure

Absolute Pressure

in °F (°C)

in PSIA (kPa)

in Feet (M) of Water

32 (0)

0.089 (.61)

0.205 (.062)

40 (4.4)

0.122 (.84)

0.281 (.086)

60 (15.6)

0.256 (1.77)

0.592 (.180)

80 (26.7)

0.507 (3.50)

1.172 (.358)

100 (37.8)

0.95 (6.55)

2.195 (.669)

120 (48.9)

1.695 (11.69)

3.914 (1.193)

140 (60.0)

2.892 (19.94)

6.681 (2.036)

160 (71.1)

4.745 (32.72)

10.961 (3.341)

180 (82.2)

7.515 (51.84)

17.36 (5.291)

200 (93.3)

11.529 (79.49)

26.632 (8.117)

210 (98.9)

14.125 (97.39)

32.629 (9.945)

212 (100)

14.698 (101.34)

33.952 (10.349)

220 (104.4)

17.188 (118.51)

39.704 (12.102)

230 (110.0)

20.78 (143.28)

48.002 (14.631)

240 (115.6)

24.97 (172.17)

57.681 (17.581)

248 (120.0)

28.79 (188.51)

66.505 (20.271)

TABLE VI – Vapor Pressure of Water

Summary of Contents for VM0102

Page 1: ... and Three Phase 60 Cycle Record the following information from the motor and pump nameplates for future reference Pump Model No Bill of Material No Motor Model No Motor Serial No H P Volts Hz Ph Rated Amp Draw Taco Inc 1160 Cranston Ave Cranston RI 02920 BE807 TACO 12 5 06 ...

Page 2: ...y glasses at all times when working on pumps INSPECT THE SHIPMENT The vertical multistage centrifugal inline pump has been carefully inspected and packaged to assure safe delivery Inspect the pump and fittings and report to the carrier any items which are damaged or missing CONFIRM YOU HAVE THE RIGHT PUMP APPLICATIONS AND OPERATING RANGES Multistage in line centrifugal pumps are designed for liqui...

Page 3: ...12 3 8 11 1 8 5 1 4 2 25 5 8 7 1 8 VM0204 13 1 2 11 1 8 5 3 4 2 1 8 26 5 8 7 1 4 VM0205 14 1 2 12 5 3 4 2 1 8 28 5 8 7 1 4 VM0206 16 13 5 8 6 7 8 2 7 8 32 1 2 8 1 2 VM0207 18 1 8 13 5 8 6 7 8 2 7 8 34 5 8 8 1 2 VM0208 18 1 8 13 5 8 6 7 8 2 7 8 34 5 8 8 1 2 VM0210 20 1 4 15 1 4 8 3 3 8 38 7 8 10 5 8 VM0212 22 3 8 15 1 4 8 3 3 8 41 10 5 8 VM0214 24 1 2 15 1 4 8 3 3 8 43 1 8 10 5 8 VM0216 26 5 8 15 1...

Page 4: ...ling and lubrication of the pump See Table III Run the bypass relief valve and discharge pipe to a floor drain or a tank for collection Suction pipe should be adequately sized See Table IV and run as straight and as short as possible to keep friction losses to a minimum Pipes valves and fittings must have a pressure rating equal to or greater than the maximum system pressure Pressure check the dis...

Page 5: ...ied electrician in accordance with the National Electrical Code and all local codes and regulations Make sure that the motor voltage phase and frequency match the incoming electrical supply The proper operating voltage and other electrical information can be found on the motor nameplate These motors are designed to run up to 10 of the nameplate rated voltage The wiring connection diagram can be fo...

Page 6: ...tion pipe and the pump are completely filled with liquid 4 Replace the vented priming plug and tighten it securely 5 Repeat steps 1 4 until the pump is primed NOTICE Please turn to Starting Page 7 before proceeding any further No Flow Operation This pump must not operate at no flow To prevent no flow operation install a bypass orifice sized to allow the minimum rate of flow to pass the pump at all...

Page 7: ...lating Minimum Inlet Pressure Minimum inlet pressure is required to avoid cavitation in the pump and is calculated as follows H Pb NPSHR Hf Hv Hs H Minimum Inlet Pressure in Feet of Head Pb Barometric Pressure in Feet 1 Bar 29 92 inches of Mercury Hg 1 PSI 2 31 Ft of Head 1 Bar 33 5 Ft of Head NPSHR Net Positive suction head required To be read from the NPSHR curve Figure 8 at the highest flow the...

Page 8: ...ws that hold the motor and the motor bracket together then tighten evenly and diagonally See Table VIII Page 11 for torque specifications 12 Reinstall the coupling pin Key No 5 in the shaft 13 Reinstall the coupling halves Key No 2 on the pump and motor shaft Make sure to engage the couping pin Key No 5 NOTICE Be sure coupling surfaces are thoroughly clean prior to assembly 14 Snug up the socket h...

Page 9: ... only 12 Clean the O Ring seat and install a new O Ring Key No 21A VM01 and VM02 only 13 Install a new lower sleeve O Ring 14 Install the new stack without the stainless steel sleeve NOTICE Be sure to align either the small priming hole or the suction interconnector pin hole located on the bottom stage of the stack properly in the base of the Suction Discharge Key No 21 See Figure 11 15 Use a rubb...

Page 10: ...k and clean all sealing and gasket surfaces with a clean wet cloth Replace all seals gaskets and O Rings 1 Turn the motor bracket Key No 6 upside down 2 Moisten the seal seat in the motor bracket with a small amount of water 3 Lubricate the larger diameter O Ring Key No 15A with a small amount of water and install it on the stationary half of mechanical seal Key No 15B 4 Press the stationary half ...

Page 11: ...he pump meets required performance and is operating smoothly and quietly 2 There are no leaks 3 The motor is not overheating 4 Remove and clean all strainers and filters in the system 5 Verify amp draw check motor amperage 6 Pump wear rings and shaft require no regular maintenance 11 Coupling Motor Staybolt Stack Nut Socket Head Socket Head Socket Head Capscrew Capscrew Hex Hex Hex Hex Screw Screw...

Page 12: ...er 12 Lockwasher 13 Capscrew 14 Spring Ring 15 Seven Part Mechanical Seal Includes 15A thru 15G 15A O Ring Larger Diameter 15B Stationary Half of Mechanical Seal 15C Rotating Half of Mechanical Seal 15D O Ring Smaller Diameter 15E Flat Washer 15F Spring 15G Mechanical Drive Ring 16 Replacement Stack Kit Incl Key Nos 16A thru 16L Key No Description 16A Shaft 16B Stop Ring 16C Mechanical Seal Spacer...

Page 13: ... Plug 11 Flat Washer 12 Lock Washer 13 Capscrew 14 Conic Spring 15 Seven Part Mechanical Seal Includes 15A thru 15G 15A O Ring Larger Diameter 15B Stationary Half of Mechanical Seal 15C Rotating Half of Mechanical Seal 15D O Ring Smaller Diameter 15E Flat Washer 15F Spring 15G Mechanical Drive Ring Key No Description 16 Replacement Stack Kit Incl 16A thru 16L 16A Shaft 16B Stop Ring 16C Mechanical...

Page 14: ... OR FITNESS FOR USE AND THERE ARE NO WARRANTIES WHICH EXTEND BEYOND THE DESCRIPTION CONTAINED HEREIN TACO INC WILL NOT BE LIABLE FOR ANY SPECIAL INCIDENTAL OR CONSEQUENTIAL DAMAGES Taco Inc 1160 Cranston Street Cranston RI 02920 401 942 8000 14 TROUBLESHOOTING GUIDE Hazardous voltage and risk of sudden starts Disconnect all power to the pump before servicing or working on pump Make sure that power...

Page 15: ...15 ...

Page 16: ......

Reviews: