2. Principle of Operation

The main function of the control unit is to keep temperature in the water jacket at the preset

value. The task is realized by measuring temperature (T3) and controlling the cold air choke valve
(PP) properly. Fireplace operation temperature is defined by the
parameter (see PARAMETERS LEVEL 1).
If the fireplace temperature (T3) is higher than the

parameter the

choke valve is gradually shut off limiting air supply, and if the temperature (T3) is lower than the

parameter the choke valve is gradually opened up.

The second function is control the loading pump of the BUF container (P2). The pump P2 runs if the
fireplace temperature exceeds “

” and is above the buffer temperature (T1) by the

parameter (see see PARAMETERS LEVEL 1).

The third function is controlling the loading pump of the BUF container from the solar collector KSL
(P1). The pump of the collector P1 runs if the temperature of the collector (T2) exceeds the
temperature of the buffer (T1) by the parameter value

"<64>DeltaKSL".

The next function is to control the circulating pump (P3) of central heating system. The pump

works if the buffer temperature exceeds the

value.

<20>

FIREPLACE Temp.

<20>

FIREPLACE Temp.

<20>

FIREPLACE Temp.

BUFF ON

<61>

DeltaBUF

CH ON

Fig. 1 Basic operation configuration of the control unit

WAW-

Warm Applicable Water container (boiler)

FIREPLACE-

Water jacket fireplace

BUF-

Buffer container

KSL-

Solar collector (or another heat source)

CH-

Central heating system

T1-

Temperature sensor of the BUF buffer container

T2-

Temperature sensor of the KSL solar collector

T3-

Temperature sensor of the FIREPLACE fireplace water jacket

P1-

Pump loading the BUF from KSL

P2-

Pump loading the BUF from FIREPLACE

P3-

Circulating pump CH

PP-

Electronically controlled air damper of the fireplace

Admission

date

Realization

date

Signature

Remarks

CH

FIREPLACE

Summary of Contents for RT-08G-BUF-SOLAR

Page 1: ...ion Housing protection class IP41 Fuse 6 3A 250V Number of outputs to control pumps 3 250W 230V 50Hz Number of nonvoltage outputs 1 Number of outputs to control the air damper drive 1 5V 500mA DC Numb...

Page 2: ...tainer from the solar collector KSL P1 The pump of the collector P1 runs if the temperature of the collector T2 exceeds the temperatureofthebuffer T1 bytheparametervalue 64 DeltaKSL The next function...

Page 3: ...p P1 2 4 2 5Summermode CH The collector pump P1 runs if the collector temperature T2 exceeds the buffer temperature T1 by thevalue Exceeding the maximum collector temperature parameter causes the KSLp...

Page 4: ...ver to the screen of the fireplace 12 CONTROL Relay 3 3 2 7 6 4 5 7 6 Fig 2 Control panel view Connection cable of the control may be replaced only by producer or his authorized service locations WARR...

Page 5: ...ce toohigh temp ofthebuffer toohigh temp ofthecollector Alarm screen ALARM the limittemperatureof thefireplace definedbythe parameter the limit temperature of the buffer defined by the parameter the l...

Page 6: ...ION OF THE PREVIOUS PASSWORD IF PRESENT WITHOUT IT BEING EXPOSED PASSWORD OF PRODUCER S SERVICE IS UNIQUE AND IS NOT DEPENDENT ON THE USER S PASSWORD IT SHOUDN T BE EXPOSED TO THE USER INSTEAD OF THAT...

Page 7: ...at which the alarm generates 75 95 o C 85 o C Fireplace temperature T3 at which the alarm turns on 5 25 o C 10 o C Decreasing fireplace temperature in relation to preset temperature at whose exceedin...

Page 8: ...3 4 5 8 00 End of the 1st time zone 72 0 00 23 4 5 14 00 73 0 00 23 4 5 17 30 74 0 00 23 4 5 20 00 75 0 00 23 4 5 22 30 76 ECO4 from 0 00 23 4 5 23 00 Start of the 4th time zone economic 77 ECO4 to 0...

Reviews: