TX7004 Operating Instruction 

Following FAULT Condition  

FAULT 

Alarm Tone and Yellow Display 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 
 
 
 

 

 

 

N0001: 02-17 01:11 Panelself Z0001 L01 D001  

˂

 Photo w/Heat Detector 

˃

 

     

Loss Communication 

     General Manager Office

 

 

List of Devices on Fault Condition - - - Total Devices: 0002 

Pre-Alarm: 0000 

Supervisory: 0000 

Fault: 0002 

Activation: 0000

 

000000

 

0000 

  

 

 

F1 

F2 

F3 

 

BUZZ 

Mute 

Evac 

Silence 

Menu 

Monitoring Status 

Level 1-User 

Stand-alone 

2014-02-17 01:14:37 

 

 

1.  Open the door. LCD screen 

displays: The first, and in multiple 
alarm condition also the last fault, 
time and 

device details

. General 

Fault LED turn on steady and 
corresponding zone indication is 
blinking.  

 

Check the fault, restore or replace the defective 
device. Isolate the fault during analysis if 
necessary. 

Disable the device. 

1. 

On the main menu, press “2 Operation Menu, 
Display show “PASSCODE: __” input the 
code and press “Enter”  

2. 

On operation menu, press “4 Disable/Enable 
Setup, then press “2 Dis/Enable devices by 
Address” and then “1 Disable device by 
address”.  

3.  Input the loop and address number, press 

Enter and then Disable LED turn on steady 

 

 

 

Enable the device. 
 

1. 

On the main menu, press “2 Operation 
Menu, Display show “PASSCODE: __” input 
the code and press 

“Enter” 

2. 

On operation menu, press “4 Disable/Enable 
Setup, then press “2 Dis/Enable devices by 
Address” and then “2 Enable device by 
address”.  

3.  Input the loop and address number, press 

Enter and then Disable LED turn off once it 
is confirmed. 

 

BUZ Mute 

Fire: 0000 

N0002: 02-17 01:13 Panelself Z0001 L01 D002 

˂

 MCP 

˃

 

     Loss Communication 
     Service Door 

 

Reset 

 
 
 
 

 

 

 

N0001: 02-17 01:11 Panelself Z0001 L01 D001  

˂

 Photo w/Heat Detector 

˃

 

     

Loss Communication 

     General Manager Office

 

 

List of Devices on Fault Condition - - - Total Devices: 0002 

Pre-Alarm: 0000 

Supervisory: 0000 

Fault: 0002 

Activation: 0000

 

000000

 

0000 

  

 

 

F1 

F2 

F3 

 

BUZZ 

Mute 

Evac 

Silence 

Menu 

Monitoring Status 

Level 3- Maintenance 

Stand-alone 

2014-02-17 01:14:37 

 

 

2.  Silencing the panel buzzer.  

Press the “BUZ Mute” button. 
Display show “PASSCODE: __” 
input the code and press “Enter”  

 

 

BUZ Mute 

Fire: 0000 

N0002: 02-17 01:13 Panelself Z0001 L01 D002 

˂

 MCP 

˃

 

     Loss Communication 
     Service Door 

 

Reset 