TX7004 Operating Instruction
Following FAULT Condition
FAULT
Alarm Tone and Yellow Display
N0001: 02-17 01:11 Panelself Z0001 L01 D001
˂
Photo w/Heat Detector
˃
Loss Communication
General Manager Office
List of Devices on Fault Condition - - - Total Devices: 0002
Pre-Alarm: 0000
Supervisory: 0000
Fault: 0002
Activation: 0000
000000
0000
F1
F2
F3
BUZZ
Mute
Evac
Silence
Menu
Monitoring Status
Level 1-User
Stand-alone
2014-02-17 01:14:37
1. Open the door. LCD screen
displays: The first, and in multiple
alarm condition also the last fault,
time and
device details
. General
Fault LED turn on steady and
corresponding zone indication is
blinking.
Check the fault, restore or replace the defective
device. Isolate the fault during analysis if
necessary.
Disable the device.
1.
On the main menu, press “2 Operation Menu,
Display show “PASSCODE: __” input the
code and press “Enter”
2.
On operation menu, press “4 Disable/Enable
Setup, then press “2 Dis/Enable devices by
Address” and then “1 Disable device by
address”.
3. Input the loop and address number, press
Enter and then Disable LED turn on steady
Enable the device.
1.
On the main menu, press “2 Operation
Menu, Display show “PASSCODE: __” input
the code and press
“Enter”
2.
On operation menu, press “4 Disable/Enable
Setup, then press “2 Dis/Enable devices by
Address” and then “2 Enable device by
address”.
3. Input the loop and address number, press
Enter and then Disable LED turn off once it
is confirmed.
BUZ Mute
Fire: 0000
N0002: 02-17 01:13 Panelself Z0001 L01 D002
˂
MCP
˃
Loss Communication
Service Door
Reset
N0001: 02-17 01:11 Panelself Z0001 L01 D001
˂
Photo w/Heat Detector
˃
Loss Communication
General Manager Office
List of Devices on Fault Condition - - - Total Devices: 0002
Pre-Alarm: 0000
Supervisory: 0000
Fault: 0002
Activation: 0000
000000
0000
F1
F2
F3
BUZZ
Mute
Evac
Silence
Menu
Monitoring Status
Level 3- Maintenance
Stand-alone
2014-02-17 01:14:37
2. Silencing the panel buzzer.
Press the “BUZ Mute” button.
Display show “PASSCODE: __”
input the code and press “Enter”
BUZ Mute
Fire: 0000
N0002: 02-17 01:13 Panelself Z0001 L01 D002
˂
MCP
˃
Loss Communication
Service Door
Reset