80
With help of the CBmount_CM_1 the CM can be mounted on a DIN rail in the low voltage compartment of a
Switchgear. There are two variants of the CM installation available.
Figure 144
Variants of the CM installation on the DIN rail
The CM can operate in any mounting position. Care must be taken for good access and visibility of the
terminals, LEDs.
Figure 145
Installation to CM terminals
Wires are connected to the CM terminals by using a screwdriver (Figure 22). The terminals can accept solid
and stranded wire within the range 0.5-2.5 mm. The insulation stripping length shall be 6-10 mm. Insulated
auxiliary circuits shall provide 2 kV power frequency dielectric strength.
Installation of secondary cables between ISM and CM
Before connection CM to ISM the compliance between ISM type (shown on ISM serial number plate
– Figure
2) and CM (applicability of CM for particular type of ISM are shown on CM designation label
– Figure 4 and
CM packing label - Figure 21) shall be confirmed.
Warning! If the CM label does not show the correct ISM type connection shall not be established. It can lead
to damage of the ISM. Contact your nearest Tavrida Electric partner for replacement.
Secondary cables between ISM and CM shall be installed according to the following instructions (
–
Figure 149). To achieve best possible protection against electromagnetic influences. The earthing point 3
shall be as close as possible to the CM. Unshielded parts of wires shall be not longer than 10 cm. Connections
between the end of cable shields and ISM earthing points shall be not longer than 5 cm.
Summary of Contents for VCB Series
Page 1: ...COMPATIBLE SERIES USER GUIDE...
Page 2: ......
Page 4: ......
Page 5: ...1 Product description...
Page 13: ...13 2 Nameplates and seals...
Page 18: ...18 3 Product handling...
Page 37: ...4 Installation...
Page 87: ......
Page 88: ...5 Commissioning...
Page 94: ...94 Figure 155 The connection points of the contact resistance meter...
Page 95: ......
Page 96: ...6 Operation...
Page 100: ...7 Maintenance and troubleshooting...
Page 105: ......
Page 106: ...8 Disposal...
Page 109: ...109 Appendix 2 Overall Drawings...
Page 112: ...112 ISM15_LD_3 Weight 13 kg ISM15_LD_6 PCD 133 mm Weight 55 kg...
Page 113: ...113 ISM15_LD_8 PCD 210 mm Weight 26 kg...
Page 114: ...114 ISM15_MD_1 150_L PCD 150 mm Weight 33 kg ISM15_MD_1 210_L PCD 210 mm Weight 35 kg...
Page 115: ...115 ISM15_MD_3 Weight 13 kg ISM15_Shell_2 150_L PCD 150 mm Weight 51 kg...
Page 120: ...120 ISM15_HD_1 275 PCD 275 mm Weight 72 kg ISM25_LD_1 210_Par2 PCD 210 mm Weight 36 kg...
Page 123: ...123 ISM25_LD_2 2 PCD 150 mm Weight 37 kg ISM25_LD_3 Weight 14 kg...
Page 125: ...125 Dimensions of Control Module CM_16_1 Par1_Par2_Par3_Par4_Par5 Weight 1 kg...
Page 127: ...127 Dimensions of Interlocking Kits CBkit_Interlock_1 CBkit_Interlock_3...
Page 128: ...128 CBkit_Interlock_4 CBkit_Interlock_5...
Page 129: ...Appendix 3 Secondary Schemes...
Page 130: ...130...
Page 131: ...131...
Page 132: ...132...
Page 133: ...133...
Page 134: ...134...
Page 135: ...135...
Page 136: ...136...
Page 137: ...137...
Page 138: ...138...
Page 139: ...139...
Page 140: ...140...
Page 142: ...Bartlett...