2.1 Air damper operation
The air damper regulates an air supply to the combustion chamber, which allows the temperature of
the fireplace water jacket to be kept at the preset value. The task is realized by comparing the
temperature of the water jacket(T3) and preset temperature (the <20>
parameter) and then by gradual opening/shutting the air damper. The change of the air damper
position is done every 20secs
The shutdown of the control unit automatically causes the air damper to be set at the rest position
defined by the <50>
parameter (Default setting is 0% - full shut-off).
C (
) and higher than temperature in the container by 1 C (parameter
).
Turning off the pump below the parameter
causes a faster heating of the
water jacket above the dew point and as a result the longer life time of the fireplace.
After the loading the BUF pump still runs for 1min (parameter "
")
The control unit protects the system from freezing, automatically turning on the circulating pump if
the measured temperature is below 4 C.
The control unit realizes the after season rundown of the pump by switching it on for 1 min if it
doesn
’
t operate for a week.
5 C (parameter
).
The control unit realizes the after season rundown of the pump by switching it on for 1 min if it
doesn
’
t operate for a week.
If the buffer temperature exceeds the preset value of 45 C (the <31>
parameter) the CH pump turns on.
The control unit protects the system from freezing, automatically turning on the circulating pump if
the measured temperature is below 4 C.
The control unit realizes the after season rundown of the pump by switching it on for 1 min if it
doesn
’
t operate for a week.
Turning off the heating system in summer time (the CH pump doesn
’
t
operate). Fireplace only works in the function of loading the BUF buffer.
tandard operation
SUMMER-
”FIREPLACE Temp.”
ChokeV State OFF
parameter <60>
PumpBUFtemp.ON
“<61>DeltaBUF”
<60> PumpBUFtemp.ON
<63>RundownTimeBUF
"<64>DeltaKSL"
Switch-on Temp. of PUMPS
2.2
Operation of the loading pump of the buffer (P2)
CH pump operation (P3)
o
o
o
0
o
o
2.3 Operation of the KSL pump (P1)
2.4
2.5 Summer mode CH
The collector pump P1 runs if the collector temperature (T2) exceeds the buffer temperature (T1) by
the value
! Exceeding the maximum collector temperature (parameter "
") causes the
KSL pump (P1) to be switched on in order to protect the solar collector against overheating. The KSL
protection has a higher priority than limiting the BUF temperature.
- s
<26> ALARM Temp KSL
ON
The control unit controls the pump loading the buffer. The BUF pump (P2) can be switched on if
water temperature in the fireplace is above the preset threshold 48
You can select "ModeCH"=SUMMER setting, in which the CH pump doesn't run.
CE CONFORMITY DECLARATION
Ref. No. 58.RT.01.2007/1/B
We,
ZAK
Ł
AD ELEKTRONICZNY TATAREK Jerzy Tatarek
75 Swieradowska St. , 50-559 Wroclaw
declare under our sole responsibility that
the following product:
the control unit of the heating system with the fireplace controlled by the air damper
model:
PN-EN 55022: 2000 -
(EMC)- IT devices
Characteristics of radioelectric noises. Acceptable levels and measurement methods
:
Laboratory IASE 51-618 Wroclaw, 1 Wystawowa st.
Test report No.
39/DL/I/07 of 22.06.2007
41/DL/I/07 of 03.07.2007
Place of issue:
Manufacturer representative:
Wroclaw
Miros
ł
aw Zas
ę
pa
Date of issue:
Position:
08.2007
Konstruktor
RT-08G-BUF-SOLAR
is in conformity with the basic requirements included in Directive EMC 2004/108/WE of 15.12.2004 (the
electromagnetic compatibility law of 13.04.07) and Directive LVD 2006/95/WE of 21.08.07 (Laws Journal
of 2007 No. 155 pos. 1098) regarding the requirements for electric devices.
To the conformity evaluation the following harmonized standards were used:
PN-EN 60730-2-1: 2002 -
Automatic electric control units for house usage and the like. Part 2-1:
Specific requirements regarding electric control units for electric house
devices
PN-EN 60730-1: 2002 -
Automatic electric control units for house usage and the like.
Part 1: General requirements.
Electromagnetic compatibility
Complementary information
Electronic Engineering Plant TATAREK
has initiated management system and complies with the following standard :
ISO9001: 2000 CERTIFICATE No. 133/2004 of 01.2004
Polish Foreign Trade Chamber
The last two digits of the year in which the CE marking was affixed: 07