Alarm situation is accompanied by a broken sound alarm that can be turned off by pressing the
CONFIRM button (6)

shows the current temperature of the fireplace and the level of

air damper opening.

In the emergency of exceeding the temperature the corresponding pumps start to run to

cool off

the system. The KSL protection ha a higher priority than limiting the BUF

temperature.

!

Screen of the fireplace operation

It

s a stable state, that is, in order to change it you need to press the CHOOSE button (7)

During appearing this screen you can change the preset temperature of the fireplace (the

parameter). After pressing the CONFIRM button (6) the preset temperature

blinks whose value can be altered with the buttons

+

(4) or

-

(5) To confirm the changes you

need to press the CONFIRM button (6) once more.

If the manual mode is set (

) (the green LED diode (7) blinks.) you can

manually control the air damper-. The

+

button (4) causes the opening of the air damper (one step

10%) and the

+

button (5) causes its closing.

<20>

FIREPLACE Temp.

FIREPLACE MODE=MAN

There are the following operation modes of the fireplace:

MAN-

OFF-

AUTO-

ON-

Full automatic burning cycle in the fireplace (firing up - operation - burning

out).

Automatic control locked - only manual control of the air damper is

available. Green status diode

blinks.

Setting the air damper to the rest position ( the

parameter).Green status diode

doesn

t light.

The air damper is automatically controlled to stabilize temperature of

the water jacket. Green status diode

does light.

(1)

<50> ChokeV State OFF

(1)

(1)

Automatic operation is controlled by pressing the button

Green status

diode

lights during the fireplace operation and goes out when the burnt-out state is detected.

At the end of the burning-out phase the air damper sets to the rest position (

,

which prevents a room from cooling off and protects the water attachment against freezing.

(3)

ON/OFF

.

(1)

0%, full shut-off)

Temperature of

the water jacket

of the fireplace (T3)

Current

time

Time

zone

Operation mode

of

the fireplace

Preset

temperature

Air damper

opening

FIREPLACE

Password

The changes of important parameters are possible only at unlocked password. To unlock the password you
need to input proper sequence of digits with the buttons

+/-

. With the CHOOSE button (7) to change the

digits position and CONFIRM button (6) to acknowledge all and finish the procedure of changing the
password. The unlocked password is set to

0000

. Once again entering into the password change procedure

causes a new password to be set.

!

!

PASSWORD

9999

HAS CONSIDERABLE MEANING. IT CAUSES THE REACTIVATION OF THE PREVIOUS

PASSWORD IF PRESENT WITHOUT IT BEING EXPOSED.

PASSWORD OF PRODUCER'S SERVICE IS UNIQUE AND IS NOT DEPENDENT ON THE USER'S PASSWORD-

IT SHOUDN'T BE EXPOSED TO THE USER. INSTEAD OF THAT THE SERVICE CAN SET THE USER HIS OWN
PASSWORD.

Examples of passwords:

1.The control unit is installed with the unlocked password. The user can enter his own password e.g.

1234

.

From this moment the important parameters cannot be altered without the password being unlocked (that is,
resetting the password

1234

). After changing essential parameters the user can leave the control unit

unlocked, set any new password or enter

9999

, which activates the password

1234

2. Producer gives the control unit with the set password. The user cannot alter the important parameters. The
servic can change the settings with its own secret password. At the end a serviceman enter the secret password or

9999

, the user still hasn't access to the important parameters.

3. Producer gives the control unit with the set password. The user cannot alter the important parameters. The
servic can change the settings with its own secret password. At the end a serviceman leaves the control unit
unlocked, the user now has access to the important parameters. He can enter his own password like in example
No. 1.
4. Producer gives the control unit with the set password. The user cannot alter the important parameters. The
servic can change the settings with its own secret password. At the end a serviceman sets the password e.g.

1234

and tells it to the user, the user has access to the important parameters but without knowing the password

the other persons cannot make the changes.
5. The user has the unlocked control unit or his own password. Serviceman decides, the user though oughtn't
have access to the important parameters. The serviceman locks the control unit with his secret password, which
removes the user's password and locks the control unit.

6. Serviceman doesn't have to know the user's password. Always he can use his own secret password and at

the end lock with the

9999

, which reactivates the user's password.

Demonstration change of the <50> ChokeV State OFF

<50> ChokeV State OFF

parameter defining the choke valve position after powering off

the control unit (Parameters level 3):
Press:

* Repeatedly the button

CHOOSE

till the

parameter setting

screen appears.

* Button

CONFIRM

->

0

blinks

* 3 times the button

+

->

3

blinks

* Button

CONFIRM

->

3

stops blinking (the

has been chosen)

* Button

CHOOSE

-> current value of the

parameter shows up

* Button

CONFIRM

-> current value, you want to change, starts blinking

* Buttons

+

and

-

-> you set the new value

* Button

CONFIRM

-> we confirm the new value

* Repeatedly the button

CHOOSE

till the

***

parameter end setting screen appears.

PARAMETERS LEVEL

Parameters Level 3

Summary of Contents for RT-08G-BUF-SOLAR

Page 1: ...ion Housing protection class IP41 Fuse 6 3A 250V Number of outputs to control pumps 3 250W 230V 50Hz Number of nonvoltage outputs 1 Number of outputs to control the air damper drive 1 5V 500mA DC Numb...

Page 2: ...tainer from the solar collector KSL P1 The pump of the collector P1 runs if the temperature of the collector T2 exceeds the temperatureofthebuffer T1 bytheparametervalue 64 DeltaKSL The next function...

Page 3: ...p P1 2 4 2 5Summermode CH The collector pump P1 runs if the collector temperature T2 exceeds the buffer temperature T1 by thevalue Exceeding the maximum collector temperature parameter causes the KSLp...

Page 4: ...ver to the screen of the fireplace 12 CONTROL Relay 3 3 2 7 6 4 5 7 6 Fig 2 Control panel view Connection cable of the control may be replaced only by producer or his authorized service locations WARR...

Page 5: ...ce toohigh temp ofthebuffer toohigh temp ofthecollector Alarm screen ALARM the limittemperatureof thefireplace definedbythe parameter the limit temperature of the buffer defined by the parameter the l...

Page 6: ...ION OF THE PREVIOUS PASSWORD IF PRESENT WITHOUT IT BEING EXPOSED PASSWORD OF PRODUCER S SERVICE IS UNIQUE AND IS NOT DEPENDENT ON THE USER S PASSWORD IT SHOUDN T BE EXPOSED TO THE USER INSTEAD OF THAT...

Page 7: ...at which the alarm generates 75 95 o C 85 o C Fireplace temperature T3 at which the alarm turns on 5 25 o C 10 o C Decreasing fireplace temperature in relation to preset temperature at whose exceedin...

Page 8: ...3 4 5 8 00 End of the 1st time zone 72 0 00 23 4 5 14 00 73 0 00 23 4 5 17 30 74 0 00 23 4 5 20 00 75 0 00 23 4 5 22 30 76 ECO4 from 0 00 23 4 5 23 00 Start of the 4th time zone economic 77 ECO4 to 0...