background image

9

  

English

L-2066 Operation

Using The Humidity
Control Routine

 

 

When engaged, the SMX humidity control routine automati-
cally turns the air conditioning system on at timed intervals
to remove moisture from the air. The system is pro-
grammed at the factory for average values. To change the
factory settings, see “Humidity Control Program”.

To start the dehumidification program:

• Press OFF.

• Press COOL, HEAT and FAN keys simultaneously.

For the SMXir Remote Control only 

- Press the

Dehumid key to enter dehumidification mode.

• The data display will flash HU, indicating that the

program is active.

• To halt the dehumidification program, press any key.  The

HU message will stop flashing.

Safety Note

Whenever the SMX system is in the dehumidification mode,
all of the system safeguard controls remain active. If the
seawater flow fails or if line voltage falls below preset limits,
the system will automatically shut down. If AC power is in-
terrupted, the system will automatically resume operation in
the dehumidification mode when power is restored.

Anti-Ice Routine

The SMX control will occasionally shut down the compres-
sor in the cooling mode to allow any ice that may have
formed on the evaporator coil to melt. The anti-ice shut-
down only occurs at inside temperatures lower than 70°F
(21°C).

In a 10-minute cycle period, the compressor will shut off for
15 seconds per degree below 70°F. For example, if the
inside temperature is 67°F, the compressor will shut off for
45 seconds every 10 minutes.

Seawater Temperature and
Your Cruisair System

The basic principle behind an air conditioner or a heat
pump is the movement of heat. In an air conditioner, heat is
removed from the inside cabin and released to the seawa-
ter. In reverse-cycle heating, the refrigerant flow is reversed
and heat is extracted from the seawater and discharged
into the living space. The efficiency of the system operation
depends on both the seawater and cabin temperatures.

In cooling, the air conditioner will work best in seawater
temperatures below 90°F (32°C). At higher water tempera-
tures, the unit may work, but at reduced capacity. A high-
pressure shutdown can occur at higher water temperatures.

In heat mode, the opposite is true. As the water gets colder,
there is less heat available, and the heating performance
drops. Full heating capacity is obtained at about 55°F
(13°C). Performance drops to about 50% of rated capacity
in 40°F (4.4°C) water. Below this, the system pressure can
be so low that the unit will shut down on low-pressure fault.
This problem is compounded when the cabin is cold also.
The low pressure shutdown routine is such that the unit will
try many times to heat up the cabin enough to raise system
pressure and continue running.

Warning

Do not operate your A/C unit in water that is colder
than 38°F (3.3°C). Doing so could lead to water
freezing in the condenser coil which can cause
damage to the unit.

Programming the SMX II System

SMX control systems are programmed at the factory for
average values. For optimum performance, you may wish to
change these settings to suit your individual preferences.

All programming steps are entered by pressing the OFF
key, followed by the SET key, then simultaneously depress-
ing the two or three keys noted in the table below. Success-
ful entry into a programming mode is indicated by the
presence of a decimal point to the right of the two displayed
characters. To raise or lower a value, touch the UP or
DOWN keys. To exit the programming mode, touch the OFF
key. (The SMXir Remote Control can not be used to
program the system.)

Factory Memory Reset

 

 

You can use the memory-reset sequence to restore all
programmed functions to the factory default settings.

To restore programmed functions to factory setting:

• Press OFF, SET and FAN simultaneously.

• Press SET.

• After a delay, the memory will be reset from stored

values. After another delay, the display will come back on
normally.

Summary of Contents for Cruisair SMX II

Page 1: ...SMX II Control Systems DX English INSTALLATION OPERATION Revised 12 17 02 L 2066 LP 11 DIRECT EXPANSION SYSTEMS For Direct Expansion SMX II Control Systems using these displays...

Page 2: ...Anti Ice Routine 9 Seawater Temperature and Your Cruisair System 9 Programming the SMX II System 9 Factory Memory Reset 9 Programming Summary Table 10 Custom Programming Record 10 Compressor Time Del...

Page 3: ...y different parts required for a complete installation so make sure that you have all the necessary items when installing the system Two different keypad displays are available for use with SMX II con...

Page 4: ...integrated SMX II controls have the P L box already installed on the unit In selecting a location for the Power Logic box bear in mind that several sets of wires will be connected to it Refer to insta...

Page 5: ...dard phone cable will not work with SMX controls Pressure Switches retrofit only Standard SX and FX units that have an integrated SMX II P L box include both the high and low pressure switches already...

Page 6: ...Mode Indicator Lights when you press the COOL key to select the cooling mode 10 Heat Mode Indicator Lights when you press the HEAT key to select the heating mode 11 COOL Key Turns the system on in th...

Page 7: ...he SMXir remote also has two quick hit buttons that allow easy access to the humidity control program and the automatic changeover mode The remote has three buttons that are not used on SMX II systems...

Page 8: ...ressor is running When the compressor cycles off the Cooling Indicator goes off but the Cool Mode Indicator stays on Heat Mode Press the HEAT key to select HEAT Mode The Heat Mode Indicator will light...

Page 9: ...he efficiency of the system operation depends on both the seawater and cabin temperatures In cooling the air conditioner will work best in seawater temperatures below 90 F 32 C At higher water tempera...

Page 10: ...Compressor Differential SLOW FAN 12 4 to 24 Fan Response Differential COOL SLOW 4 2 to 8 SLOW FAN FAST Before 8 98 Low Fan Speed DOWN SET 32 30 to 56 High Fan Speed SET SLOW 60 41 to 90 Fan Mode Cont...

Page 11: ...2 1 5 The compressor differential is the temperature change needed for the compressor to cycle on and off The factory setting of 1 5 Fahrenheit should be adequate for most applications Differential se...

Page 12: ...actory default is 60 While listening to the fan noise level use the UP key to raise the displayed value past the point that you can hear an increase in the fan noise level Press the DOWN key to lower...

Page 13: ...le 10 min Dehumidification cycle 30 min The factory settings are adequate for most moderate climates and boats For humid climates you may wish to shorten the overall time period and extend the dehumid...

Page 14: ...he display will flash LO AC for low AC This is a sustained shutdown and the system will not resume operation even if the line voltage rises to normal levels To reset press the OFF key Fault Shutdowns...

Page 15: ...are number Press OFF Press OFF SET and FAN simultaneously Press COOL twice until display reads 68 Press UP once The display should read Version Number Press SLOW until display reads F2 Press UP once T...

Page 16: ...those expressly authorized herein TME shall not be responsible for any liability or expense except as is specifically autho rized and provided in this section TME reserves the right to improve its pro...

Page 17: ...dry and checked periodically for electrical leakage If any electrical leakage is detected the component should be replaced or the fault causing the leakage corrected before the component is put back i...

Page 18: ...cluding Parts and Labor Cruisair Tempered Water New complete system installation using any member of the SMX family 2 year warranty including Parts and Labor NOTE Excludes pump which has a 1 year warr...

Page 19: ...460V 3Ph 50 60 Hz Dwg No 084901 P1050 Fig 6 SMX II Retrofit Typ 3 knob Dwg No 084001 P 1063 A 284 Fig 7 SMX II Retrofit F20C 48RC to 3 knob term strip Dwg No 082605 P 1065 A 279 Fig 8 SMX II Retrofit...

Page 20: ...20 L 2066 Fig 1 SXR7 16CK 115 230V 50 60Hz...

Page 21: ...21 L 2066 Fig 2 SX7 24CK 115 230V 50 60Hz...

Page 22: ...22 L 2066 Fig 3 FX5 36CK 115 230V 50 60Hz...

Page 23: ...23 L 2066 Fig 4 FX48RC 230V 50 60 Hz...

Page 24: ...24 L 2066 Fig 5 FX20DC FX48EC 230V 460V 3Ph 50 60Hz...

Page 25: ...25 L 2066 Fig 6 SMXII Retrofit Typical 3 knob...

Page 26: ...26 L 2066 Fig 7 SMXII Retrofit F20C 48RC to 3 knob term strip...

Page 27: ...27 L 2066 Fig 8 SMXII Retrofit F20C 48RC to condensing unit...

Page 28: ...28 L 2066 Fig 9 Cable Diagrams Old and New P L Boards...

Page 29: ...29 L 2066 Fig 10 SMXIR Mounting Template and Instructions...

Page 30: ...or SMXIRB F SMXIR Keypad Display Black Full Door SMXIRW F SMXIR Keypad Display White Full Door SMXIR REM SMXIR Remote Control 5103400 Replacement Full Door for SMXIRB Black 5103400W Replacement Full D...

Page 31: ...il info wardsmarine com Cruisair Suncoast Inc Location St Petersburg FL USA Territory Tampa St Petersburg and surrounding areas Phone 727 526 7875 Fax 727 528 9519 Email cruisairsuncoast aol com Kansa...

Page 32: ...Fax 242 356 5271 Email rolandknowles bahamas net bs Bahrain International Agencies Location Manama Bahrain Phone 973 728691 Fax 973 728412 Email service intercol com Benelux ASA Boot Electro BV Locati...

Page 33: ...espolo Cinzia C Sne Location Bevazzana de Latisana UD Italy Territory Northeast Italy Austria Croatia Slovenia Phone 390 431 53 644 Fax 390 431 53 460 Email nautica centis nauticacentis it Web www nau...

Page 34: ...65 6861 1188 Fax 65 6861 4263 Email tritex pacific net sg Web www tritex com sg Slovenia Nautica Centis di Nespolo Cinzia C Sne Location Bevazzana de Latisana UD Italy Territory Northeast Italy Austr...

Page 35: ...ne 758 452 0205 Fax 758 452 0206 Email stlucia regiselectronics com Zambia Southern Power Products Location Cape Town South Africa Territory Angola Botswana Mozambique Nambia S Africa Zambia Zimbabwe...

Page 36: ...enviro va com www tmenviro com Taylor Made is a registered trademark of Nelson A Taylor Co Inc the Taylor Made Group Logo is a trademark of Taylor Made Group Inc the Cruisair logo is a registered trad...

Reviews: