AIR-IQ Air Flow Measurement Damper (ADMD)

 Packaged Solution

AIR

-IQ INS

TALL GUIDE_R3

INSTALLATION GUIDELINES

Summary of Contents for AIR-IQ

Page 1: ...0 561 3449 Toll Free Fax 800 668 8476 www tamcodampers com EBTRON Inc 1663 Hwy 701 S Loris SC USA 29569 Toll Free 800 2EBTRON 232 8766 Fax 843 756 1838 www ebtron com AIR IQ Air Flow Measurement Damper ADMD Packaged Solution AIR IQ INSTALL GUIDE_R3 INSTALLATION GUIDELINES ...

Page 2: ...nual TM_GTx116 under separate cover LIMITED PRODUCT WARRANTY DESCRIPTION AIR IQ products are warranted against defects in materials or workmanship for 36 months from the date of shipment Should the product or component parts qualify as a warrantable failure within this time period the product or component involved will be repaired or replaced at the factory of origin in accordance with the TAMCO o...

Page 3: ...ons or issues not covered in this document contact TAMCO Customer Service at 1 800 561 3449 EBTRON Airflow Measurement Station Refer to the EBTRON Technical Manual TM_GTx116 under separate cover for airflow measurement station wiring instrument setup and operation For additional assistance with EBTRON Airflow Measurement Station questions or issues not covered in the Technical Manual contact your ...

Page 4: ...r flanges correct by bending them back into position gently taking care not to disturb the EBTRON sensor probes and transmitter Do not install the AIR IQ Unit if damage is more than superficial if uncertain as to extent of damage or if the damper does not seal correctly Call TAMCO customer service at 1 800 561 3449 Operate the damper section manually on a flat section of floor to verify correct bl...

Page 5: ...are If required make a hole in the duct work to allow extension of the drive rod Verify that the AIR IQ unit is square and then secure the bottom damper frame to the floor of the duct using a 90 mounting angle Operate the damper manually to confirm proper sealing As each mounting angle is installed verify operation to ensure the damper is sealing correctly Caulk all joints AIR IQ TYPICAL SINGLE SE...

Page 6: ... 5 A 3 5 4 Jumpers will always be on the face of damper downstream from the louver Airflow Minimum 4 clearance for EBTRON insertion style sensor probes and electronic actuator Does not include access for wiring after installation of assembly See specific EBTRON and TAMCO series technical documentation for more information Inside Sleeve dimensions Parallel to blade A 2 5 Perpendicular to blade B 2 ...

Page 7: ...square Verify that the duct flange or hole is square flat and even Verify that the unit AIR IQ unit is square Operate the damper to verify free movement of the blades and correct sealing Secure the damper to the duct work or opening Re verify that the damper is square If the AIR IQ unit is manufactured as Sleeve Only and ducted on both sides repeat the procedure for the other flange Caulk all join...

Page 8: ...blade B Outside Damper Frame dimensions Parallel to blade A 2 Perpendicular to blade B 2 Outside Flare dimensions Parallel to blade A 6 Perpendicular to blade B 6 NOTES A x B Always opening dimensions Width A Always dimension parallel to blades Height B Always dimension perpendicular to blades AIR IQ shown with sleeve and flare AIR IQ TYPICAL TWO SECTION HORIZONTAL BLADE DAMPER PROBES MOUNTED PARA...