70
Installation operations are carried out by utility technical personnel and can be supervised by Tavrida Electric
technical representatives. This chapter describes installation procedures and required equipment. For more
detailed information about the installation process contact a Tavrida electric technical representative.
6.1 Required Equipment
1. Set of wrenches (8-24mm);
2. Set of screw drivers (+ and - );
3. Screw driver “-” 2.5x0.4 for WAGO terminals;
4. Diagonal pliers;
5. Power line connection provision:
▪
Wires (preferable insulated) (6 pcs.);
▪
Support insulators 3 pcs. (if required);
▪
Cable lugs applicable for chosen connection wires and M12 bolt (6 pcs.);
▪
Connection clamps (waterproof if insulated connection wires are used) (6 pcs.).
6. Hydraulic cable terminal lug manual clamp up to 240mm2;
7. Alcohol for insulation cleaning;
8. Crane or other lift for the Outdoor Switching Module and RC5_4 lifting.
6.2 Installation Procedure
WARNING!
The installation procedure in this manual is offered as a guide only. It should be used in conjunction
with the utility’s own safety procedures. Before installation begins, all necessary precautions should be carried
out.
Outdoor Switching Module Installation
Before starting the Outdoor Switching Module installation, make sure that:
•
The Outdoor Switching Module main contacts are open,
•
The control cable is disconnected,
•
The Outdoor Switching Module control cable socket cover is closed.
The mounting kit and surge arresters (depending on particular installation) should be installed according to
procedure described in the Handling and Installation guide.
The Outdoor Switching Module installed on the mounting frame should be lifted as shown in Figure 37.
ATTENTION!
The HV assembly lifting facilities should not come into contact with bushings, surge arresters or
auxiliary VT bushing extensions.
ATTENTION!
When installing the HV assembly, make sure that the connection to the line is performed
according to the procedure described in the Handling and Installation guide.
Summary of Contents for Rec15
Page 1: ......
Page 5: ...1 Introduction...
Page 9: ...2 Technical Parameters...
Page 14: ...3 Product Description...
Page 26: ...26 Figure 25 Anti vandal housing...
Page 27: ...4 Functionality...
Page 56: ...5 Product Handling...
Page 69: ...6 Installation...
Page 81: ...7 Commissioning...
Page 84: ...8 Operation...
Page 99: ...99 Figure 76 Settings uploading wizard...
Page 100: ...9 Maintenance and Troubleshooting...
Page 114: ...114 Figure 90 Securing the trip hook shaft against rotation...
Page 115: ...10 Product Coding...
Page 122: ...11 Appendices...
Page 128: ...128 Appendix 4 Recloser Control Drawings Figure 99 Dimensions of RC5_4...
Page 133: ...133 Figure 106 Dimensions of standard OSM mounting kit arrangement for lateral installation...
Page 134: ...134 Figure 107 Dimensions of interface bracket...
Page 135: ...135 Figure 108 Dimensions of OSM mounting kit with M16 pole interface front installation...
Page 136: ...136 Figure 109 Dimensions of OSM mounting kit with M16 pole interface lateral installation...
Page 137: ...137 Figure 110 Dimensions of OSM mounting kit with M20 pole interface front installation...
Page 138: ...138 Figure 111 Dimensions of OSM mounting kit with M20 pole interface lateral installation...
Page 149: ...149 Figure 122 Dimensions of OSM substation mounting kit...
Page 152: ...152 Figure 125 Dimensions of RC mounting kit for through the pole installation...
Page 153: ...153 Figure 126 Dimensions of RC substation mounting kit...
Page 154: ...154 Figure 127 Dimensions of VT mounting kit One VT holder...
Page 163: ...163 Appendix 8 Connectors Drawings Figure 141 Dimensions of aerial connector...
Page 164: ...164 Figure 142 Dimensions of bird guards for aerial connector...
Page 165: ...165 Figure 143 Dimensions of two hole NEMA connector...
Page 166: ...166 Figure 144 Dimensions of bird guards for two hole NEMA connector...
Page 167: ...167 Figure 145 Dimensions of four hole NEMA connector...
Page 168: ...168 Figure 146 Dimensions of bird guards for four hole NEMA connector...
Page 169: ...169 Figure 147 Dimensions of Burndy NEMA connector...
Page 170: ...170 Appendix 9 Recloser Control Wiring Diagram Figure 148 RC5_4 wiring diagram...
Page 172: ......