Specifications A
Taktis Fire Control Panel - Installation Manual
Man-1154-In, Revision E01.02
109 of 156
Earth Fault Indication
An earth fault indication occurs on the Taktis Fire Control Panel when a minimum of 30K Ohms exists between
earth-ground and either DC RTN or +24 VDC of the power-supply.
System Power
Standby and alarm conditions of the fire control panel are expressed in volt-amperes VA at the primary of the
power supply. Secondary standby and alarm currents of the power supply are determined under no load
conditions and occur during AC power failure at the primary. The resulting no-load current draw from the
5.25 Amp or 10.25 Amp Power Supply occurs from standby-battery operation on the secondary.
All loads of the fire control panel exclude external loads except End Of Line (EOL) devices. “Primary” loads of
the fire control panel assume a fully charged battery. Alarm currents are dependent on the number of active
zones and the number of zones in the extinguishant-state.
Standby and Alarm Current
Standby and Alarm Currents are provided below for 115 VAC and 230 VAC models of the 5.25 A and 10.25 A
Power Supply. The data includes current of the fire alarm control panel in 2 and 4 loop conditions.
Two loop operation includes System Board A Module, System Board B Module and the Dual Loop Module.
Two loop operation represent the minimum board configuration of the Taktis Fire Control Panel.
Four loop operation includes the System Board A Module, System Board B Module and two
Dual Loop Modules.
5.25 A, 115 VAC Power Supply
Loops
Standby (mA)
Alarm (mA)
Description
2
244 mA @ 115 VAC
272 mA @ 115 VAC
Line current for standby and alarm when battery
current is less than 30 mA.
560 mA @ 24 VDC
650 mA @ 24 VDC
Battery current for standby and alarm when power
failure condition occurs on the AC line.
4
274 mA @ 115 VAC
302 mA @ 115 VAC
Line current for standby and alarm when battery
current is less than 30 mA.
680 mA @ 24 VDC
760 mA @ 24 VDC
Battery current for standby and alarm when power
failure condition occurs on the AC line.
Summary of Contents for Incite Fire S3
Page 1: ...Taktis Operating Instructions Part Number OPIN 000004IN Revision E01 02 Date 18 09 2015...
Page 2: ......
Page 3: ......
Page 4: ...D F C B A E...
Page 5: ...I G H J...
Page 6: ......
Page 7: ......
Page 8: ......
Page 9: ......
Page 10: ......
Page 11: ......
Page 12: ......
Page 13: ......
Page 14: ......
Page 15: ......
Page 16: ......
Page 17: ......
Page 19: ......
Page 20: ......
Page 21: ......
Page 22: ......
Page 23: ......
Page 24: ......
Page 25: ......
Page 26: ......
Page 27: ......
Page 28: ......
Page 29: ......
Page 30: ......
Page 31: ......
Page 32: ......
Page 33: ......
Page 34: ......
Page 35: ......
Page 36: ......
Page 37: ......
Page 38: ......
Page 39: ......
Page 40: ......
Page 41: ......
Page 42: ......
Page 43: ......
Page 44: ......
Page 45: ......
Page 46: ......
Page 47: ......
Page 48: ......
Page 49: ......
Page 50: ......
Page 51: ......
Page 52: ......
Page 53: ......
Page 54: ......
Page 55: ......
Page 56: ......
Page 57: ......
Page 58: ......
Page 59: ......
Page 60: ......
Page 61: ......
Page 62: ......
Page 63: ......
Page 64: ......
Page 65: ......
Page 66: ......
Page 67: ......
Page 68: ......
Page 69: ......
Page 70: ...Part Number OPIN 000004IN Revision E01 02 Date 18 09 2015...
Page 211: ......