31
OC protection consists of six (6) individual overcurrent elements providing three stages of protection for both
the Forward () and Reverse (Source-) power flow directions: OC1+, OC1-, OC2+, OC2-, OC3+, OC3-
.
OC1
Phase overcurrent low set element OC1 is designated to provide time delayed trips. It is enabled in any
selected sequence in t
he Overcurrent Reclosing element. „I“ (Instantaneous) stands for accelerated and „D“
(Delayed) for delayed step of overcurrent protection in an autoreclosing sequence.
OC2
Phase overcurrent low set element OC2 is designated to provide accelerated trips. If a sequence step in the
Overcurrent Reclosing Element is set „D“ OC2 element is disabled. If a sequence step in the Overcurrent
Reclosing element is set „I“ OC2 element is enabled.
OC3
Phase fault high set instantaneous element provides protection against phase high current faults with a
reduced number of trips to lockout. If there is no intention to reduce the number of trips to lockout at high
current faults, enabling this element is not recommended. OC1 and OC2 allow reduction of tripping time to any
desired value at high currents.
For details on available TCC refer to Table 20 of this guide.
OC3 element settings are described in Table 21.
Earth Fault (EF)
This element is available
for OCR mode “Recloser” only.
This element provides protection against single phase and double phase earth faults.
EF protection consist of six (6) individual overcurrent protection elements providing three stages of protection
for both the Direct () and Reverse power flow (Source-) directions: EF1+, EF1-, EF2+, EF2-, EF3+,
EF3-.
EF1
Earth fault low set element EF1 is designated to provide time delayed trips. It is enabled in any selected
sequence in the Overcurrent Reclosing element. „I“ (Instantaneous) stands for accelerated and „D“ (Delayed)
for delayed step of overcurrent protection in an autoreclosing sequence.
EF2
Earth fault low set element EF2 is designated to provide accelerated trips. If a sequence step in the Overcurrent
Reclosing Element
is set „D“ EF2 element is disabled. If the sequence step in the Overcurrent Reclosing
element is set „I“ EF2 element is enabled.
EF3
Earth fault high set instantaneous element provides protection against high earth current faults with a reduced
number of trips to lockout. If there is no intention to reduce the number of trips to lockout at high current faults,
enabling this element is not recommended. EF1 and EF2 allow reduction of tripping time to any desired value
at high currents.
For details on available TCC refer to Table 17 of this guide.
EF3 element settings are described in Table 18.
Table 17
– TCC types
Settings
Designation
Range
Default
Type of time current
characteristic
TCC
ANSI: Extremely Inverse (EI), Moderately Inverse (MI), Very Inverse (VI)
IEC: Extremely Inverse (EI), Very Inverse (VI), Inverse (I)
Definite Time (TD)
Custom: custom curves are available on request. Contact Tavrida
Electric representative.
TD
Summary of Contents for Rec15
Page 1: ......
Page 5: ...1 Introduction...
Page 9: ...2 Technical Parameters...
Page 14: ...3 Product Description...
Page 26: ...26 Figure 25 Anti vandal housing...
Page 27: ...4 Functionality...
Page 56: ...5 Product Handling...
Page 69: ...6 Installation...
Page 81: ...7 Commissioning...
Page 84: ...8 Operation...
Page 99: ...99 Figure 76 Settings uploading wizard...
Page 100: ...9 Maintenance and Troubleshooting...
Page 114: ...114 Figure 90 Securing the trip hook shaft against rotation...
Page 115: ...10 Product Coding...
Page 122: ...11 Appendices...
Page 128: ...128 Appendix 4 Recloser Control Drawings Figure 99 Dimensions of RC5_4...
Page 133: ...133 Figure 106 Dimensions of standard OSM mounting kit arrangement for lateral installation...
Page 134: ...134 Figure 107 Dimensions of interface bracket...
Page 135: ...135 Figure 108 Dimensions of OSM mounting kit with M16 pole interface front installation...
Page 136: ...136 Figure 109 Dimensions of OSM mounting kit with M16 pole interface lateral installation...
Page 137: ...137 Figure 110 Dimensions of OSM mounting kit with M20 pole interface front installation...
Page 138: ...138 Figure 111 Dimensions of OSM mounting kit with M20 pole interface lateral installation...
Page 149: ...149 Figure 122 Dimensions of OSM substation mounting kit...
Page 152: ...152 Figure 125 Dimensions of RC mounting kit for through the pole installation...
Page 153: ...153 Figure 126 Dimensions of RC substation mounting kit...
Page 154: ...154 Figure 127 Dimensions of VT mounting kit One VT holder...
Page 163: ...163 Appendix 8 Connectors Drawings Figure 141 Dimensions of aerial connector...
Page 164: ...164 Figure 142 Dimensions of bird guards for aerial connector...
Page 165: ...165 Figure 143 Dimensions of two hole NEMA connector...
Page 166: ...166 Figure 144 Dimensions of bird guards for two hole NEMA connector...
Page 167: ...167 Figure 145 Dimensions of four hole NEMA connector...
Page 168: ...168 Figure 146 Dimensions of bird guards for four hole NEMA connector...
Page 169: ...169 Figure 147 Dimensions of Burndy NEMA connector...
Page 170: ...170 Appendix 9 Recloser Control Wiring Diagram Figure 148 RC5_4 wiring diagram...
Page 172: ......