background image

1

24

Zakład elektroniczny TATAREK Jerzy Tatarek

50-559 Wroclaw, 75 Swieradowska st.

ph. (071) 367-21-67, 373-14-88, fax 373-14-58; Tax index number 899-020-21-48;

Bank account: BZ WBK S.A. WROCLAW 6910901522-0000-0000-5201-9335

www.tatarek.com.pl.; E-mail: tatarek@tatarek.com.pl

Zakład elektroniczny TATAREK Jerzy Tatarek

USER MANUAL

program version 2.1 (06.02.2014

)

from program v2.1

RT-14

CONTROLLER OF HEATING SYSTEM

WITH SOLID FUEL BOILER

RT14/2014/v.2.1/ANG

1.Basic parameters

Power

Number of outputs to control pumps
Number of outputs to control the valve motor
Number of temperature sensors of water

Switch-on temperature of the STB safety thermostat

94 C

230V/50Hz

Power consumption without load

4W

Max connection power

750W

Operation conditions

0-50 C, humidity10-90%
no condensation

Housing protection class

IP41

Fuse

6,3A/250V

P

of blower output

1,5A/230V/50Hz
3 * 200W/230V/50Hz
2 * 200W/230V/50Hz
3 * KTY81 (0...+100 C )

Temperature sensor of the flue gas

PT1000 (-30...+450 C)

Temp. measurement precision

+/- 1 C

Temp. measurement resolution

0,1 C

o

o

o

o

o

ower-carrying capacity

o

The controller controls the heating system based on the solid fuel boiler in which by controlling the
efficiency of the blower the burning process is under control. The receivers of the heat are as follows:
Container of the Warm Applicable Water (WAW) and Heating System (CH). The controller
cooperates with the 3-way mixing valve in the heater or floor system and safety system of the return
temperature of the boiler.

Summary of Contents for RT-14

Page 1: ...thermostat 94 C 230V 50Hz Power consumption without load 4W Max connection power 750W Operation conditions 0 50 C humidity10 90 no condensation Housing protection class IP41 Fuse 6 3A 250V P of blower...

Page 2: ...ILER 45min the temperature doesn t increase then the blower turns off an The given temperatures relate to the situation when the sensor of the flue gas is inactive After connecting the flue gas sensor...

Page 3: ...r our sole responsibility that the product Controller of the Heating System model RT 14 PN EN 55022 2011 EMC IT devices Characteristics of radioelectric noises Acceptable levels and measurement method...

Page 4: ...TimeStopPumpCH o o The controller protects the system from freezing automatically switches on the circulating pump if themeasuredtemperatureisbelow The controller realizes an after season rundown of t...

Page 5: ...the WAW pump afterloadingthecontainercausesthenormaloperationoftheCH pumptocomeback the pumps run as in PRIO mode Additionally during loading the container the presettemperatureoftheboileris raisedto6...

Page 6: ...ents onthecontrolpanel fig 8 The operation state is presented on the graphic display 2 The screens inform about the operation of devices temperature of sensors they make it possible to change the para...

Page 7: ...21 TempALARM_BOILER 61 TempALARM FLOOR o 9 2 Screen of boiler operation Thescreenfeaturescurrenttemperatureof theboilerandrotationof theblower Fig 82 Screen of boiler operation 18 WARNING WE INFORM T...

Page 8: ...ler in case of the room thermostat operation TempBOILER TempTHERMOSTAT 17 PASSWORD 9999 HAS CONSIDERABLE MEANING IT CAUSES THE REACTIVATION OF THE PREVIOUS PASSWORD IF PRESENT WITHOUT IT BEING DISCLOS...

Page 9: ...he cyclical run After that time the CH pump runs for 45secs Temperature hysteresis of turning on off the pumps The temperature difference between turning on and turning off the pumps It prevents often...

Page 10: ...60min 45min The time of keeping up the low boiler temperature after which the transition to the stop state follows 3X blower DEFAULT boiler 30 ADJUSTABLE 31 10 100 100 32 1 10 o C 2 o C 38 2 10 o C 5...

Page 11: ...ways when the controller is on Switching off the backlighting means it gets the value defined by the next parameter 15 Minimum LCD backlighting it s valid at the negative LCD The value 0 means a full...

Page 12: ...t Parameter value change Upper and lower change limit THE PARAMETERS ADJUST THE CONTROLLER TO THE FEATURES OF THE BOILER AND THE CH SYSTEM THEIR CHANGE SHOULD BE CONSULTED WITH THE PRODUCER OF THE BOI...

Reviews: