RAYTHON User Manual V1.0
4.5 Wiring Recommendation
Please find the following minimum wire size. In case of DC cable longer than 1m, please increase
the cross section of the cable to reduce the loss.
Cable Size
Circuit Breaker
AC in input
10mm²
50A
AC output
6mm²
32A
PV input
16mm²
55A
AGS cable
1 mm²
-
4.6 Connection Terminal Description
Item
Name
Description
Label
Comments
1
Relay1
Connect to
generator start
control port
NO
C
2
Relay2
Connect to
generator start
control port
NO
C
3
AC in
Connect to the grid AC input
L
Line
N
Neural
4
AC Out1
General load without being
protected by installed MCB
L
Line
N
Neural
5
AC Out2
General load without being
protected by installed MCB
N
Neural
L
Line
6
PV in
Loads controlled being
+
Positive