Wireless Functions: Monitor Mode
Monitoring Current Readings
The RTR-500DC can be set to patrol and monitor Remote Units
groups and display in order the current readings for view.
11
In the Main Menu, open [
WL RU Settings] and then Select [Monitor
Mode] .
21
Select the monitoring range and Set the monitoring interval.
31
Press Operation Daial.
①
②
③
④
①
All Groups
Remote Units in all groups registered to the RTR-500DC will be contacted
via wireless communication.
②
Specify Group
All Remote Units in the selected groups will be contacted via wireless
communication.
- If you wish to monitor using the [All Groups] range, it is possible to monitor only 120
Remote Units. Therefore, when making changes to the [Set Number of Possible
Registrations] make sure to register no more than 120 Remote Units to the Group or
use the [Specify Group] range as oulined below.
③
Specify a Remote Unit
All Remote Units in the selected groups will be contacted via wireless
communication.
④
Interval
The monitoring interval is the amount of time between the starting
of wireless communication to gather current Remote Unit readings.
Selections can be made from 10 sec to 60 minutes (in 1 minute units).
- The amount of communication time depends on the number of registered groups
and remote units. Please note that if the monitoring interval is set for less time than
communication takes to complete a round of monitoring, the system will
automatically extend the interval to allow for the necessary amount of communication
time.