Turbomachinery Package Specification
Taurus
60 Compressor Set and Mechanical Drive
•
Purchaser piping and instrumentation diagram including suction and recycle
pipe size and schedule
•
Anti-surge control (recycle) valve and specification sheet, unless included in
Solar's scope
•
Suction and discharge gas temperature signal (100-ohm platinum resistance
temperature devices (RTDs) preferred)
Typical system scope includes the following:
•
Engineering to determine the optimum control algorithms
•
Control software programmed and tested for the selected gas compressor
staging
•
Engineering to specify the anti-surge control valve and accessories, including
valve performance evaluation over the gas compressor performance map at
varying valve positions
•
Engineering to specify the flow meter type and size
•
Automatic override of manual control mode
•
Evaluation of user piping and instrumentation diagram
•
Documentation, including all surge control calculations and program constants
•
Gas compressor flow versus differential pressure control with suction pressure
and temperature compensation
•
Speed setpoint decoupling
•
Surge detection with step valve opening
•
On-screen, real-time graphic displays
•
On-screen, real-time control parameter setting
•
All surge control parameters are available for remote monitoring via serial link
11.1.5 Anti-Surge
Recycle
Valve
When included in Solar’s scope of supply, the anti-surge recycle valve is supplied as a
complete and functionally tested assembly, shipped separately for field installation. The
assembly includes the valve and the following accessories and features:
•
Spring-return, diaphragm-type, pneumatic actuator
•
Position transmitter with valve fully open and fully close relay outputs and 4-to-
20 mA proportional to percentage closed
•
Pressure regulator
•
3-way 24-VDC solenoid valve
•
Electropneumatic valve positioner
•
½-in. NPT actuator pressure port
•
Carbon steel body per ASTM A352
•
Interconnecting 316L stainless steel tubing and compression-type fittings
•
Temperature Limits:
−
Process gas:
-
6.7
o
to 218°C (20 to 425°F)
−
Ambient:
-
28.9
o
to 60°C (
-
20 to 140°F)
The assembly requires clean, dry regulated air or natural gas, 552 to 862 kPag (80 to 125
psig), -28.9
o
to 60°C (-20
o
to 140°F), dew point -40°C (-40°F)
Successful operation of the anti-surge control system is dependent on correct valve
selection. The following anti-surge recycle valve is selected based on the application data