Specifications
------------------------------------------------------------------------------------
179
Protection Functions
Specification/Models
400H
400HA
800H
800HA
1600H
1600HA
Over Voltage
Protection (OVP)
Range
10V~704V
Accuracy
±(0.2% of set value ±5digit(0.5V)) *13
Operation
Shuts off output, stops switching, or cuts off input switch *14
Over Current
Protection (OCP)
Range
0.1A~5.5A
0.2A~11.0A
0.4A~22.0A
Accuracy
±(0.6%of set value ±5digit(0.05A)) *13
Operation
Shuts off output, stops switching, or cuts off input switch *14
Over Power Protection Circuit
Restricts output voltage and output current if the output power exceeds the rated output
and if the internal power loss exceeds the reference value.
Automatically recovers once values return within ratings.
Over Heating Protection Circuit
・Stops switching, shuts off output, and displays alarms if the temperature of the radiating
section heat exceeds 85℃ (1600L/LA:95℃) due to stopped fan motor, etc.
・Welds temperature fuses, built in the Inrush Limiting Resistors, at 135℃.
Excessive Input Current Protection
Fuse
10A
Fuse
20A
Protected by
20A Fuse/unit
*14 : Input switch cut-off turns the power supply’s internal input power relays OFF.
This can be selected for 1600H/1600HA
Remote Sensing
・ Able to compensate a voltage drop, due to lead wire up to load, of up to 1V one-way.
・ Restricts the rise in output voltage within 10mV if sensing lines are opened.
・ During remote sensing, the output power can be set to a maximum of 642V at the power supply’s output terminals.
Also, the output power can be set within the rating.
Summary of Contents for ZX-S-H Series
Page 1: ...Constant Voltage Constant Current DC Power Supply series Instruction Manual ...
Page 37: ...Basic Operations 33 This is blank page ...
Page 59: ...Useful Function 55 This is blank page ...
Page 115: ...Using via Digital Data Communication 111 This is blank page ...
Page 141: ...Controlling with External Analog Contact Signals 137 This is blank page ...
Page 147: ...Special Loads 143 This is blank page 守 ...
Page 188: ... 184 付録 External Diagrams ZX S 400H 400HA 4 M3 ...
Page 189: ...Appendix 185 ZX S 800H 800HA ...
Page 190: ...Appendix 186 ZX S 1600H 1600HA ...