Preparation and Connection
18
!
Mandatory
Verify that the main power supply for the power supply is turned off when connecting loads.
Prohibited
Do not wire loads when voltage is being outputted from the power supply.
!
Mandatory
Use wires with sufficient cross section areas for load currents.
For selecting wires,
r
efer to Appendix 4 "Load Current vs Recommended Cross Section Area"
(page
!
Mandatory
Attach crimp-style terminals to wires and securely fasten.
If insecurely fastened, wires may become deformed or burn out due to the generated heat at
connection points.
!
Mandatory
Please to use it always attached parallel connection terminal cover (already factory attached).
* 30V type has not been attached.
!
DANGER
!
CAUTION
Parallel
connection
terminal cover
Summary of Contents for HX-S-G2 Series
Page 165: ...Special Loads 165 This page is blank...
Page 169: ...Maintenance 169 This page is blank...
Page 211: ...Specifications 211 External Diagrams 1 HX S 030 200G2 F I...
Page 212: ...Specifications 212 2 HX S 030 400G2 F I...
Page 213: ...Specifications 213 3 HX S 060 100G2 F I...
Page 214: ...Specifications 214 4 HX S 060 200G2 F I...
Page 215: ...Specifications 215 5 HX S 0120 50G2 F I...
Page 216: ...Specifications 216 6 HX S 0120 100G2 F I...
Page 217: ...Specifications 217 7 HX S 0400 15G2 F I...
Page 218: ...Specifications 218 8 HX S 0400 30G2 F I...
Page 219: ...Specifications 219 9 HX S 0500 12G2 F I...
Page 220: ...Specifications 220 10 HX S 0500 24G2 F I...
Page 221: ...Specifications 221 11 HX S 01000 6G2 F I...
Page 222: ...Specifications 222 12 HX S 01000 12G2 F I...
Page 223: ...Specifications 223...
Page 239: ......