ELECTRICAL INSTALLATION

PRODUCT IS SUITABLE FOR END USER INSTALLATION ONLY BY 

APPROPRIATELY QUALIFIED PERSONNEL

Installation Considerations

The SX-LS-P7XXXXA series Electromagnetic lock can be installed and used just like a conventional
electromagnetic lock by fitted onto the frame and acting on the armature plate (keeper unit) which is
usually mounted to the top of the door.

Electrical Installation

The Electromagnetic Lock is factory fitted as standard with a grey, multi-core ‘wire braided’ cable. The
signal cores MUST be appropriately terminated via a suitable certified Ex e gland into a local Ex e junction
box.

7

12V DC Product Versions – V 

Max 13.2V DC 1A

24V DC Product Versions – V 

Max 26.4V DC 0.5A

SX EX ELECTROMAGNETIC LOCK - WIRING 

CONNECTIVITY & FUSING TABLE BY MODEL 

NUMBER for  24V DC PRODUCT

SWITCHING SYSTEM:

SPCO

VOLTAGE

TEMP

24V DC T6

–40 °C … +45 °C 

SX-LS-P71211A

 

24V DC T5

–40 °C … +60 °C 

SX-LS-P72211A

 

CABLE TYPE

7 CORE

LINE FUSE

CORE NUMBER 1

+VE

 

0.5A SLO BLO

CORE NUMBER 2

0 VDC

NA

CORE NUMBER 3

NO

NA

CORE NUMBER 4

NC

NA

CORE NUMBER 5

COMMON

0.5A SLO BLO

CORE NUMBER 6

COMMON

0.5A SLO BLO

EARTH CORE

GND

NA

SPECIAL NOTE 3:

Only competent personnel should carry out the
electrical connection of this product.

Driver circuits to the lock and the magnetic switch
should be appropriately fused / protected in line as
specified by the ‘X’ conditions to prevent exceeding
the design limits set out in the Technical
Specifications section.

‘SLO-BLO’ is the minimum requirement for fusing
as shown in the tables (see left). We recommend
fused terminals are fitted for this purpose, located
close to the ACS.

To prevent the risk of hazardous voltages
accidentally being transmitted into the hazardous
area we recommend that power to this device is
supplied from a suitable power source, e.g.,
isolating transformer / PELV source.

The user cable is mechanically braided for
protection. However, the electrical installer should
take such additional measures to protect the cable
when installed on-site as may be necessary to
comply with local regulations and good installation
practice. This may require routing the user cable
through an appropriate protective conduit.

For additional protection a safety earth point is
provided. This can be found beneath the gland on
the cable entry side of the Electromagnetic Lock.

SX EX ELECTROMAGNETIC LOCK - WIRING 

CONNECTIVITY & FUSING TABLE BY MODEL 

NUMBER for  12V DC PRODUCT

SWITCHING SYSTEM:

SPCO

VOLTAGE

TEMP

12V DC T6

–40 °C … +45 °C 

SX-LS-P71111A

12V DC T5

–40 °C … +60 °C 

SX-LS-P72111A

 

CABLE TYPE

7 CORE

LINE FUSE

CORE NUMBER 1

+VE

 

1A SLO BLO

CORE NUMBER 2

0 VDC

NA

CORE NUMBER 3

NO

NA

CORE NUMBER 4

NC

NA

CORE NUMBER 5

COMMON

0.5A SLO BLO

CORE NUMBER 6

COMMON

0.5A SLO BLO

EARTH CORE

GND

NA

Summary of Contents for SecureEx SX-LS-P7 Series

Page 1: ...SX EX ELECTROMAGNETIC LOCK REVISION 2 INSTALLATION OPERATION MAINTENANCE GUIDE IOMG PART NO SX LS P7XXXXA CERTIFICATE ISSUE No 2...

Page 2: ...y products supplied either as individual components or as matched building blocks of a complete bespoke solution Products typically are CE ATEX IECEx and or UL certified for use in various gas and dus...

Page 3: ...e 6 MOUNTING OPTIONS Page 7 ELECTRICAL INSTALLATION Page 8 OPERATION Page 9 MAINTENANCE Page 10 ELECTROMAGNETIC LOCK GA Page 11 ARMATURE KEEPER GA Page 12 ATEX PRODUCT CERTIFICATE Page 15 DECLARATION...

Page 4: ...unit may be fitted to a wide variety of door configurations including left or right handed and in or outward opening doors by using the appropriate approved matching mounting systems sold separately...

Page 5: ...INSTALLATION ONLY BY APPROPRIATELY QUALIFIED PERSONNEL Installation Considerations The SX LS P7XXXXA series Electromagnetic locks can be installed and used just like a conventional electromagnetic loc...

Page 6: ...rom the door to close directly onto the lock This arrangement requires our optional custom Z bracket Note Due to common mounting points the Z bracket can also be used to mount the lock in an alternate...

Page 7: ...magnetic switch should be appropriately fused protected in line as specified by the X conditions to prevent exceeding the design limits set out in the Technical Specifications section SLO BLO is the m...

Page 8: ...d to lock product The case is specially designed to dissipate heat and acts as a natural heat sink The external temperature of the unit will therefore rise under normal use and may become hot DOOR STA...

Page 9: ...tic surfaces are kept clean and clear of debris which could impair performance Every 3 months check the external sealing of the multicore cable connections and the overall condition of the unit NOTE I...

Page 10: ...ELECTROMAGNETIC LOCK GA 10...

Page 11: ...ARMATURE KEEPER GA 11...

Page 12: ...IECEx PRODUCT CERTIFICATE 12 For IECEx Certificate of conformity please download from https www iecex certs com home Certificate number IECEx EXV 17 0018X ATEX PRODUCT CERTIFICATE...

Page 13: ...13...

Page 14: ...14...

Page 15: ...EU EC DECLARATIONS OF CONFORMITY 15...

Page 16: ...armature plate keeper The equipment is supplied with a flying lead though a factory fitted gland which requires suitable termination at installation this can be supplied in various length cords Optio...

Page 17: ...ems 1 SPCO Contact S0 STDFS 2 SEOL Grade 2 S1 3 TEOL Grade 3 S2 4 Alarm Tamper Loop S3 5 SPECIAL Contact S4 6 Tamper Loop Only S5 System specified on order Configuration only available on special requ...

Page 18: ...NOTES 18...

Page 19: ...NOTES 19...

Page 20: ...ingdom T 44 0 1709 352301 E info securex technology E Documents Electronic copies of this manual together with additional product information and copies of the IECEx ATEX certificates can be found on...

Reviews: