background image

www.tamcodampers.com

© T.A. Morrison & Co. Inc., 2017

2

6

4

6

1

Back or 

Rear Side 

of Damper

Front, Label, 

Jackshaft,

or Actuator

Side of Damper

2

1

4

3

3

4

3

5

Back or 

Rear Side 

of Damper

Front, Label,

Jackshaft,

or Actuator

Side of Damper

Front, Label,

Jackshaft,

or Actuator

Side of Damper

Back or Rear

or Wall Side 

of Damper

2

7

6

4

1

Opening

8

Smoke

Barrier

INSTALLATION PROCEDURES FOR  |  

Smoke Damper Install Types

3

*LEGEND:

1. TAMCO Smoke Damper 4. Fastener

7. Extended flange frame

2. Silicone caulk

5. Sleeve /duct

8. Substrate fastener

3. Clip angle

6. Flanged to Duct connection

*SEE 

LEGEND 

BELOW

²APPROVED SILICONE CAULK:

 

Dow Corning:

RTV Silicone Silastic 732, Xiameter 732, Xiameter SLT 5100

 

Momentive 

      Performance Materials:

RTV 108

a. Measure and if necessary, adjust the duct or opening to ensure that it 

is true and square.

b. Run a bead of silicone caulk² around the inside perimeter of the 

flange, where it comes into contact with the damper frame, to 

prevent leakage at the connection point between the duct and 

damper frame. This step may be performed now or after step "d", 

once the smoke damper has been fastened in place. 

c. Position the Flanged to Duct mount type smoke damper, so that it is 

adjacent to the flanged duct.

d. Secure the flanged connections together using, as a minimum; #8 

sms screws, 

3

/

16

” 

(4.8 mm)

 rivets, #12 bolts/nuts, flange mount system, 

or tack welds, placed at 12” 

(305 mm)

 oc intervals. Fasteners should 

begin at no more than 6” 

(152 mm)

 from the corners. A minimum of 1 

fastener is required per side.

a. Dampers should be ordered from the factory with extended rear 

flanges if they are to be wall mounted.

b. Measure both the wall opening and the damper ID, to ensure that the 

two dimensions are identical.

c. Run a bead of silicone caulk² around the perimeter of the damper 

flange face, where it will come into contact with the substrate upon 

installation. This is to prevent leakage between the damper and the 

wall. Caulking may be applied at this step, or following step "e", once 

the smoke damper has been fastened in place.

d. Place the damper in the desired location on the wall, so that the 

inside of the damper's frame aligns with the edges of the wall 

opening.

e. Secure the damper to the wall using, as a minimum; #8 sms screws, 

3

/

16

” 

(4.8 mm)

 rivets, #12 bolts/nuts, ¼" 

(6.4 mm)

 Tapcons, or tack 

welds, placed at 12” 

(305 mm)

 oc intervals. Fasteners should begin at 

no more than 6” 

(152 mm)

 from the corners. A minimum of 1 fastener 

is required per side.

a. Determine the location where the damper is to be installed inside 

the duct or sleeve. This location must be within 24" 

(609 mm) 

of the 

smoke barrier.

b. Slide the damper into pre-determined sleeve or duct location. Ensure 

that the damper, sleeve, and/or duct are all square and true.

c. Situate the clips around the back or rear perimeter of the damper 

frame,  at a maximum of 12” 

(305 mm) 

on center (oc) intervals and so 

they begin at no more than 6” 

(152 mm)

 from the corners. A minimum 

of 1 clip is required per side. 

d. Fasten clips to the duct first and then to the damper using, as a minimum; 

#8 sms screws, 

3

/

16

 (4.8 mm)

 rivets, #12 bolts/nuts, or tack welds. Clips 

are not required on the front (label) side of the damper. 

e. Run a bead of silicone caulk² around the inside perimeter of the back 

side of the damper, where it comes into contact with the sleeve or 

duct. It is not necessary to caulk around the front (label) side of the 

damper. If caulking is applied after installation, it is recommended to 

caulk around all clips to minimize leakage.  

IN DUCT INSTALL TYPE  

&

EXTENDED REAR FLANGE INSTALL TYPE (WALL MOUNT)  

&

FLANGED TO DUCT INSTALL TYPE  

&

Summary of Contents for 1000 SM Series

Page 1: ...e provided if the damper actuator is mounted inside the duct GENERAL INSTALLATION NOTES Smoke dampers must be installed square and free from racking to ensure proper operation and performance Dampers must be installed without stretching or compression to allow them to maintain their original factory adjustment thereby retaining their low leakage rating TAMCO Smoke Dampers are approved to be instal...

Page 2: ...LL TYPE SHOWN JACKSHAFT MOUNTED top view ACTUATOR WIRING MUST BE CONNECTED IN ACCORDANCE WITH LOCAL CODES ORDINANCES AND NEC CSA REGULATIONS MULTIPLE ACTUATORS MOUNTED ON A SINGLE UNIT SHALL BE WIRED TO A SINGLE POINT TO ALLOW SIMULTANEOUS OPERATION OPTIONS FOR ACTUATOR MOUNTING 2 ACTUATOR WIRING GUIDE Wiring used to connect each actuator shall be as a minimum No 16 ga AWM The minimum temperature ...

Page 3: ... dimensions are identical c Run a bead of silicone caulk around the perimeter of the damper flange face where it will come into contact with the substrate upon installation This is to prevent leakage between the damper and the wall Caulking may be applied at this step or following step e once the smoke damper has been fastened in place d Place the damper in the desired location on the wall so that...

Page 4: ...ont label and back rear side of damper assemblies c Attach each joiner to the damper frame members using as a minimum four 8 sms screws or rivets as shown in Figures A B d Install the bridge bracket connecting the lower sections Place the bridge bracket so that it is centered over the joint where all four damper sections meet e Fasten the Bridge Bracket in place using 20 bolts making sure they are...

Reviews: