On-Demand Water Heater Installation Manual and Owner’s Guide
Operation
Controllers
Built-in controller
Remote controller
13.
The following steps will set the
temperature drop
that
must occur before the recirculation pump will turn off
.
Temperature drop below set temp. at which
pump turns off
°F
-5* -10 -15 -20 -25 -30 -35
°C
-3
-6
-8
-11 -14 -17 -19
*Preset at the factory. (Default)
Press the
"HOT"
button or the
"COLD"
button to select
the temperature at which the pump will turn off.
14.
Press the
"PUMP"
button on the controller to save your
settings.
When the controller is on, the current time and set
temperature in the display turns on.
When the controller is off, the display turns off.
OR
- Selecting a pump timer-
Operation
Controllers
Built-in controller
Remote controller
1.
Both
PUMP TIMERS
have a default setting of OFF from
the factory.
Press the
"PUMP"
button on the controller
to set the mode. (The options are shown in step 3.)
This operation is available regardless of the ON/OFF
status of the controller.
2.
The current status of the
PUMP TIMER
will flash for 10
seconds. During this time, you can change the mode.
Otherwise, the mode will remain unchanged.
3.
Press the
"PUMP"
button on the controller in order to
change the option. The order of the option is as follows.
PUMP TIMERS 1 & 2
activated
NO PUMP TIMER
activated
Only PUMP TIMER 1
activated
Only PUMP TIMER 2
activated
4.
Press the
"INFO"
button on the controller in order to
save your setting.
OPERATION
Controller settings