PRSU Series, Operating Instructions Manual (Revision 1.0) 

Monitoring Channel Mode Wiring 

 

For both of the following configurations, please note the maximum and minimum  
electrical parameters for these devices listed in the table on Pages 13 and 14. 

 
 

 

1.  Dual channel (fail-safe): 

For fail-safe (safety) applications, the following configuration must  
be used:

 

 

 

 

 
 

 

 

 
 
 
 
 
This configuration ensures that the full length of all switch/sensor  
conductors are 

monitored. If the switch/sensor’s conductors are  

compromised at any point along their length, the controller will detect the  
fault and cause the output relay to de-energize. 
 

Warning: For this configuration to work as intended, the series  
resistance between each end of the sensor’s conductors cannot exceed  
10

Ω. Additionally, the short circuit resistance between both of the  

switch/sensor’s conductors cannot exceed 200Ω. 
(Up to Category 3, SIL2, PLd Unreachable). 

 
 

2.  Single channel (Non-Safety): 

For non-failsafe applications (non-safety), utilize the following 
configuration where one side of each switch/sensor´s conductors is  
connected to a monitoring terminal: 
 
 
 
 
 
 
 
 
 
 
 
 

 

                           

Single Lead / Single channel 

 

 

Warning: This configuration does NOT provide detection of a 
broken conductor/malfunctioning switch and is therefore 
unsuitable for safety-related applications. For such applications, do  
NOT use this configuration and opt for a “Dual Channel” fail-safe 
configuration instead.   

 

Figure 8: Dual-Channel (With Wire-Break Safety) Configuration 

Figure 9: Single-Channel (Non-Safety) Configuration 

Summary of Contents for PRSU/2

Page 1: ...lants who are familiar with the safety instructions and safety regulations Skilled personnel who build install maintain and operate safety equipment in plants and machinery Symbol Key These operating...

Page 2: ...regulations for safety at work and accident prevention and who have read this manual s content in full Installation assembly and maintenance of electrical equipment is only permitted by specialized s...

Page 3: ...voltage of 24VDC or 24VAC This model features two normally open safety relays that are triggered by the Sensor Monitoring terminals S11 S12 S21 S22 Terminals Description A1 Power input 24VDC or 24VAC...

Page 4: ...relays that are triggered by the Sensor Monitoring terminals S11 S12 S21 S22 This model also features an additional normally closed auxiliary relay not for safety use Terminals Description A1 Power in...

Page 5: ...ty relays that are triggered by the Sensor Monitoring terminals S11 S12 S21 S22 This model also features an additional normally closed auxiliary relay not for safety use Terminals Description A1 Power...

Page 6: ...or more information After the RESET signal is received and the monitored switch is in the unactuated state the relay contacts 13 14 23 24 will close Device Startup Verification PRSU 4 PRSU 5 Before cr...

Page 7: ...application will require only a single PRSU 2 PRSU 4 or PRSU 5 the following rule of thumb guidelines can be used Recommended Application Limits Product Type Maximum Area Maximum Length ControlMat Arm...

Page 8: ...ch on the rear of the unit for DIN Rail attachment Electrical Connections Wire the device based on which of the following options best suits the target application RESET Mode Control Wiring 1 Automati...

Page 9: ...closure is broken and a RESET signal is manually generated by the operator via a mechanical N O pushbutton or switch 3 Conditional In this operating mode the RESET signal cannot propagate unless all o...

Page 10: ...nergize Warning For this configuration to work as intended the series resistance between each end of the sensor s conductors cannot exceed 10 Additionally the short circuit resistance between both of...

Page 11: ...no terminal of the device is connected to a live voltage before continuing 2 Unscrew terminals A1 and A2 from the device before removing any other connections 3 One at a time free connections from the...

Page 12: ...es In cases where either one or both Channel LEDs is OFF during normal operation please verify that the device is properly wired If the problem persists the device is no longer capable of service Reti...

Page 13: ...47 5 1 AC 15 3 A DC 13 3 A Max Switching Capacity 1500 VA resistive load Mechanical Lifetime 107 switching cycles Creeping Distance and Clearance EN 50178 at pollution grade 2 over voltage category 3...

Page 14: ...rical Lifetime 105 switching cycles DC 24V 2A 105 switching cycles DC 24V 2A Creeping Distance and Clearance EN 50178 at pollution grade 2 over voltage category 3 250V Basis isolation over voltage cat...

Reviews: