ES100 ESS Unit user manual
9
3. Installation and Configuration
3.1 Ready for installation
Safety Requirement
This system can only be installed by personnel who have been trained on the power supply system
and have sufficient knowledge of the power system.
The safety regulations and local safety regulations listed below should always be followed during
the installation.
All circuits connected to this power system with an external voltage of less than 48V must meet
the SELV requirements defined in the IEC60950 standard.
If operating within the power system cabinet, make sure the power system is not charged.
Battery devices should also be switched off.
Distribution cable wiring should be reasonable and has the protective measures to avoid
touching these cables while operating power equipment.
The following protective equipment must be worn when installing the battery system:
Protective gloves Safety goggles Protective shoes
Figure 3-1
3.1.1 Environmental requirements
Working temperature
:﹣
20
℃
~55
℃
Charging temperature range is 0
℃
~55
℃
Discharging temperature range is -20
℃
~55
℃
Storage temperature
:
0
℃
~35
℃
Relative humidity
:
15%~90%
Elevation
:
86 kPa-106 kPa
Operating environment: It needs to be installed indoors. The installation location needs to be
protected from sunlight, no wind, no conductive dust and no corrosive gas.
And the following conditions should be met:
Installation location should be away from the sea to avoid brine and high humidity environment.
The ground is flat and horizontal.
There are no flammable explosive articles near to the installation places.
The optimal ambient temperature is 15
℃
~ 30
℃
.
Keep away from dust and messy zones.
Summary of Contents for ES100
Page 1: ...1 ...
Page 2: ...1 ES100 ESS Unit User Manual ...
Page 24: ...ES100 ESS Unit user manual 18 ...