background image

© 

T.A. Morrison & Co. Inc., 2017

INSTALLATION PROCEDURES FOR  |  MULTI-SECTION SMOKE DAMPER ASSEMBLIES 

4

INSTRUCTIONS BELOW ARE IN ADDITION TO APPLICABLE INSTALL TYPE INSTALLATION PROCEDURES.

MULTIPLE SECTION SMOKE DAMPER ASSEMBLIES SHOULD BE INSTALLED USING SAME FASTENERS AND 

FASTENING PATTERNS AS DESCRIBED IN THE INSTRUCTIONS FOR SINGLE-SECTION SMOKE DAMPERS. 

9

/

16

(14.3 mm)

±

1

/

8

"

 

(3.2 mm)

Min. #8 sms Screw

or 3/16" Rivet

2"

 

(610 mm) 

(

±¼"

 

(6.4 mm)

)

Damper

Frame

Damper

Frame

Joiner

Min. #8

sms Screw, or

3

/

16

” 

(4.8 mm)

 Rivet

FIG. A

(front view)

Min. ¼”

 

(6.4 mm) 

Bolt/Nut, 

#8 sms Screw, or 

3

/

16

 (4.8 mm)

 Rivet,

2” (+/- ¼“)

 [51 mm (+/- 6 mm)] 

from each end of the damper. 

Damper 

Blade 

Damper 

Linkage

Damper 

Frame

¼"-20

Bolt/Nut

Jackshaft Linkage

(if provided)

Rivet Nuts

(inserted into frame)

Bridge

Min. 14” 

(355 mm)

 

long,

secured with ¼"

 

(6.4 mm)

 

bolts

FIG. C

(top view)

ASSEMBLING SMOKE DAMPERS THAT ARE 
MULTIPLE SECTIONS HIGH:

a.  Slide joiners over frame members, where top and bottom sections 

meet.

b.  Joiners must be secured to both the front (label) and back (rear) side 

of damper assemblies.

c.  Attach each joiner to the damper frame members using, as a minimum, 

four #8 sms screws or rivets as shown in Figures A & B.

ASSEMBLING SMOKE DAMPERS THAT ARE 
MULTIPLE SECTIONS HIGH AND MULTIPLE 
SECTIONS WIDE: 

a.  Slide joiners over frame members, where top and bottom sections 

meet.

b.  Joiners must be secured to both the front (label) and back (rear) side 

of damper assemblies.

c.  Attach each joiner to the damper frame members using, as a 

minimum, four #8 sms screws or rivets as shown in Figures A & B. 

d.  Install the bridge bracket connecting the lower sections. Place the 

bridge bracket so that it is centered over the joint where all four 

damper sections meet.

e.  Fasten the Bridge Bracket in place, using ¼"-20 bolts, making sure 

they are secured in the pre-set, factory-supplied rivet nut holes. 

MULLION END CAPS

 

FOR FLANGED TO DUCT INSTALL TYPE, 

MULTI-SECTION DAMPER INSTALLATIONS  

 

>

Mullion end caps are provided with all multi-section dampers 

that are to be installed as Flanged to Duct Install Type.

 

>

These are required to prevent air flow from passing through 

open channels. (Mullion end caps are not intended for use as 

structural support.)

 

>

Caulk surfaces between mullion end caps and damper frame for 

an airtight seal.

 

>

Mullion end caps are not required for In Duct and Extended Rear 

Flange Install Type dampers. As such they are not provided as 

standard, but are available for order as separate parts.

Joiner

Joiner

Min. #8 

sms Screw, or 

3

/

16

” 

(4.8 mm)

 Rivet

Min. #8 

sms Screw, or 

3

/

16

 

(4.8 mm)

 

Rivet

FIG. B

(side view)

Joiner

Damper Section ID

 

Joiner width =

Damper Section ID

Less 0.5” 

(12.7 mm)

 

(± 0.125”

 

(3 mm)

)

 

(See Fig. A & B 

Details)

Bridge Bracket centered

where sections meet 

(See Fig. C Detail)

Frame members are designed

to overlap and are manufactured 

with aligned positioning holes. 

When dampers are positioned

correctly, holes will be aligned.

Joiner

Mullion End Cap

(at top and bottom)

Summary of Contents for 1000 SM Series

Page 1: ...e provided if the damper actuator is mounted inside the duct GENERAL INSTALLATION NOTES Smoke dampers must be installed square and free from racking to ensure proper operation and performance Dampers must be installed without stretching or compression to allow them to maintain their original factory adjustment thereby retaining their low leakage rating TAMCO Smoke Dampers are approved to be instal...

Page 2: ...LL TYPE SHOWN JACKSHAFT MOUNTED top view ACTUATOR WIRING MUST BE CONNECTED IN ACCORDANCE WITH LOCAL CODES ORDINANCES AND NEC CSA REGULATIONS MULTIPLE ACTUATORS MOUNTED ON A SINGLE UNIT SHALL BE WIRED TO A SINGLE POINT TO ALLOW SIMULTANEOUS OPERATION OPTIONS FOR ACTUATOR MOUNTING 2 ACTUATOR WIRING GUIDE Wiring used to connect each actuator shall be as a minimum No 16 ga AWM The minimum temperature ...

Page 3: ... dimensions are identical c Run a bead of silicone caulk around the perimeter of the damper flange face where it will come into contact with the substrate upon installation This is to prevent leakage between the damper and the wall Caulking may be applied at this step or following step e once the smoke damper has been fastened in place d Place the damper in the desired location on the wall so that...

Page 4: ...ont label and back rear side of damper assemblies c Attach each joiner to the damper frame members using as a minimum four 8 sms screws or rivets as shown in Figures A B d Install the bridge bracket connecting the lower sections Place the bridge bracket so that it is centered over the joint where all four damper sections meet e Fasten the Bridge Bracket in place using 20 bolts making sure they are...

Reviews: