- 43 -
ADDITIONAL CLEARANCES
Please follow all local and national codes in regards to proper termination clearances. In the absence of
such codes, the following clearances can be used as guidelines. Local codes supersede these
guidelines.
For sidewall terminations
Exhaust termination
1ft.
1ft.
2ft.
Inside
corner
Air supply inlet
3ft.
3ft.
3ft.
Direct vent termination
1ft.
1ft.
Inside
corner
2ft.
For multiple sidewall exhaust
terminations (e.g. multi-unit
systems), an exhaust termination
must be at least 1 ft. away from
another exhaust termination. An
exhaust termination must also be
at least 2 ft. away from an inside
corner (if the adjacent wall is less
than 2 ft. of length, the minimum
required distance away from the
inside corner will be equal to the
length of the wall).
For direct-vent sidewall
terminations that use two
separate penetrations for the
intake and exhaust, distance
the intake and exhaust
terminations at least 3 ft. away
from each other, no matter the
orientation.
For multiple-unit, direct-vent
sidewall terminations that
combine the intake and exhaust
into a single penetration, space
each direct-vent termination at
least 1 ft. away from each other,
no matter the orientation. A
direct-vent termination must also
be at least 2 ft. away from an
inside corner (if the adjacent wall
is less than 2 ft. of length, the
minimum required distance away
A
A
2ft.
Exhaust
termination
Air intake
A
A
A
Air intake
Exhaust termination
For multiple-unit rooftop terminations (whether for standard indoor or direct-
vent installations) space all exhaust and intake terminations in accordance
with local codes. An exhaust termination must be spaced from a wall or
surface in accordance with local codes as well. In the absence of such a
code, an exhaust termination must be a horizontal distance of at least 2 ft.
away from a wall or surface.
Exhaust and/or direct-vent
sidewall terminations should
be at least 2 ft. away from an
opposite surface/wall. Do not
place the termination directly
in front of an opening into a
building.
A: in accordance with local codes
For rooftop terminations
2ft.
Exhaust
termination