14
TARGET FEED MASTER
TARGET FEED MASTER rev.09
Feed Weigher and
Mixer VX.X
4. House 1
4. House 1
4. History
4.4 House1 M Hist
1. Mortality
2. Cons./100(or/bird)
3. Tot. Cons.
4. House 1
5. Blend Curves
4.5 Blend curve
Use curve ? Yes
1.Da 1 Blend 1
2.Da 15 Blend 2
4. House 1
6. On/Off
4.6 House 1 status
Status: Off
Output Auger:
Auto
Auger Bin 1: Auto
Scale 1 Valve: Auto
Feed Weigher and
Mixer VX.X
5. House 2
Feed Weigher for
Breeders VX.X
6. Time Clocks
6. Time Clocks
1. Time Clock #1
2. Time Clock #2
On 1 6:00 Off 6:30
On 2 8:00 Off 9:00
On 3 9:30 Off 10:00
On 4 1:00 Off 2:00
Feed Weigher for
Breeders VX.X
7. Alarm Log
Feed Weigher for
Breeders VX.X
8. Ack. Alarm
Feed Weigher for
Breeders VX.X
9. Installation
9. Installation
1. Settings
9.1 Inst. settings
# of bins: 6
# of houses: 2
# of blends: 8
Timed feeding: Yes
# time clocks: 8
Units: kg
Feed qty: /100
Time of reset: 0:00
Shut off augers at
run time alarm ? Yes
Use max feed? Yes
Max feed alarm ? Yes
51
TARGET FEED MASTER
TARGET FEED MASTER rev.09
PROBLEM
CAUSE
SOLUTION
- There is no voltage
between terminals
PWR and GND of the
LCT or between
terminals 1 and 4 of
the main controller.
- The voltage between
terminals PWR and
GND of the LCT or
between terminals 1
and 4 of the main
controller is too low (5-
11VDC).
The LCT light
does not
flash.
- The voltage selector switch is
in the wrong position. Set the
switch to the correct position.
- Fuse F2 of the main controller
is blown. Turn the power off
and replace the fuse. If the fuse
blows regularly, check the
wiring or replace the LCT.
- The ID number of
LCT is not set to #1
- Set the ID module to #1
using the jumpers.
- The end of line
jumpers are not
positioned correctly
- Set the end of line jumpers to
YES at both ends of the
communication line. The other
end of line jumpers must be set
to NO.
- The wiring between
the LCT and the main
controller is incorrect.
- Fix the wiring
- The LCT is defec-
tive.
- Replace the LCT module.