Using in Series/Parallel Operation
132
Load Wire Connection
Connect wires from the Slave’s minus terminal to the Master’s plus terminal.
Connect wires from the Slave’s plus terminal to the Load’s plus terminal.
Connect wires from the Master’s minus terminal to the Load’s minus terminal.
Control Terminal Wiring
Connect wires from the Slave’s external control connector No. 21 terminal to the Master’s plus terminal.
Connect wires from the S
eries control connector of the Slave to the Master’s minus terminal.
Connect wires from the Slave’s isolatedcontrol connector No. 15 terminal to the Master’s external control
connector No. 9 terminal.
Connect w
ires from the Slave’s isolated control connector No. 12 terminal to the Master’s external control
connector No. 10 terminal.
Connect w
ires from the Slave’s isolated control connector No. 16 terminal to the Master’s external control
connector No. 22 terminal.
Connect wi
res from the Master’s isolated control connector No. 15 terminal to the Slave’s external control
connector No. 9 terminal.
Connect wi
res from the Master’s isolated control connector No. 16 terminal to the Slave’s external control
connector No. 22 terminal.
* The signal lines of
,
,
,
, and
should be stranded wires.
Operation
1. Setting the Master
Press the Function "FUNC." key.
Select Item 10 with VOLTAGE dial.
Change the set value to 2 with CURRENT dial.
Press the FUNC. key again to finalize settings.
* For the function item 10 "Toggling Output ON/OFF with External Contacts", refer to page 137.
2. Setting the Slave
Press the Function "FUNC." key.
Select Item 73 with VOLTAGE dial.
Change the set value to 1 (Slave Mode) with
CURRENT dial.
Press the FUNC. key again to finalize settings.
Turn the POWER switch OFF.
* The device will operate as a Slave unit when the POWER switch is turned ON again. At that time, the
"OUTPUT" lamp is lit.
3. Order of turning on “POWER” switch.
Turn on the power switch in orde of slave, then master.
Toggling Output ON/OFF with External Contacts in Series Operation
For the connecting refer to page141.
By setting this item, output ON of the Master is
prohibited when the input power of the Slave is
OFF.
When returning to Master, set FUNCTION Item 73
to 0, Item 51 to 0, and Item 60 to 1.
MEMO
MEMO
Summary of Contents for HX-S-G2 Series
Page 165: ...Special Loads 165 This page is blank...
Page 169: ...Maintenance 169 This page is blank...
Page 211: ...Specifications 211 External Diagrams 1 HX S 030 200G2 F I...
Page 212: ...Specifications 212 2 HX S 030 400G2 F I...
Page 213: ...Specifications 213 3 HX S 060 100G2 F I...
Page 214: ...Specifications 214 4 HX S 060 200G2 F I...
Page 215: ...Specifications 215 5 HX S 0120 50G2 F I...
Page 216: ...Specifications 216 6 HX S 0120 100G2 F I...
Page 217: ...Specifications 217 7 HX S 0400 15G2 F I...
Page 218: ...Specifications 218 8 HX S 0400 30G2 F I...
Page 219: ...Specifications 219 9 HX S 0500 12G2 F I...
Page 220: ...Specifications 220 10 HX S 0500 24G2 F I...
Page 221: ...Specifications 221 11 HX S 01000 6G2 F I...
Page 222: ...Specifications 222 12 HX S 01000 12G2 F I...
Page 223: ...Specifications 223...
Page 239: ......