Instruction & Operating Manual

TA-15/6P...200/6P

Drive does not run when switched to "DRIVE

ON"

6.1 Fault location

Symptom

LED 8 (Power on) does not light up.

+/- 15V (LED 5, LED 2) does not light up.

Possible causes

a) Defective fuse Si 1 on the upper PC-board
b) One phase is missing
c) No supply voltage (115V) for relays d1 and d2.

Check voltage (115V) between terminals 9 and

16

d) LED 8 or D37 defect.

a) One phase is missing
b) Check power supply, m/- 24V

a) Motor load too high.
b) Drive operates at the current limit, LED 6 lights

up.

c) Current limit is adjusted too low, drive switches

off after short operation.

d) Defective speed potentiometer.

a) Check switch-on contact (terminals 1 and 9)
b) Defective fuse Si 1 on the upper PC-board
c) LED 8 (Power on) does not light up
d) LED 9 does not light up however LED 11 lights

up, jumper or quick-stop contacts terminals 24

and 25 not closed.

e) No reference voltage (terminal 2) voltage is

variable by speed potentiometer from 0 to 10V

f) Relay d6 (malfunction) not energised. LED 3,

red, lights up. Confirmation of malfunction is

only possible if LED 4 and LED 6 do not light

up and if the field control is not activated.

g) Check three phase line input.
h) Defective fuses Si 1, Si 2 or Si 3 on lower PC-

board.

i) Check field voltage and field current.

a) I x R compensation P3 is set too high.
b) Defective tachometer or tachometer leads.
c) Stability potentiometer P8 is wrong adjusted.
d) Auxiliary winding of the d.c. motor is wrong

connected

e) Triggerinig of one Thyristor temporarely

interrupted.

Output voltage does not increase when

speed potentiometer is turned up

Drive does not run stable

Summary of Contents for TA-15/6P

Page 1: ...ntriebstechnik de TA_BA TA 15 200_6P_EN PDF The German text applies in cases of doubt TA 15 6P 200 6P Instruction and Operation Manual Caution There is always a risk involved in the handling of electr...

Page 2: ...al 4 and 9 Jog Speed ON Closing contact Drive remains switched on until contacts open 1 Technical Data r Motor Zero Speed Indicator r Current Limit control r Tachometer Signal control r Electronic cir...

Page 3: ...or speed r When tachometer feedback is utilized jumpers I and VII and resistor R82 must be removed r Jumpers IX and X must be installed and jumper VIII must be removed r The adaption of the tachometer...

Page 4: ...installed or when the reference speed is changed Current limit P5 Adjustment of the requested max armature current adjust the nominal motor current Minimum Speed P6 Adjustment of min speed during ope...

Page 5: ...center position Potentiometer P3 IxR Compensation set fully counter clockwise Potentiometer P8 Stability set in center position Potentiometer P7 Jog speed set fully counter clockwise Potentiometer P1...

Page 6: ...iometer P8 This potentiometer must be adjusted so that the drive operates without overshoot in the presset speeds 5 2 Tachometer feedback control 1 Check all connections with an Ohm meter for grounds...

Page 7: ...tive fuse Si 1 on the upper PC board c LED 8 Power on does not light up d LED 9 does not light up however LED 11 lights up jumper or quick stop contacts terminals 24 and 25 not closed e No reference v...

Page 8: ...Type TA 15 6P 200 6P a Too low adjustment of current limit b Motor is overloaded mechanical defect on machine or motor Check motor brushess c Supply voltage 15V for electronic circuit incorrect or mi...

Page 9: ...VITESSE D ACCROCHAGE Reglerfreigabe ALTERNATIF FIELD DC TACHOMETER Sollwertpotentiometer Schleichgang JOG SPEED DEBLOCAGE RUN EXCITATION Feld Anker Netz INDUIT ARMATURE ALIMENTATION EN LINE FAULT DOC...

Page 10: ...changes reserved Instruction Operating Manual TA 15 6P 200 6P 8 Mounting template TA 40 6P TA 60 6P 200 6P TA 15 6P 310 270 165 7 x 13 270 350 KL1 310 270 165 7 x 13 400 270 460 40 KL3 KL1 KL2 530 486...

Reviews: