Fuel
Dispensers
TATSUNO
EUROPE
‐
Installation
and
User
Manual
,
revision
10,
January
2022
107
a.s.
about
the
necessity
to
install
service
lines.
For
service
lines
we
recommend
using
multi
‐
wire
shielded
H05VVC4V5
‐
K
cables
(0.5
mm
2
).
3.5.6.
SECURITY
LINE
(STOP
BUTTON)
The
security
line
serves
to
output
the
signal
from
the
STOP
button
located
in
the
dispenser
to
the
station
switchboard
security
circuits.
The
security
line
must
be
especially
installed
in
LPG
and
CNG
dispensers/modules
that
operate
in
an
unattended
mode.
Pressing
the
STOP
button
on
the
dispenser
activates
the
security
circuits
that
disconnect
the
dispenser
from
the
power
supply
and
at
the
same
time
the
safety
valves
on
the
supply
line
close.
In
order
to
install
the
security
line
it
is
necessary
to
route
the
3
‐
wire
power
cable
H05VV5
‐
F
3x1.5
(see
Table
22)
to
each
dispenser
at
the
fuel
station.
The
security
line
cable
is
always
brought
from
the
main
switchboard
in
the
booth
to
the
first
module
of
the
dispenser
into
the
distribution
box.
From
the
distribution
box,
the
cable
is
routed
to
the
dispenser
electronic
head
where
it
is
connected
to
the
STOP
button.
Table
22
–
Identification
of
wires
in
the
security
line
Identification
of
wires
in
the
H05VV5
‐
F
3x1.5
cable
identification
colour
description
ST
black2
STOP
signal
ST
black1
STOP
signal
PE
yellow
‐
green
protection
wire
3.5.7.
REGULATION
OF
VALVES
IN
PRESSURE
SECTIONS
OUTSIDE
DISPENSER
(CNG
MODULE)
If
the
valves
from
high
‐
pressure
sections
are
located
at
the
CNG
fuel
station
outside
the
dispenser
in
the
area
of
pressure
reservoirs
and
compressor
then
their
switching
is
performed
by
a
5
‐
wire
H05VV5
‐
F
5G1.5
cable
(see
Table
14).
The
cable
from
valves
regulation
is
routed
from
the
main
switchboard
in
the
booth
to
the
supply
distribution
box
of
the
dispenser.
The
H05VV5
‐
F
5G1.5
cable
is
routed
from
the
distribution
box
to
the
counter
case
to
the
outputs
that
ensure
the
valves
regulation.
Table
23
–
Identification
of
wires
in
the
cable
for
regulating
the
valves
in
CNG
pressure
sections
Identification
of
wires
in
the
H05VV5
‐
F
5x1.5
cable
identification
colour
description
V1
black
1
valve
1
regulation
V2
black
2
valve
2
regulation
V3
black
3
valve
3
regulation
VC
black
4
common
wire
for
valves
PE
yellow
‐
green
protection
wire
CAUTION
In
order
to
regulate
external
valves
the
dispenser
outlets
are
used
that
use
the
voltage
of
24V
DC
with
maximum
current
‐
carrying
capacity
of
0.8
A
for
switching
.
Always
consult
the
dispenser
manufacturer
for
the
use
of
another
control
voltage
and
current.