GAS SUPPLY AND PIPING SIZING
This unit needs a manual gas control valve (system shutoff valve) that must be placed on the
unit before it is connected to the gas supply line.
Check the gas inlet pressure and that the type of gas matches the rating plate located on
your water heater. Insufficient gas pressure will cause your MOBIUS Water Heater to be
inefficient and not work properly. Size the gas supply piping correctly following
ANSI233.1/NFPA 54, or by local code.
The minimum and maximum inlet gas pressures are listed below:
Natural Gas
Min. 5” WC
Max. 10.5” WC
Propane Gas
Min. 11” WC
Max. 14” WC
12"
12"
4"
12"
12"
2"
2"