background image

 

© 

Copyright (2021) 

All

 rights reserved. Changes, which serve technical improvements are reserved.

 

 

12 

PRSU Series, Operating Instructions Manual (Revision 1.0) 

 
 
 

 
Fault Diagnostic and Subsequent Measures 
 

If the controller appears to be operating erroneously, please use the following  
diagnostic guide to determine what action should be taken.

 

 

 

 

Ground fault AC/DC 
(with electronic fuse 
protection)

 

If the input fuse blows and the output contacts open, safely locate the source 
of the fault and correct it, then 

replace the input fuse and follow the “Device 

Startup Verification” procedure on Page 6 of this manual. If normal operation 
of the device does not resume, retire the device and send to Tapeswitch  
Corporation for evaluation.

 

 

Faulty/welded 
Contact  
 

In the case of welded contacts, the device can no longer implement its  
intended function. Retire this device and send back to Tapeswitch  
Corporation for evaluation. 

 

Only one or no 
LED illuminates

 

In cases where either one or both “Channel” LEDs is OFF during normal  
operation, please verify that the device is properly wired. If the problem  
persists, the device is no longer capable of service. Retire the device and 
send to Tapeswitch Corporation for evaluation. 
 
 

 

Excessive contact-
to-contact resistance 

In cases where the device does not appear to operate properly, perform the 
following checks (cables removed from controller ports):  
 

1.  Upper (cables between S22 and S21) conductor plus total cable  

resistance in the unactuated state. Must be less than 10Ω. 
 

2.  Lower (cables between S11 and S12) conductor plus total cable 

resistance in the unactuated state. Must be less than 10Ω. 

 

3.  Upper to lower (cables going from S11 to S21) conductor plus total 

cable resistance. Measure at both sides (includes S21 to S22) during 
actuation

. Must be less than 200Ω. 

 
If the results exceed the stated limits, the system will need one or more  
additional controllers to conform to the maximum resistance parameters per 
relay. 
 
If the results are within the allowable limits and the controller is still not  
working, contact Tapeswitch as the unit is likely faulty. 
 

 

 
 

 

Summary of Contents for PRSU/2

Page 1: ...lants who are familiar with the safety instructions and safety regulations Skilled personnel who build install maintain and operate safety equipment in plants and machinery Symbol Key These operating...

Page 2: ...regulations for safety at work and accident prevention and who have read this manual s content in full Installation assembly and maintenance of electrical equipment is only permitted by specialized s...

Page 3: ...voltage of 24VDC or 24VAC This model features two normally open safety relays that are triggered by the Sensor Monitoring terminals S11 S12 S21 S22 Terminals Description A1 Power input 24VDC or 24VAC...

Page 4: ...relays that are triggered by the Sensor Monitoring terminals S11 S12 S21 S22 This model also features an additional normally closed auxiliary relay not for safety use Terminals Description A1 Power in...

Page 5: ...ty relays that are triggered by the Sensor Monitoring terminals S11 S12 S21 S22 This model also features an additional normally closed auxiliary relay not for safety use Terminals Description A1 Power...

Page 6: ...or more information After the RESET signal is received and the monitored switch is in the unactuated state the relay contacts 13 14 23 24 will close Device Startup Verification PRSU 4 PRSU 5 Before cr...

Page 7: ...application will require only a single PRSU 2 PRSU 4 or PRSU 5 the following rule of thumb guidelines can be used Recommended Application Limits Product Type Maximum Area Maximum Length ControlMat Arm...

Page 8: ...ch on the rear of the unit for DIN Rail attachment Electrical Connections Wire the device based on which of the following options best suits the target application RESET Mode Control Wiring 1 Automati...

Page 9: ...closure is broken and a RESET signal is manually generated by the operator via a mechanical N O pushbutton or switch 3 Conditional In this operating mode the RESET signal cannot propagate unless all o...

Page 10: ...nergize Warning For this configuration to work as intended the series resistance between each end of the sensor s conductors cannot exceed 10 Additionally the short circuit resistance between both of...

Page 11: ...no terminal of the device is connected to a live voltage before continuing 2 Unscrew terminals A1 and A2 from the device before removing any other connections 3 One at a time free connections from the...

Page 12: ...es In cases where either one or both Channel LEDs is OFF during normal operation please verify that the device is properly wired If the problem persists the device is no longer capable of service Reti...

Page 13: ...47 5 1 AC 15 3 A DC 13 3 A Max Switching Capacity 1500 VA resistive load Mechanical Lifetime 107 switching cycles Creeping Distance and Clearance EN 50178 at pollution grade 2 over voltage category 3...

Page 14: ...rical Lifetime 105 switching cycles DC 24V 2A 105 switching cycles DC 24V 2A Creeping Distance and Clearance EN 50178 at pollution grade 2 over voltage category 3 250V Basis isolation over voltage cat...

Reviews: